Specifications Table for EWAT-B-SS

EWAT085B-SSA1 EWAT085B-SSB1 EWAT115B-SSA1 EWAT115B-SSB1 EWAT135B-SSA1 EWAT135B-SSB1 EWAT155B-SSA2 EWAT155B-SSB2 EWAT175B-SSA1 EWAT175B-SSB1 EWAT195B-SSA2 EWAT195B-SSB2 EWAT205B-SSA2 EWAT205B-SSB2 EWAT215B-SSA1 EWAT215B-SSB1 EWAT240B-SSA2 EWAT240B-SSA2-VFDFAN EWAT240B-SSB2 EWAT240B-SSB2-VFDFAN EWAT260B-SSA2 EWAT260B-SSA2-VFDFAN EWAT260B-SSB2-VFDFAN EWAT260B-SSB2 EWAT290B-SSA1 EWAT290B-SSB1-VFDFAN EWAT290B-SSA1-VFDFAN EWAT290B-SSB1 EWAT310B-SSB2 EWAT310B-SSA2 EWAT310B-SSB2-VFDFAN EWAT310B-SSA2-VFDFAN EWAT310B-SSC1 EWAT320B-SSC2 EWAT330B-SSA2 EWAT330B-SSB2 EWAT330B-SSA2-VFDFAN EWAT330B-SSB2-VFDFAN EWAT340B-SSA1 EWAT340B-SSB1 EWAT340B-SSB1-VFDFAN EWAT340B-SSA1-VFDFAN EWAT350B-SSA2 EWAT350B-SSB2-VFDFAN EWAT350B-SSB2 EWAT350B-SSA2-VFDFAN EWAT350B-SSC1 EWAT380B-SSC2 EWAT420B-SSB2 EWAT420B-SSA2 EWAT420B-SSA2-VFDFAN EWAT420B-SSB2-VFDFAN EWAT430B-SSC2 EWAT460B-SSA2 EWAT460B-SSB2-VFDFAN EWAT460B-SSA2-VFDFAN EWAT460B-SSB2 EWAT480B-SSC2 EWAT510B-SSA2-VFDFAN EWAT510B-SSA2 EWAT510B-SSB2-VFDFAN EWAT510B-SSB2 EWAT570B-SSA2-VFDFAN EWAT570B-SSB2 EWAT570B-SSA2 EWAT570B-SSB2-VFDFAN EWAT570B-SSC2 EWAT610B-SSA2 EWAT610B-SSA2-VFDFAN EWAT610B-SSB2-VFDFAN EWAT610B-SSB2 EWAT620B-SSC2 EWAT670B-SSA2-VFDFAN EWAT670B-SSA2 EWAT670B-SSB2 EWAT670B-SSB2-VFDFAN EWAT670B-SSC2 EWAT730B-SSC2 EWAT790B-SSC2 EWAT860B-SSC2 EWAT960B-SSC2
Sound pressure level Cooling Nom. dBA 67.4 67.4 (1) 70.5 70.5 (1) 72 72 (1) 69.5 69.5 (1) 73.8 73.8 (1) 71.3 71.3 (1) 72.3 72.3 (1) 74.8 74.8 (1) 74.3 74.3 74.3 (1) 74.3 (1) 74.8 74.8 74.8 (1) 74.8 (1) 75.8 75.8 (1) 75.8 75.8 (1) 75.4 (1) 75.4 75.4 (1) 75.4 74.9 74.7 75.8 75.8 (1) 75.8 75.8 (1) 76.6 76.6 (1) 76.6 (1) 76.6 76.1 76.1 (1) 76.1 (1) 76.1 75.5 75.4 76.7 (1) 76.7 76.7 76.7 (1) 75.9 77 77 (1) 77 77 (1) 76.2 77.6 77.6 77.6 (1) 77.6 (1) 77.9 77.9 (1) 77.9 77.9 (1) 76.5 77.9 77.9 77.9 (1) 77.9 (1) 76.7 78.2 78.2 78.2 (1) 78.2 (1) 77.0 77.2 77.4 77.5 77.8
Operation range Air side Cooling Min. °CDB -10   -10   -10   -10   -10   -10   -10   -10   -18 -18     -18 -18     -18   -18     -18   -18 -20 -20 -18   -18   -18     -18 -18     -18 -20 -20   -18 -18   -20 -18   -18   -20 -18 -18     -18   -18   -20 -18 -18     -20 -18 -18     -20 -20 -20 -20 -20
      Max. °CDB 43   43   43   43   43   43   43   43   43 43     43 43     43   43     43   43 52 52 43   43   43     43 43     43 52 52   43 43   52 43   43   52 43 43     43   43   52 43 43     52 43 43     52 52 52 52 52
  Water side Evaporator Min. °CDB -13   -13   -13   -13   -13   -13   -13   -13   -13 -13     -13 -13     -13   -13     -13   -13 -13 -13 -13   -13   -13     -13 -13     -13 -13 -13   -13 -13   -13 -13   -13   -13 -13 -13     -13   -13   -13 -13 -13     -13 -13 -13     -13 -13 -13 -13 -13
      Max. °CDB 20   20   20   20   20   20   20   20   20 20     20 20     20   20     20   20 30 30 20   20   20     20 20     20 30 30   20 20   30 20   20   30 20 20     20   20   30 20 20     30 20 20     30 30 30 30 30
Space cooling ηs,c % 149 161 161.8 173 149 161 149 161 163 176.2 157.8 170.6 159.8 173 151 161 165.4 169   175.4 155.4 158.6 165.4   168.2 177.8 172.6     166.2 182.6 170.2     167.4   171 173.4 169.8   183.4 177 161.4 169.4   163.8       174.6 177.4 179.8   171 182.2 149     176.6 172.2 181.8   173.4   169.8 179.4   171.4 173.8 180.2     177.4 171.4   183.8
