Specifications Table for EPVX14A9W / EPSK12-14AW1

EPVX14S18AJ9W / EPSK12ARW1 EPVX14S23AJ9W / EPSK12ARW1 EPVX14S18AJ9W / EPSK14ARW1 EPVX14S23AJ9W / EPSK14ARW1
Indoor unit EPVX14S18AJ9W EPVX14S23AJ9W EPVX14S18AJ9W EPVX14S23AJ9W
Heating capacity Nom. kW 10.2 (1) 10.2 (1) 10.2 (1) 10.2 (1)
  Max. kW 11.99 (2) 11.99 (2) 13.34 (2) 13.34 (2)
Cooling capacity Nom. kW 9.37 (3), 6.74 (4) 9.37 (3), 6.74 (4) 11.3 (3), 6.74 (4) 11.3 (3), 6.74 (4)
Power input Heating Nom. kW 1.86 (1) 1.86 (1) 1.86 (1) 1.86 (1)
    Max. kW 3.51 (5) 3.51 (5) 3.98 (5) 3.98 (5)
  Cooling Nom. kW 2.64 (3), 1.12 (4) 2.64 (3), 1.12 (4) 3.45 (3), 1.12 (4) 3.45 (3), 1.12 (4)
  Domestic hot water from 10°C to 50°C Nom. kWh 2.24 2.54 2.24 2.54
Heat up time from 10°C to 50°C hr 1h 17min 1h 30min 1h 17min 1h 30min
COP 5.50 (1) 5.50 (1) 5.50 (1) 5.50 (1)
EER 3.55 (3), 6.04 (4) 3.55 (3), 6.04 (4) 3.28 (3), 6.04 (4) 3.28 (3), 6.04 (4)
Domestic hot water heating General Declared load profile   L L L L
  Average climate Water heating energy efficiency class   A+ A+ A+ A+
Space heating Average climate water outlet 55°C General SCOP   4.04 4.04 3.84 3.84
      Seasonal space heating eff. class   A+++ A+++ A+++ A+++
  Average climate water outlet 35°C General SCOP   5.14 5.14 4.96 4.96
      Seasonal space heating eff. class   A+++ A+++ A+++ A+++
Notes (1) - Condition: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) (1) - Condition: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) (1) - Condition: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) (1) - Condition: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C)
  (2) - Capacity according to standard EN14511 and valid for heated water range dT = 3~8°C at Ta 7°C (2) - Capacity according to standard EN14511 and valid for heated water range dT = 3~8°C at Ta 7°C (2) - Capacity according to standard EN14511 and valid for heated water range dT = 3~8°C at Ta 7°C (2) - Capacity according to standard EN14511 and valid for heated water range dT = 3~8°C at Ta 7°C
  (3) - Cooling: EW 12°C; LW 7°C; ambient conditions: 35°CDB (3) - Cooling: EW 12°C; LW 7°C; ambient conditions: 35°CDB (3) - Cooling: EW 12°C; LW 7°C; ambient conditions: 35°CDB (3) - Cooling: EW 12°C; LW 7°C; ambient conditions: 35°CDB
  (4) - Cooling: EW 23°C; LW 18°C; ambient conditions: 35°CDB (4) - Cooling: EW 23°C; LW 18°C; ambient conditions: 35°CDB (4) - Cooling: EW 23°C; LW 18°C; ambient conditions: 35°CDB (4) - Cooling: EW 23°C; LW 18°C; ambient conditions: 35°CDB
  (5) - Power input is total input of indoor and outdoor units, including the circulation pump; according to EN14511 (5) - Power input is total input of indoor and outdoor units, including the circulation pump; according to EN14511 (5) - Power input is total input of indoor and outdoor units, including the circulation pump; according to EN14511 (5) - Power input is total input of indoor and outdoor units, including the circulation pump; according to EN14511