Specifications Table for EWAT-B-SL

EWAT085B-SLA1 EWAT115B-SLA1 EWAT115B-SLB1 EWAT135B-SLA1 EWAT135B-SLB1 EWAT155B-SLA2 EWAT155B-SLB2 EWAT175B-SLA1 EWAT175B-SLB1 EWAT195B-SLA2 EWAT195B-SLB2 EWAT205B-SLA2 EWAT205B-SLB2 EWAT215B-SLA1 EWAT215B-SLB1 EWAT240B-SLA2-VFDFAN EWAT240B-SLA2 EWAT240B-SLB2-VFDFAN EWAT240B-SLB2 EWAT260B-SLA2-VFDFAN EWAT260B-SLA2 EWAT260B-SLB2-VFDFAN EWAT260B-SLB2 EWAT290B-SLA1-VFDFAN EWAT290B-SLA1 EWAT290B-SLB1-VFDFAN EWAT290B-SLB1 EWAT310B-SLA2-VFDFAN EWAT310B-SLA2 EWAT310B-SLB2 EWAT310B-SLB2-VFDFAN EWAT330B-SLA2-VFDFAN EWAT330B-SLA2 EWAT330B-SLB2-VFDFAN EWAT330B-SLB2 EWAT340B-SLA1-VFDFAN EWAT340B-SLA1 EWAT340B-SLB1-VFDFAN EWAT340B-SLB1 EWAT350B-SLA2-VFDFAN EWAT350B-SLA2 EWAT350B-SLB2-VFDFAN EWAT350B-SLB2 EWAT420B-SLA2-VFDFAN EWAT420B-SLB2-VFDFAN EWAT420B-SLA2 EWAT420B-SLB2 EWAT460B-SLA2-VFDFAN EWAT460B-SLA2 EWAT460B-SLB2-VFDFAN EWAT460B-SLB2 EWAT510B-SLA2-VFDFAN EWAT510B-SLA2 EWAT510B-SLB2-VFDFAN EWAT510B-SLB2 EWAT570B-SLA2-VFDFAN EWAT570B-SLA2 EWAT570B-SLB2-VFDFAN EWAT570B-SLB2 EWAT610B-SLA2-VFDFAN EWAT610B-SLA2 EWAT610B-SLB2-VFDFAN EWAT610B-SLB2 EWAT670B-SLA2-VFDFAN EWAT670B-SLA2 EWAT670B-SLB2-VFDFAN EWAT670B-SLB2
Sound pressure level Cooling Nom. dBA 66.3 68.5 68.5 (1) 69.3 69.3 (1) 68.4 68.4 (1) 70.7 70.7 (1) 69.5 69.5 (1) 70.1 70.1 (1) 71.6 71.6 (1) 71.8 71.8 71.8 (1) 71.8 (1) 71.8 71.8 71.8 (1) 71.8 (1) 72 72 72 (1) 72 (1) 72.3 72.3 72.3 (1) 72.3 (1) 72.4 72.4 72.4 (1) 72.4 (1) 73.2 73.2 73.2 (1) 73.2 (1) 72.4 72.4 72.4 (1) 72.4 (1) 73.3 73.3 (1) 73.3 73.3 (1) 73.4 73.4 73.4 (1) 73.4 (1) 74 74 74 (1) 74 (1) 74 74 74 (1) 74 (1) 74.1 74.1 74.1 (1) 74.1 (1) 74.6 74.6 74.6 (1) 74.6 (1)
Operation range Air side Cooling Min. °CDB -10 -10   -10   -10   -10   -10   -10   -10   -18 -18     -18 -18     -18 -18     -18 -18     -18 -18     -18 -18     -18 -18     -18   -18   -18 -18     -18 -18     -18 -18     -18 -18     -18 -18
      Max. °CDB 43 43   43   43   43   43   43   43   43 43     43 43     43 43     43 43     43 43     43 43     43 43     43   43   43 43     43 43     43 43     43 43     43 43
  Water side Cooling Max. °CDB 20 20   20   20   20   20   20   20   20 20     20 20     20 20     20 20     20 20     20 20     20 20     20   20   20 20     20 20     20 20     20 20     20 20
      Min. °CDB -13 -13   -13   -13   -13   -13   -13   -13   -13 -13     -13 -13     -13 -13     -13 -13     -13 -13     -13 -13     -13 -13     -13   -13   -13 -13     -13 -13     -13 -13     -13 -13     -13 -13
Compressor Type   Driven vapour compression Driven vapour compression Scroll compressor Driven vapour compression Scroll compressor Driven vapour compression Scroll compressor Driven vapour compression Scroll compressor Driven vapour compression Scroll compressor Driven vapour compression Scroll compressor Driven vapour compression Scroll compressor Driven vapour compression Driven vapour compression Scroll compressor Scroll compressor Driven vapour compression Driven vapour compression Scroll compressor Scroll compressor Driven vapour compression Driven vapour compression Scroll compressor Scroll compressor Driven vapour compression Driven vapour compression Scroll compressor Scroll compressor Driven vapour compression Driven vapour compression Scroll compressor Scroll compressor Driven vapour compression Driven vapour compression Scroll compressor Scroll compressor Driven vapour compression Driven vapour compression Scroll compressor Scroll compressor Driven vapour compression Scroll compressor Driven vapour compression Scroll compressor Driven vapour compression Driven vapour compression Scroll compressor Scroll compressor Driven vapour compression Driven vapour compression Scroll compressor Scroll compressor Driven vapour compression Driven vapour compression Scroll compressor Scroll compressor Driven vapour compression Driven vapour compression Scroll compressor Scroll compressor Driven vapour compression Driven vapour compression Scroll compressor Scroll compressor
  Starting method       Direct on line   Direct on line   Direct on line   Direct on line   Direct on line   Direct on line   Direct on line               Direct on line                       Direct on line       Direct on line       Direct on line       Direct on line       Direct on line       Direct on line               Direct on line       Direct on line