Compressor Type   Driven vapour compression Scroll compressor Driven vapour compression Scroll compressor Driven vapour compression Scroll compressor Driven vapour compression Scroll compressor Driven vapour compression Scroll compressor Driven vapour compression Scroll compressor Driven vapour compression Scroll compressor Driven vapour compression Scroll compressor Driven vapour compression Driven vapour compression Scroll compressor Scroll compressor Driven vapour compression Driven vapour compression Scroll compressor Scroll compressor Driven vapour compression Scroll compressor Driven vapour compression Scroll compressor Scroll compressor Driven vapour compression Scroll compressor Driven vapour compression Scroll compressor Scroll compressor Driven vapour compression Scroll compressor Driven vapour compression Scroll compressor Driven vapour compression Scroll compressor Scroll compressor Driven vapour compression Driven vapour compression Scroll compressor Scroll compressor Driven vapour compression Scroll compressor Scroll compressor Scroll compressor Driven vapour compression Driven vapour compression Scroll compressor Scroll compressor Driven vapour compression Scroll compressor Driven vapour compression Scroll compressor Scroll compressor Driven vapour compression Driven vapour compression Scroll compressor Scroll compressor Driven vapour compression Scroll compressor Driven vapour compression Scroll compressor Scroll compressor Driven vapour compression Driven vapour compression Scroll compressor Scroll compressor Scroll compressor Driven vapour compression Driven vapour compression Scroll compressor Scroll compressor Scroll compressor Scroll compressor Scroll compressor Scroll compressor Scroll compressor
  Starting method   Direct on line Direct on line Direct on line Direct on line Direct on line Direct on line Direct on line Direct on line Direct on line Direct on line Direct on line Direct on line Direct on line Direct on line Direct on line Direct on line Direct on line Direct on line Direct on line Direct on line Direct on line Direct on line Direct on line Direct on line Direct on line Direct on line Direct on line Direct on line Direct on line Direct on line Direct on line Direct on line     Direct on line Direct on line Direct on line Direct on line Direct on line Direct on line Direct on line Direct on line Direct on line Direct on line Direct on line Direct on line     Direct on line Direct on line Direct on line Direct on line   Direct on line Direct on line Direct on line Direct on line   Direct on line Direct on line Direct on line Direct on line Direct on line Direct on line Direct on line Direct on line   Direct on line Direct on line Direct on line Direct on line   Direct on line Direct on line Direct on line Direct on line
  Quantity   2 2 2 2 2 2 4 4 2 2 4 4 4 4 2 2 4 4 4 4 4 4 4 4 3 3 3 3 4 4 4 4 3 4 4 4 4 4 3 3 3 3 4 4 4 4 3 4 4 4 4 4 4 5 5 5 5 5 5 5 5 5 6 6 6 6 5 6 6 6 6 6 6 6 6 6 6 6 7 7 8
Weight Operation weight kg 686 686 773 773 820 820 1,014 1,014 996 996 1,177 1,177 1,169 1,169 1,200 1,200 1,668 1,668 1,723 1,723 1,694 1,694 1,750 1,750 1,869 1,928 1,869 1,928 2,205 2,114 2,205 2,114 2,099 2,146 2,141 2,233 2,141 2,233 2,268 2,363 2,363 2,268 2,169 2,261 2,261 2,169 2,228 2,646 2,749 2,630 2,630 2,749 2,837 2,789 2,909 2,789 2,909 2,960 2,946 2,946 3,065 3,065 3,195 3,320 3,195 3,320 3,555 3,597 3,597 3,754 3,754 3,747 3,924 3,924 4,115 4,115 3,856 4,385 4,743 5,196 5,412
  Unit kg 679 681 763 767 810 811 1,005 1,007 983 984 1,164 1,166 1,156 1,158 1,181 1,184 1,660 1,660 1,712 1,712 1,688 1,688 1,739 1,739 1,853 1,912 1,853 1,912 2,186 2,096 2,186 2,096 2,080 2,120 2,123 2,214 2,123 2,214 2,247 2,343 2,343 2,247 2,150 2,242 2,242 2,150 2,200 2,620 2,721 2,600 2,600 2,721 2,800 2,756 2,881 2,756 2,881 2,920 2,913 2,913 3,037 3,037 3,148 3,278 3,148 3,278 3,500 3,554 3,554 3,712 3,712 3,670 3,888 3,888 4,073 4,073 3,780 4,310 4,670 5,120 5,310
Air heat exchanger Type   Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel
EER 2.55 2.55 2.82 2.83 2.64 2.64 2.55 2.55 2.58 2.58 2.75 2.75 2.63 2.63 2.53 2.53 2.82 2.81 2.83 2.83 2.71 2.71 2.73 2.73 2.61 2.62 2.61 2.62 2.72 2.71 2.72 2.71 2.869 2.764 2.7 2.71 2.69 2.7 2.92 2.94 2.93 2.91 2.64 2.65 2.65 2.64 2.658 3.046 2.84 2.83 2.82 2.83 2.871 2.72 2.73 2.71 2.73 2.714 2.74 2.74 2.76 2.76 2.61 2.63 2.61 2.62 3.058 2.64 2.64 2.66 2.66 2.921 2.77 2.78 2.8 2.8 2.823 2.957 2.889 3.002 2.870
