| ERA100A7V1B | ERA125A7V1B | ERA140A7V1B | |||||
|---|---|---|---|---|---|---|---|
| Cooling capacity | Nom. | 35°CDB | kW | 12.1 (1) | 14 | 15.5 (1) | |
| Heating capacity | Nom. | 6°CWB | kW | 12.1 (2) | 14 | 15.5 (2) | |
| SEER | 8.2 (3) | 7.7 (3) | 7.6 (3) | ||||
| SCOP | 5.1 (3) | 4.7 (3) | 4.7 (3) | ||||
| Indoor index connection | Min. | 63 | 100 | 100 | |||
| Max. | 100 | 125 | 140 | ||||
| Dimensions | Unit | Height | mm | 869 | 869 | 869 | |
| Width | mm | 1100 | 1100 | 1100 | |||
| Depth | mm | 460 | 460 | 460 | |||
| Weight | Unit | kg | 102 | 102 | 102 | ||
| Fan | External static pressure | Max. | Pa | 45 | 45 | 45 | |
| Compressor | Type | Hermetically sealed swing compressor | Hermetically sealed swing compressor | Hermetically sealed swing compressor | |||
| Operation range | Cooling | Min. | °CDB | -5 | -5 | -5 | |
| Max. | °CDB | 46 | 46 | 46 | |||
| Heating | Min. | °CWB | -20 | -20 | -20 | ||
| Max. | °CWB | 15.5 | 15.5 | 15.5 | |||
| Sound power level | Cooling | Nom. | dBA | 67 | 68.1 (4) | 69 | |
| Sound pressure level | Cooling | Nom. | dBA | 49 | 51 | 51 | |
| Refrigerant | Type | R-32 | R-32 | R-32 | |||
| GWP | 675 | 675 | 675 | ||||
| Charge | tCO2Eq | 2.3 | 2.3 | 2.3 | |||
| Charge | kg | 3.4 | 3.4 | 3.4 | |||
| Piping connections | Liquid | Type | Braze connection | Braze connection | Braze connection | ||
| OD | mm | 9.52 | 9.52 | 9.52 | |||
| Gas | Type | Braze connection | Braze connection | Braze connection | |||
| OD | mm | 15.9 | 15.9 | 15.9 | |||
| Total piping length | System | Actual | m | 50 (6) | 50 (6) | 50 (6) | |
| Level difference | OU - IU | Outdoor unit in highest position | m | 50 | 50 | 50 | |
| Indoor unit in highest position | m | 40 | 40 | 40 | |||
| Standard Accessories | Auxiliary piping set | 1 | 1 | 1 | |||
| Installation and operation manual | 1 | 1 | 1 | ||||
| Power supply | Name | V1 | V1 | V1 | |||
| Phase | 1~ | 1~ | 1~ | ||||
| Frequency | Hz | 50 | 50 | 50 | |||
| Voltage | V | 220-240 | 220-240 | 220-240 | |||
| Notes | (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m | (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m | (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m | ||||
| (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m | (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m | (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m | |||||
| (3) - Defined for a system capacity ratio of 100% ± 5%, configured for complete air recirculation applications. | (3) - Defined for a system capacity ratio of 100% ± 5%, configured for complete air recirculation applications. | (3) - Defined for a system capacity ratio of 100% ± 5%, configured for complete air recirculation applications. | |||||
| (4) - Sound power level is an absolute value that a sound source generates. | (4) - Sound power level is an absolute value that a sound source generates. | (4) - Sound power level is an absolute value that a sound source generates. | |||||
| (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. | (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. | (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. | |||||
| (6) - Refer to refrigerant pipe selection or installation manual | (6) - Refer to refrigerant pipe selection or installation manual | (6) - Refer to refrigerant pipe selection or installation manual | |||||
| (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB | (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB | (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB | |||||
| (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. | (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. | (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. | |||||
| (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value | (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value | (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value | |||||
| (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. | (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. | (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. | |||||
| (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). | (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). | (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). | |||||
| (12) - TOCA means the total value of each OC set. | (12) - TOCA means the total value of each OC set. | (12) - TOCA means the total value of each OC set. | |||||
| (13) - FLA means the nominal running current of the fan | (13) - FLA means the nominal running current of the fan | (13) - FLA means the nominal running current of the fan | |||||
| (14) - For AHU HEX volume limitations, refer to the engineering data book or installation manual | (14) - For AHU HEX volume limitations, refer to the engineering data book or installation manual | (14) - For AHU HEX volume limitations, refer to the engineering data book or installation manual | |||||
| (15) - For detailed contents of standard accessories, see installation/operation manual | (15) - For detailed contents of standard accessories, see installation/operation manual | (15) - For detailed contents of standard accessories, see installation/operation manual | |||||