  Quantity   2 2 2 2 2 4 4 2 2 4 4 4 4 2 2 4 4 4 4 4 4 4 4 3 3 3 3 4 4 4 4 4 4 4 4 3 3 3 3 4 4 4 4 4 4 4 4 5 5 5 5 5 5 5 5 6 6 6 6 6 6 6 6 6 6 6 6
Weight Operation weight kg 696 783 783 830 830 1,035 1,035 1,006 1,006 1,198 1,198 1,190 1,190 1,210 1,210 1,822 1,822 1,826 1,826 1,849 1,849 1,853 1,853 1,951 1,951 2,020 2,020 2,268 2,268 2,308 2,308 2,296 2,296 2,336 2,336 2,350 2,350 2,454 2,454 2,324 2,324 2,364 2,364 2,784 2,852 2,784 2,852 2,954 2,954 3,094 3,094 3,111 3,111 3,251 3,251 3,360 3,360 3,526 3,526 3,762 3,762 3,960 3,960 4,089 4,089 4,321 4,321
  Unit kg 689 773 777 820 821 1,026 1,028 993 994 1,185 1,187 1,177 1,179 1,191 1,194 1,815 1,815 1,815 1,815 1,843 1,843 1,842 1,842 1,935 1,935 2,004 2,004 2,251 2,251 2,289 2,289 2,277 2,277 2,317 2,317 2,330 2,330 2,434 2,434 2,304 2,304 2,345 2,345 2,754 2,824 2,754 2,824 2,921 2,921 3,066 3,066 3,078 3,078 3,223 3,223 3,312 3,312 3,484 3,484 3,718 3,718 3,918 3,918 4,053 4,053 4,279 4,279
Air heat exchanger Type   Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel
EER 2.55 2.82 2.83 2.64 2.64 2.55 2.55 2.58 2.58 2.75 2.75 2.63 2.63 2.53 2.53 2.81 2.82 2.83 2.83 2.71 2.71 2.73 2.73 2.61 2.61 2.62 2.62 2.71 2.71 2.72 2.72 2.69 2.7 2.7 2.71 2.91 2.92 2.93 2.94 2.64 2.64 2.65 2.65 2.82 2.83 2.83 2.84 2.71 2.72 2.73 2.73 2.74 2.74 2.76 2.76 2.61 2.61 2.62 2.63 2.64 2.64 2.66 2.66 2.77 2.78 2.8 2.8
ESEER 3.96 4.03   3.86   3.83   4.09   4   3.94   3.85   4 3.94     3.86 3.76     4.09 3.99     4.09 4.02     4.01 3.97     4.21 4.06     3.98 3.91     4.14   4.09   4.13 4     4.06 3.97     4.03 4.03     4.08 4.01     4.11 3.98
Refrigerant GWP   675 675   675   675   675   675   675   675   675 675 675   675 675 675   675 675 675   675 675   675 675 675 675   675 675 675   675 675 675   675 675 675   675 675 675   675 675 675   675 675 675   675 675 675   675 675 675
  Type   R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32
  Circuits Quantity   1 1   1   2   1   2   2   1   2 2 2 2 2 2 2   1 1 1 1 2 2 2 2 2 2 2   1 1 1   2 2 2   2 2 2   2 2 2   2 2 2   2 2 2 2 2 2 2   2 2 2
  Charge kg 10 11 8.2 12.5 8.4 15 12.4 14 10.7 18 14 18 13.4 17 12.7 36 36 19 19 38 38 19 18 36 36 19 19 42 42 25.5 25.5 43 43 25 26.5 50 50 26 27 44 44 24 24.3 57 34.5 57 34.3 58 58 36 36.1 60 60 41 39.7 62 62 42 42 80 80 46.5 45.5 90 90 52.5 55.5
Cooling capacity Nom. kW 80.92 108.73 109 131.2 131 157.55 158 174.49 175 190.91 191 209.86 211 216.55 217 240.44 240.44 241 241 259.39 259.39 261 261 281.85 281.85 283 283 305.6 305.6 306 306 328.59 328.59 330 330 342 342 344 344 348.88 348.88 350 350 414.98 416 414.98 416 465.75 465.75 468 468 511.1 511.1 513 513 564.43 564.43 567 567 609.05 609.05 612 612 664.62 664.62 668 668
Water heat exchanger Water volume l 5 6   9   7   12   11   11   16   11 11 11 11 11 11 11   16 16 16 16 19 19 19 19 19 19 19   20 20 20   19 19 19   28 28 28   28 28 28   28 28 28   42 42 42 42 42 42 42   42 42 42
  Type   Brazed plate Brazed plate   Brazed plate   Brazed plate   Brazed plate   Brazed plate   Brazed plate   Brazed plate   Brazed plate Brazed plate Brazed plate Brazed plate Brazed plate Brazed plate Brazed plate   Brazed plate Brazed plate Brazed plate Brazed plate Brazed plate Brazed plate Brazed plate Brazed plate Brazed plate Brazed plate Brazed plate   Brazed plate Brazed plate Brazed plate   Brazed plate Brazed plate Brazed plate   Brazed plate Brazed plate Brazed plate   Brazed plate Brazed plate Brazed plate   Brazed plate Brazed plate Brazed plate   Brazed plate Brazed plate Brazed plate Brazed plate Brazed plate Brazed plate Brazed plate   Brazed plate Brazed plate Brazed plate
Power input Cooling Nom. kW 31.8 38.5   49.8   61.8   67.7   69.4   79.8   85.6   85.5 85.3 85.4 85.2 95.7 95.7 95.6   108 108 108 108 112 112 113 112 122 121 122   117 117 117   132 132 132   147 146 146   171 171 171   186 186 186   216 216 216 216 230 230 230   239 239 238