Refrigerant Type   R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32
  GWP   675 675 675 675 675 675 675 675 675 675 675 675 675 675 675 675 675 675   675 675 675 675   675 675 675     675 675 675 675 675 675   675 675 675   675 675 675 675   675 675 675   675 675 675 675 675 675 675   675 675 675 675   675   675 675 675 675 675 675   675 675 675   675 675 675 675 675 675
  Circuits Quantity   1 1 1 1 1 1 2 2 1 1 2 2 2 2 1 1 2 2 2 2 2 2 2 2 1 1 1 1 2 2 2 2 1 2 2 2 2 2 1 1 1 1 2 2 2 2 1 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
  Charge kg 10 7.1 11 8.4 12.5 8.4 15 12.4 14 10.7 18 14.1 18 14.4 17 12.7 36 36 19 19 38 38 19 18 36 19 36 18.8 25.5 42 25.5 42 22.0 25.0 43 25 43 25 50 26 26 50 44 24 25.2 44 30.0 31.0 34.3 57 57 34.5 35.0 58 36 58 36.5 39.0 60 60 41 40 62 42 62 42 45.0 80 80 46.5 46.1 50.0 90 90 52.5 52.5 53.0 59.0 63.0 68.0 77.0
Fan motor Drive   Phase cut Phase cut Phase cut Phase cut Phase cut Phase cut Phase cut Phase cut Phase cut Phase cut Phase cut Phase cut Phase cut Phase cut Phase cut Phase cut ON/OFF VFD driven ON/OFF VFD driven ON/OFF VFD driven VFD driven ON/OFF ON/OFF VFD driven VFD driven ON/OFF ON/OFF ON/OFF VFD driven VFD driven ON/OFF ON/OFF ON/OFF ON/OFF VFD driven VFD driven ON/OFF ON/OFF VFD driven VFD driven ON/OFF VFD driven ON/OFF VFD driven ON/OFF ON/OFF ON/OFF ON/OFF VFD driven VFD driven ON/OFF ON/OFF VFD driven VFD driven ON/OFF ON/OFF VFD driven ON/OFF VFD driven ON/OFF VFD driven ON/OFF ON/OFF VFD driven ON/OFF ON/OFF VFD driven VFD driven ON/OFF ON/OFF VFD driven ON/OFF ON/OFF VFD driven ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF
Cooling capacity Nom. kW 80.92 81 108.73 109 131.2 131 157.55 158 174.49 175 190.91 191 209.86 211 216.55 217 240.44 240.44 241 241 259.39 259.39 261 261 281.85 283 281.85 283 306 305.6 306 305.6 305.92 317.98 328.59 330 328.59 330 342 344 344 342 348.88 350 350 348.88 345.59 381.40 416 414.98 414.98 416 426.61 465.75 468 465.75 468 477.56 511.1 511.1 513 513 564.43 567 564.43 567 567.34 609.05 609.05 612 612 622.34 664.62 664.62 668 668 668.92 734.97 791.18 857.22 961.63
IPLV 4.65 4.65 4.92 4.92 4.46 4.46 4.68 4.68 4.78 4.78 4.8 4.84 4.87 4.86 4.49 4.7 4.66 4.77 4.67 4.81 4.46 4.59 4.27 4.44 4.76 4.55 4.88 4.74 4.86 4.67 5.02 4.85 4.948 4.794 4.65 4.63 4.73 4.75 4.77 4.8 5 4.84 4.58 4.7 4.56 4.71 4.948 4.849 4.87 4.77 4.89 4.91 4.907 4.75 4.89 4.92 4.84 4.940 4.81 4.7 4.9 4.81 4.82 4.89 4.74 4.93 5.062 4.71 4.78 4.89 4.9 5.073 4.96 4.73 4.86 5 5.088 5.120 5.092 5.122 5.079
Piping connections Evaporator water inlet/outlet (OD)   76.1 76.1 76.1 76.1 76.1 76.1 88.9 88.9 76.1 76.1 88.9 88.9 88.9 88.9 76.1 76.1 88.9 88.9 88.9 88.9 88.9 88.9 88.9 88.9 76.1 76.1 76.1 76.1 88.9 88.9 88.9 88.9 88.9mm 88.9mm 88.9 88.9 88.9 88.9 76.1 76.1 76.1 76.1 88.9 88.9 88.9 88.9 88.9mm 88.9mm 88.9 88.9 88.9 88.9 88.9mm 88.9 88.9 88.9 88.9 88.9mm 88.9 88.9 88.9 88.9 114.3 114.3 114.3 114.3 139.7mm 114.3 114.3 114.3 114.3 139.7mm 114.3 114.3 114.3 114.3 139.7mm 139.7mm 139.7mm 139.7mm 139.7mm
SEER 3.8 4.1 4.12 4.4 3.8 4.1 3.8 4.1 4.15 4.48 4.02 4.34 4.07 4.4 3.85 4.1 4.21 4.3 4.37 4.46 3.96 4.04 4.21 4.14 4.28 4.52 4.39 4.42 4.52 4.23 4.64 4.33 4.689 4.517 4.26 4.33 4.35 4.41 4.32 4.44 4.66 4.5 4.11 4.31 4.24 4.17 4.604 4.649 4.56 4.44 4.51 4.57 4.698 4.35 4.63 3.8 4.56 4.649 4.49 4.38 4.62 4.56 4.41 4.56 4.32 4.56 4.834 4.36 4.42 4.58 4.55 4.797 4.51 4.36 4.55 4.67 4.778 4.834 4.844 4.889 4.801
Power input Cooling Nom. kW 31.8 31.8 38.5 38.5 49.8 49.8 61.8 61.9 67.7 67.8 69.4 69.5 79.8 80 85.6 85.8 85.3 85.5 85.2 85.4 95.7 95.7 95.6 95.6 108 108 108 108 113 112 112 112 106.6 115.0 121 122 122 122 117 117 117 117 132 132 132 132 130.0 125.2 147 146 147 146 148.6 171 171 171 171 176.0 186 186 186 186 216 216 216 216 185.5 230 230 230 230 213.1 239 239 238 238 237.0 248.6 273.9 285.5 335.1
