Specifications Table for RKXYQ-TA

RKXYQ5TAY1B
Dimensions Unit Height mm 701
    Width mm 760
    Depth mm 554
Weight Unit kg 105
Compressor Type   G-type scroll compressor
Sound power level Cooling Nom. dBA 64 (4)
Sound pressure level Cooling Nom. dBA 48 (5)
Refrigerant Type   R-410A
  GWP   2,087.5
  Charge TCO2Eq 8.35
  Charge kg 4.00
Standard Accessories Installation and operation manual 1
  Connection pipes 5
  Declaration of conformity 1
  Refrigerant label for F-gas regulation 1
  Tie-wraps 3
  Screws 1
Power supply Name   Y1
  Phase   3N~
  Frequency Hz 50
  Voltage V 380-415
Notes Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. Data for standard efficiency series
  Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. Data for standard efficiency series
  Actual number of units depends on the indoor unit type (VRV DX indoor, etc.) and the connection ratio restriction for the system (being; 50% ≤ CR ≤ 130%).
  The sound power level is an absolute value indicating the power which a sound source generates.
  Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to sound level drawings. Nominal air flow rate, ESP 60 Pa.
  Refer to refrigerant pipe selection or installation manual
  In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value
  Sound values are measured in a semi-anechoic room.
  Contains fluorinated greenhouse gases