Sound power level Cooling Nom. dBA 83.7 86.2 86.2 (1) 87 87 (1) 86.7 86.7 (1) 88.8 88.8 (1) 88.1 88.1 (1) 88.7 88.7 (1) 90 90 (1) 90.8 90.8 90.8 (1) 90.8 (1) 90.8 90.8 90.8 (1) 90.8 (1) 91 91 91 (1) 91 (1) 91.8 91.8 91.8 (1) 91.8 (1) 91.9 91.9 91.9 (1) 91.9 (1) 92.7 92.7 92.7 (1) 92.7 (1) 91.9 91.9 91.9 (1) 91.9 (1) 93.3 93.3 (1) 93.3 93.3 (1) 93.4 93.4 93.4 (1) 93.4 (1) 93.9 93.9 93.9 (1) 93.9 (1) 94 94 94 (1) 94 (1) 94.5 94.5 94.5 (1) 94.5 (1) 95.3 95.3 95.3 (1) 95.3 (1)
Dimensions Unit Width mm 1,204 1,204 1,204 1,204 1,204 1,204 1,204 1,204 1,204 1,204 1,204 1,204 1,204 1,204 1,204 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236
    Depth mm 2,120 2,660 2,660 2,660 2,660 3,570 3,570 3,180 3,180 4,170 4,170 4,170 4,170 3,780 3,780 2,326 2,326 2,326 2,326 2,326 2,326 2,326 2,326 2,326 2,326 2,326 2,326 3,226 3,226 3,226 3,226 3,226 3,226 3,226 3,226 3,226 3,226 3,226 3,226 3,226 3,226 3,226 3,226 4,126 4,126 4,126 4,126 4,126 4,126 4,126 4,126 4,126 4,126 4,126 4,126 4,126 4,126 4,126 4,126 5,025 5,025 5,025 5,025 5,874 5,874 5,874 5,874
    Height mm 1,801 1,801 1,801 1,801 1,801 1,822 1,822 1,801 1,801 1,822 1,822 1,822 1,822 1,822 1,822 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540
Capacity control Minimum capacity % 50 38 38 50 50 25 25 38 38 21 21 19 19 50 50 17 17 17 17 25 25 25 25 24 24 24 24 14 14 14 14 13 13 13 13 33 33 33 33 19 19 19 19 17 17 17 17 15 15 15 15 14 14 14 14 12 12 12 12 11 11 11 11 17 17 17 17
  Method   Staged Staged Step Staged Step Variable Step Staged Step Variable Step Variable Step Staged Step Variable Variable Step Step Variable Variable Step Step Variable Variable Step Step Variable Variable Step Step Variable Variable Step Step Variable Variable Step Step Variable Variable Step Step Variable Step Variable Step Variable Variable Step Step Variable Variable Step Step Variable Variable Step Step Variable Variable Step Step Variable Variable Step Step
Fan Air flow rate Nom. l/s 6,022 9,036   9,036   13,354   12,023   16,710   16,710   15,057   20,306 20,306 20,306 20,306 20,306 20,306 20,306   20,306 20,306 20,306 20,306 25,382 25,382 25,382 25,382 25,382 25,382 25,382   30,459 30,459 30,459   25,382 25,382 25,382   35,535 35,535 35,535   35,535 35,535 35,535   40,612 40,612 40,612   40,612 40,612 40,612 40,612 45,688 45,688 45,688   55,841 55,841 55,841
  Speed rpm 1,360 1,360   1,360   1,360   1,360   1,360   1,360   1,360   900 900 900 900 900 900 900   900 900 900 900 900 900 900 900 900 900 900   900 900 900   900 900 900   900 900 900   900 900 900   900 900 900   900 900 900 900 900 900 900   900 900 900
Compressor Starting method   Direct on line Direct on line   Direct on line   Direct on line   Direct on line   Direct on line   Direct on line   Direct on line   Direct on line Direct on line Direct on line Direct on line Direct on line Direct on line Direct on line   Direct on line Direct on line Direct on line Direct on line Direct on line Direct on line Direct on line Direct on line Direct on line Direct on line Direct on line   Direct on line Direct on line Direct on line   Direct on line Direct on line Direct on line   Direct on line Direct on line Direct on line   Direct on line Direct on line Direct on line   Direct on line Direct on line Direct on line   Direct on line Direct on line Direct on line Direct on line Direct on line Direct on line Direct on line   Direct on line Direct on line Direct on line
Power supply Phase   3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~
  Voltage range Max. %     10   10   10   10   10   10   10               10                       10       10       10       10       10       10               10       10
    Min. %     -10   -10   -10   -10   -10   -10   -10               -10                       -10       -10       -10       -10       -10       -10               -10       -10
  Frequency Hz 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
  Voltage V 400 400   400   400   400   400   400   400   400 400     400 400     400 400     400 400     400 400     400 400     400 400     400   400   400 400     400 400     400 400     400 400     400 400
Unit Max unit current for wires sizing A     107   104   144   176   204   200   184               208                       291       280       287       364       445       454               544       556
  Starting current Max A     313   324   284   462   384   395   498               420                       583       588       594       636       681       719               801       843