Sound power level Cooling Nom. dBA 84.8 84.8 (1) 88.2 88.2 (1) 89.7 89.7 (1) 87.8 87.8 (1) 91.8 91.8 (1) 89.9 89.9 (1) 90.9 90.9 (1) 93.2 93.2 (1) 93.3 93.3 93.3 (1) 93.3 (1) 93.8 93.8 93.8 (1) 93.8 (1) 94.8 94.8 (1) 94.8 94.8 (1) 94.9 (1) 94.9 94.9 (1) 94.9 94.0 93.8 95.3 95.3 (1) 95.3 95.3 (1) 96.1 96.1 (1) 96.1 (1) 96.1 95.6 95.6 (1) 95.6 (1) 95.6 94.5 95.1 96.7 (1) 96.7 96.7 96.7 (1) 95.6 97 97 (1) 97 97 (1) 95.9 97.6 97.6 97.6 (1) 97.6 (1) 97.8 97.8 (1) 97.8 97.8 (1) 96.7 98.3 98.3 98.3 (1) 98.3 (1) 97.0 99 99 99 (1) 99 (1) 97.3 97.9 98.1 98.6 99.0
Dimensions Unit Width mm 1,204 1,204 1,204 1,204 1,204 1,204 1,204 1,204 1,204 1,204 1,204 1,204 1,204 1,204 1,204 1,204 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,238 2,238 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,238 2,238 2,236 2,236 2,236 2,236 2,238 2,236 2,236 2,236 2,236 2,238 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,238 2,236 2,236 2,236 2,236 2,238 2,236 2,236 2,236 2,236 2,238 2,238 2,238 2,238 2,238
    Depth mm 2,120 2,120 2,660 2,660 2,660 2,660 3,570 3,570 3,180 3,180 4,170 4,170 4,170 4,170 3,780 3,780 2,326 2,326 2,326 2,326 2,326 2,326 2,326 2,326 2,326 2,326 2,326 2,326 3,226 3,226 3,226 3,226 2,510 2,510 3,226 3,226 3,226 3,226 3,226 3,226 3,226 3,226 3,226 3,226 3,226 3,226 2,510 3,590 4,126 4,126 4,126 4,126 3,590 4,126 4,126 4,126 4,126 3,590 4,126 4,126 4,126 4,126 4,126 4,126 4,126 4,126 4,670 5,025 5,025 5,025 5,025 4,670 5,874 5,874 5,874 5,874 4,670 5,750 5,850 6,930 6,930
    Height mm 1,801 1,801 1,801 1,801 1,801 1,801 1,822 1,822 1,801 1,801 1,822 1,822 1,822 1,822 1,822 1,822 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,535 2,535 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,535 2,535 2,540 2,540 2,540 2,540 2,535 2,540 2,540 2,540 2,540 2,535 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,535 2,540 2,540 2,540 2,540 2,535 2,540 2,540 2,540 2,540 2,535 2,535 2,535 2,535 2,535
Capacity control Minimum capacity % 50 50 38 38 50 50 25 25 38 38 21 21 19 19 50 50 17 17 17 17 25 25 25 25 24 24 24 24 14 14 14 14 22 21 13 13 13 13 33 33 33 33 19 19 19 19 19 18 17 17 17 17 16 15 15 15 15 14 14 14 14 14 12 12 12 12 22 11 11 11 11 20 17 17 17 17 18 17 15 14 25
  Method   Staged Step Staged Step Staged Step Variable Step Staged Step Variable Step Variable Step Staged Step Variable Variable Step Step Variable Variable Step Step Variable Step Variable Step Step Variable Step Variable Step Step Variable Step Variable Step Variable Step Step Variable Variable Step Step Variable Step Step Step Variable Variable Step Step Variable Step Variable Step Step Variable Variable Step Step Variable Step Variable Step Step Variable Variable Step Step Step Variable Variable Step Step Step Step Step Step Step
Casing Material   Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet
  Colour   Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white
Water heat exchanger - evaporator Type                                                                   Brazed plate Brazed plate                         Brazed plate Brazed plate         Brazed plate         Brazed plate                 Brazed plate         Brazed plate         Brazed plate Brazed plate Brazed plate Brazed plate Brazed plate
  Water pressure drop Cooling Nom. kPa                                                                 49.3 47.0                         55.3 66.9         73.3         91.4                 21.5         25.5         19.7 23.5 27.1 31.6 31.2
  Water volume l                                                                 22.95 27.27                         27.27 27.27         35.37         35.37                 58.80         58.80         75.60 75.60 75.60 75.60 92.40
Fan Type   Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller
  Quantity   4 4 6 6 6 6 8 8 8 8 10 10 10 10 10 10 4 4 4 4 4 4 4 4 4 4 4 4 5 5 5 5 4 4 5 5 5 5 6 6 6 6 5 5 5 5 4 6 7 7 7 7 6 7 7 7 7 6 8 8 8 8 8 8 8 8 8 9 9 9 9 8 11 11 11 11 8 10 10 12 12
  Air flow rate Cooling Nom. l/s                                                                 25,490 25,500                         25,490 38,240         38,240         38,240                 50,980         50,980         50,980 63,730 63,730 76,480 76,480
Power supply Phase   3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~
  Voltage range Max. % 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
    Min. % -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 0 0 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 0 0 -10 -10 -10 -10 0 -10 -10 -10 -10 0 -10 -10 -10 -10 -10 -10 -10 -10 0 -10 -10 -10 -10 0 -10 -10 -10 -10 0 0 0 0 0
  Frequency Hz 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
  Voltage V 400   400   400   400   400   400   400   400   400 400     400 400     400   400     400   400 400 400 400   400   400     400 400     400 400 400   400 400   400 400   400   400 400 400     400   400   400 400 400     400 400 400     400 400 400 400 400
Unit Max unit current for wires sizing A 80 77 94 107 106 104 157 144 146 176 171 204 183 200 185 183 202 202 212 212 214 214 209 208 237 268 237 268 262 265 263 265 269 273 278 291 278 291 282 280 280 282 290 288 287 290 316 332 364 335 335 365 379 384 446 384 445 429 425 425 455 454 474 535 474 536 487 514 514 545 544 537 559 559 556 557 584 642 694 752 849
  Starting current Max A 213 213 313 313 324 324 284 284 462 462 384 384 395 395 498 498 411 411 410 410 422 422 420 420 546 546 546 546 573 572 573 572 693 697 583 583 583 583 587 588 588 587 595 594 594 595 735 750 636 635 635 636 792 680 681 680 681 838 717 717 719 719 761 763 761 763 891 798 798 801 801 936 839 839 843 843 979 1,032 1,079 1,132 1,220
  Running current Cooling Nom. A 59 59 69 69 83 83 112 108 113 113 122 117 136 131 142 142 147.0 147 147 147 160 160 160 160 179 179 179 179 194 194 194 194 186 200 207 206 207 207 197 196 197 197 220 220 219 220 224 222 237 238 238 238 260 285 285 285 285 304 310 310 310 310 358 358 358 358 329 382 382 382 381 374 399 399 398 399 413 438 479 505 585
    Max A 73 73 86 86 96 96 143 143 132 132 156 156 167 167 168 168 183 183 182 182 195 195 193 193 215 216 215 216 243 241 243 241 245 249 253 254 253 254 256 258 258 256 264 265 265 264 287 302 307 305 305 307 344 349 351 349 351 390 386 386 389 389 431 433 431 433 443 467 467 471 471 488 508 508 513 513 531 584 631 684 772
Notes (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0     (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0     (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0   (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0   (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0   (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0   (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0
  (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only (2) - The value refers to the pressure drop in the evaporator only (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only (2) - The value refers to the pressure drop in the evaporator only (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only (2) - The value refers to the pressure drop in the evaporator only (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281     (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only (2) - The value refers to the pressure drop in the evaporator only (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only (2) - The value refers to the pressure drop in the evaporator only (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281     (2) - The value refers to the pressure drop in the evaporator only (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only   (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only   (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only (2) - The value refers to the pressure drop in the evaporator only (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only   (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only (2) - The value refers to the pressure drop in the evaporator only   (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only (2) - The value refers to the pressure drop in the evaporator only