  Running current Cooling Nom. A     69   83   108   113   117   131   143               160                       206       196       219       237       285       310               381       398
    Max A     86   96   143   132   156   167   168               193                       254       258       265       307       351       389               471       513
Notes (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0
  (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only (2) - The value refers to the pressure drop in the evaporator only (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only (2) - The value refers to the pressure drop in the evaporator only (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only (2) - The value refers to the pressure drop in the evaporator only (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only (2) - The value refers to the pressure drop in the evaporator only (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only (2) - The value refers to the pressure drop in the evaporator only (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only (2) - The value refers to the pressure drop in the evaporator only (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only (2) - The value refers to the pressure drop in the evaporator only (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only (2) - The value refers to the pressure drop in the evaporator only (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only (2) - The value refers to the pressure drop in the evaporator only (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only (2) - The value refers to the pressure drop in the evaporator only (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only (2) - The value refers to the pressure drop in the evaporator only (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only (2) - The value refers to the pressure drop in the evaporator only
  (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1
  (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level. (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level. (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level. (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level. (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level. (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level. (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level. (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level. (4) - The certification refers only to the overall sound power level. (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level. (4) - The certification refers only to the overall sound power level. (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level. (4) - The certification refers only to the overall sound power level. (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level. (4) - The certification refers only to the overall sound power level. (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level. (4) - The certification refers only to the overall sound power level. (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level. (4) - The certification refers only to the overall sound power level. (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level. (4) - The certification refers only to the overall sound power level. (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level. (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level. (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level. (4) - The certification refers only to the overall sound power level. (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level. (4) - The certification refers only to the overall sound power level. (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level. (4) - The certification refers only to the overall sound power level. (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level. (4) - The certification refers only to the overall sound power level. (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level. (4) - The certification refers only to the overall sound power level.
  (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding
  (6) - All data refers to the standard unit without options. (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - All data refers to the standard unit without options. (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - All data refers to the standard unit without options. (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - All data refers to the standard unit without options. (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - All data refers to the standard unit without options. (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - All data refers to the standard unit without options. (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - All data refers to the standard unit without options. (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - All data refers to the standard unit without options. (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - All data refers to the standard unit without options. (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - All data refers to the standard unit without options. (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - All data refers to the standard unit without options. (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - All data refers to the standard unit without options. (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - All data refers to the standard unit without options. (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition
  (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request.
  (8) - The value refers to the pressure drop in the evaporator only (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water (8) - The value refers to the pressure drop in the evaporator only (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water (8) - Fluid: Water (8) - The value refers to the pressure drop in the evaporator only (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water (8) - Fluid: Water (8) - The value refers to the pressure drop in the evaporator only (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water (8) - Fluid: Water (8) - The value refers to the pressure drop in the evaporator only (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water (8) - Fluid: Water (8) - The value refers to the pressure drop in the evaporator only (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water (8) - Fluid: Water (8) - The value refers to the pressure drop in the evaporator only (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water (8) - Fluid: Water (8) - The value refers to the pressure drop in the evaporator only (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water (8) - Fluid: Water (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water (8) - The value refers to the pressure drop in the evaporator only (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water (8) - Fluid: Water (8) - The value refers to the pressure drop in the evaporator only (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water (8) - Fluid: Water (8) - The value refers to the pressure drop in the evaporator only (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water (8) - Fluid: Water (8) - The value refers to the pressure drop in the evaporator only (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water (8) - Fluid: Water (8) - The value refers to the pressure drop in the evaporator only (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water (8) - Fluid: Water
  (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
  (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced.
  (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current
  (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
  (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum unit current for wires sizing is based on minimum allowed voltage.
  (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1
  (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options. (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options. (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options. (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options. (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options. (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options. (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options. (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options. (15) - The data are referred to the unit without additional options. (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options. (15) - The data are referred to the unit without additional options. (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options. (15) - The data are referred to the unit without additional options. (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options. (15) - The data are referred to the unit without additional options. (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options. (15) - The data are referred to the unit without additional options. (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options. (15) - The data are referred to the unit without additional options. (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options. (15) - The data are referred to the unit without additional options. (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options. (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options. (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options. (15) - The data are referred to the unit without additional options. (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options. (15) - The data are referred to the unit without additional options. (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options. (15) - The data are referred to the unit without additional options. (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options. (15) - The data are referred to the unit without additional options. (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options. (15) - The data are referred to the unit without additional options.