  (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i     (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i     (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1   (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1   (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1   (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1   (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1
  (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level. (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level. (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level. (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level. (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level. (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level. (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level. (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level. (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level. (4) - The certification refers only to the overall sound power level. (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level. (4) - The certification refers only to the overall sound power level. (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level. (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level. (4) - The certification refers only to the overall sound power level. (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level. (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition     (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level. (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level. (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level. (4) - The certification refers only to the overall sound power level. (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level. (4) - The certification refers only to the overall sound power level. (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition     (4) - The certification refers only to the overall sound power level. (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level.   (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level. (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level.   (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level. (4) - The certification refers only to the overall sound power level. (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level. (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level.   (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level. (4) - The certification refers only to the overall sound power level.   (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level. (4) - The certification refers only to the overall sound power level.
  (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request.     (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request.     (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding   (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding   (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding   (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding   (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding
  (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - All data refers to the standard unit without options. (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - All data refers to the standard unit without options. (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - All data refers to the standard unit without options.     (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - All data refers to the standard unit without options. (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - All data refers to the standard unit without options.     (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - All data refers to the standard unit without options. (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition   (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition   (6) - All data refers to the standard unit without options. (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition   (6) - All data refers to the standard unit without options. (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition   (6) - All data refers to the standard unit without options. (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition
  (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - All data are subject to change without notice. Please refer to the unit nameplate data.     (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - All data are subject to change without notice. Please refer to the unit nameplate data.     (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request.   (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request.   (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request.   (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request.   (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request.
  (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water (8) - The value refers to the pressure drop in the evaporator only (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water (8) - Fluid: Water (8) - The value refers to the pressure drop in the evaporator only (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water (8) - Fluid: Water (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water (8) - Fluid: Water (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water (8) - The value refers to the pressure drop in the evaporator only     (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water (8) - Fluid: Water (8) - The value refers to the pressure drop in the evaporator only (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water (8) - Fluid: Water (8) - The value refers to the pressure drop in the evaporator only     (8) - Fluid: Water (8) - The value refers to the pressure drop in the evaporator only (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water   (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water   (8) - The value refers to the pressure drop in the evaporator only (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water (8) - Fluid: Water (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water   (8) - The value refers to the pressure drop in the evaporator only (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water (8) - Fluid: Water   (8) - The value refers to the pressure drop in the evaporator only (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water (8) - Fluid: Water
  (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans     (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans     (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.   (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.   (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.   (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.   (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
  (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.     (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.     (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced.   (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced.   (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced.   (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced.   (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced.