  (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book
Space cooling ηs,c %     173   161   161   176.2   170.6   173   161
Refrigerant GWP       675   675   675   675   675   675   675
  Circuits Quantity       1   1   2   1   2   2   1               2                       2       1       2       2       2       2               2       2
Fan motor Drive       Phase cut   Phase cut   Phase cut   Phase cut   Phase cut   Phase cut   Phase cut               ON/OFF                       ON/OFF       ON/OFF       ON/OFF       ON/OFF       ON/OFF       ON/OFF               ON/OFF       ON/OFF
IPLV     4.92   4.46   4.68   4.78   4.84   4.86   4.7               4.44                       4.63       4.8       4.56       4.87       4.84       4.81               4.9       4.86
Piping connections Evaporator water inlet/outlet (OD)       76.1   76.1   88.9   76.1   88.9   88.9   76.1               88.9                       88.9       76.1       88.9       88.9       88.9       88.9               114.3       114.3
SEER     4.4   4.1   4.1   4.48   4.34   4.4   4.1               4.14                       4.33       4.44       4.24       4.56       4.56       4.56               4.55       4.55
Power input Cooling Nom. kW     38.5   49.8   61.9   67.8   69.5   80   85.8               95.6                       122       117       132       147       171       186               230       238
Casing Material       Galvanized and painted steel sheet   Galvanized and painted steel sheet   Galvanized and painted steel sheet   Galvanized and painted steel sheet   Galvanized and painted steel sheet   Galvanized and painted steel sheet   Galvanized and painted steel sheet               Galvanized and painted steel sheet                       Galvanized and painted steel sheet       Galvanized and painted steel sheet       Galvanized and painted steel sheet       Galvanized and painted steel sheet       Galvanized and painted steel sheet       Galvanized and painted steel sheet               Galvanized and painted steel sheet       Galvanized and painted steel sheet
  Colour       Ivory white   Ivory white   Ivory white   Ivory white   Ivory white   Ivory white   Ivory white               Ivory white                       Ivory white       Ivory white       Ivory white       Ivory white       Ivory white       Ivory white               Ivory white       Ivory white
Fan Type       Direct propeller   Direct propeller   Direct propeller   Direct propeller   Direct propeller   Direct propeller   Direct propeller               Direct propeller                       Direct propeller       Direct propeller       Direct propeller       Direct propeller       Direct propeller       Direct propeller               Direct propeller       Direct propeller
  Quantity       6   6   8   8   10   10   10               4                       5       6       5       7       7       8               9       11
Notes     (17) - All data are subject to change without notice. Please refer to the unit nameplate data.   (17) - All data are subject to change without notice. Please refer to the unit nameplate data.   (17) - All data are subject to change without notice. Please refer to the unit nameplate data.   (17) - All data are subject to change without notice. Please refer to the unit nameplate data.   (17) - All data are subject to change without notice. Please refer to the unit nameplate data.   (17) - All data are subject to change without notice. Please refer to the unit nameplate data.   (17) - All data are subject to change without notice. Please refer to the unit nameplate data.     (17) - All data are subject to change without notice. Please refer to the unit nameplate data. (17) - All data are subject to change without notice. Please refer to the unit nameplate data.     (17) - All data are subject to change without notice. Please refer to the unit nameplate data. (17) - All data are subject to change without notice. Please refer to the unit nameplate data.     (17) - All data are subject to change without notice. Please refer to the unit nameplate data. (17) - All data are subject to change without notice. Please refer to the unit nameplate data.     (17) - All data are subject to change without notice. Please refer to the unit nameplate data. (17) - All data are subject to change without notice. Please refer to the unit nameplate data.     (17) - All data are subject to change without notice. Please refer to the unit nameplate data. (17) - All data are subject to change without notice. Please refer to the unit nameplate data.     (17) - All data are subject to change without notice. Please refer to the unit nameplate data. (17) - All data are subject to change without notice. Please refer to the unit nameplate data.     (17) - All data are subject to change without notice. Please refer to the unit nameplate data. (17) - All data are subject to change without notice. Please refer to the unit nameplate data.   (17) - All data are subject to change without notice. Please refer to the unit nameplate data.   (17) - All data are subject to change without notice. Please refer to the unit nameplate data.     (17) - All data are subject to change without notice. Please refer to the unit nameplate data. (17) - All data are subject to change without notice. Please refer to the unit nameplate data.     (17) - All data are subject to change without notice. Please refer to the unit nameplate data. (17) - All data are subject to change without notice. Please refer to the unit nameplate data.     (17) - All data are subject to change without notice. Please refer to the unit nameplate data. (17) - All data are subject to change without notice. Please refer to the unit nameplate data.     (17) - All data are subject to change without notice. Please refer to the unit nameplate data. (17) - All data are subject to change without notice. Please refer to the unit nameplate data.     (17) - All data are subject to change without notice. Please refer to the unit nameplate data. (17) - All data are subject to change without notice. Please refer to the unit nameplate data.