  (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - In case of inverter driven units, no inrush current at start up is experienced.     (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - In case of inverter driven units, no inrush current at start up is experienced.     (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current   (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current   (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current   (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current   (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current
  (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current.     (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current.     (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.   (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.   (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.   (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.   (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
  (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current     (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current     (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage.   (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage.   (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage.   (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum unit current for wires sizing is based on minimum allowed voltage.   (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum unit current for wires sizing is based on minimum allowed voltage.
  (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum unit current for wires sizing is based on minimum allowed voltage.     (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum unit current for wires sizing is based on minimum allowed voltage.     (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1   (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1   (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1   (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1   (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1
  (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options. (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options. (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options. (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options. (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options. (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options. (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options. (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options. (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options. (15) - The data are referred to the unit without additional options. (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options. (15) - The data are referred to the unit without additional options. (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options. (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options. (15) - The data are referred to the unit without additional options. (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options. (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1     (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options. (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options. (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options. (15) - The data are referred to the unit without additional options. (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options. (15) - The data are referred to the unit without additional options. (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1     (15) - The data are referred to the unit without additional options. (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options.   (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options. (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options.   (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options. (15) - The data are referred to the unit without additional options. (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options. (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options.   (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options. (15) - The data are referred to the unit without additional options.   (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options. (15) - The data are referred to the unit without additional options.
  (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book     (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book     (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book   (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book   (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book   (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book   (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book
    (17) - All data are subject to change without notice. Please refer to the unit nameplate data.   (17) - All data are subject to change without notice. Please refer to the unit nameplate data.   (17) - All data are subject to change without notice. Please refer to the unit nameplate data.   (17) - All data are subject to change without notice. Please refer to the unit nameplate data.   (17) - All data are subject to change without notice. Please refer to the unit nameplate data.   (17) - All data are subject to change without notice. Please refer to the unit nameplate data.   (17) - All data are subject to change without notice. Please refer to the unit nameplate data.   (17) - All data are subject to change without notice. Please refer to the unit nameplate data.     (17) - All data are subject to change without notice. Please refer to the unit nameplate data. (17) - All data are subject to change without notice. Please refer to the unit nameplate data.     (17) - All data are subject to change without notice. Please refer to the unit nameplate data. (17) - All data are subject to change without notice. Please refer to the unit nameplate data.   (17) - All data are subject to change without notice. Please refer to the unit nameplate data.   (17) - All data are subject to change without notice. Please refer to the unit nameplate data. (17) - All data are subject to change without notice. Please refer to the unit nameplate data.   (17) - All data are subject to change without notice. Please refer to the unit nameplate data.         (17) - All data are subject to change without notice. Please refer to the unit nameplate data.   (17) - All data are subject to change without notice. Please refer to the unit nameplate data.   (17) - All data are subject to change without notice. Please refer to the unit nameplate data. (17) - All data are subject to change without notice. Please refer to the unit nameplate data.     (17) - All data are subject to change without notice. Please refer to the unit nameplate data. (17) - All data are subject to change without notice. Please refer to the unit nameplate data.       (17) - All data are subject to change without notice. Please refer to the unit nameplate data.     (17) - All data are subject to change without notice. Please refer to the unit nameplate data.     (17) - All data are subject to change without notice. Please refer to the unit nameplate data.   (17) - All data are subject to change without notice. Please refer to the unit nameplate data.       (17) - All data are subject to change without notice. Please refer to the unit nameplate data. (17) - All data are subject to change without notice. Please refer to the unit nameplate data.   (17) - All data are subject to change without notice. Please refer to the unit nameplate data.   (17) - All data are subject to change without notice. Please refer to the unit nameplate data.       (17) - All data are subject to change without notice. Please refer to the unit nameplate data. (17) - All data are subject to change without notice. Please refer to the unit nameplate data.       (17) - All data are subject to change without notice. Please refer to the unit nameplate data. (17) - All data are subject to change without notice. Please refer to the unit nameplate data.