Specifications Table for EWAT-B-XR

EWAT085B-XRA1 EWAT085B-XRB1 EWAT115B-XRA1 EWAT115B-XRB1 EWAT145B-XRA1 EWAT145B-XRB1 EWAT180B-XRA2 EWAT180B-XRB2 EWAT185B-XRA1 EWAT185B-XRB1 EWAT200B-XRA2 EWAT200B-XRB2 EWAT220B-XRA2 EWAT220B-XRB2 EWAT230B-XRA1 EWAT230B-XRB1 EWAT250B-XRA2 EWAT250B-XRB2 EWAT250B-XRC1 EWAT280B-XRA2 EWAT280B-XRB2 EWAT300B-XRA1 EWAT300B-XRB1 EWAT310B-XRA2 EWAT310B-XRB2 EWAT320B-XRA2 EWAT320B-XRB2 EWAT320B-XRC1 EWAT360B-XRA1 EWAT360B-XRB1 EWAT370B-XRA2 EWAT370B-XRB2 EWAT370B-XRC1 EWAT390B-XRC2 EWAT430B-XRA2 EWAT430B-XRB2 EWAT450B-XRC2 EWAT470B-XRA2 EWAT470B-XRB2 EWAT510B-XRC2 EWAT540B-XRA2 EWAT540B-XRB2 EWAT540B-XRC2 EWAT590B-XRC2 EWAT600B-XRA2 EWAT600B-XRB2 EWAT630B-XRC2 EWAT660B-XRA2 EWAT660B-XRB2 EWAT700B-XRA2 EWAT700B-XRB2 EWAT720B-XRC2 EWAT760B-XRC2 EWAT830B-XRC2 EWAT880B-XRC2 EWATC10B-XRC2
Sound pressure level Cooling Nom. dBA 60.2 60.2 (1) 63.9 63.9 (1) 65.6 65.6 (1) 65.3 65.3 (1) 67.7 67.7 (1) 65.5 65.5 (1) 65.8 65.8 (1) 66.7 66.7 (1) 66.3 66.3 (1) 64.9 67.1 67.1 (1) 67.5 67.5 (1) 67.2 67.2 (1) 67.4 67.4 (1) 65.7 67.8 67.8 (1) 67.7 67.7 (1) 66.0 65.9 68.3 68.3 (1) 66.5 68.5 68.5 (1) 66.7 68.9 68.9 (1) 66.9 67.1 69.2 69.2 (1) 67.2 69.3 69.3 (1) 69.6 69.6 (1) 67.5 67.6 67.7 67.8 68.1
Operation range Air side Cooling Min. °CDB -10   -10   -10   -18   -10   -18   -18   -18   -18     -18   -18   -18   -18     -18   -18       -18     -18     -18       -18     -18   -18
      Max. °CDB 46   46   46   46   46   46   46   46   46     46   46   46   46     46   46       46     46     46       46     46   46
  Water side Cooling Max. °CDB 20   20   20   20   20   20   20   20   20     20   20   20   20     20   20       20     20     20       20     20   20
      Min. °CDB -13   -13   -13   -13   -13   -13   -13   -13   -13     -13   -13   -13   -13     -13   -13       -13     -13     -13       -13     -13   -13
Compressor Type   Driven vapour compression Scroll compressor Driven vapour compression Scroll compressor Driven vapour compression Scroll compressor Driven vapour compression Scroll compressor Driven vapour compression Scroll compressor Driven vapour compression Scroll compressor Driven vapour compression Scroll compressor Driven vapour compression Scroll compressor Driven vapour compression Scroll compressor Scroll compressor Driven vapour compression Scroll compressor Driven vapour compression Scroll compressor Driven vapour compression Scroll compressor Driven vapour compression Scroll compressor Scroll compressor Driven vapour compression Scroll compressor Driven vapour compression Scroll compressor Scroll compressor Scroll compressor Driven vapour compression Scroll compressor Scroll compressor Driven vapour compression Scroll compressor Scroll compressor Driven vapour compression Scroll compressor Scroll compressor Scroll compressor Driven vapour compression Scroll compressor Scroll compressor Driven vapour compression Scroll compressor Driven vapour compression Scroll compressor Scroll compressor Scroll compressor Scroll compressor Scroll compressor Scroll compressor
  Starting method     Direct on line   Direct on line   Direct on line       Direct on line   Direct on line   Direct on line   Direct on line   Direct on line     Direct on line   Direct on line       Direct on line     Direct on line   Direct on line       Direct on line     Direct on line     Direct on line       Direct on line     Direct on line   Direct on line
  Quantity   2 2 2 2 2 2 4 4 2 2 4 4 4 4 2 2 4 4 2 4 4 3 3 4 4 4 4 3 3 3 4 4 3 4 4 4 4 4 4 4 5 5 5 5 6 6 5 6 6 6 6 6 6 7 7 8
Weight Operation weight kg 752 752 846 846 968 968 1,743 1,747 1,088 1,088 1,773 1,777 1,801 1,813 1,997 2,098 2,066 2,104 2,045 2,209 2,250 2,234 2,338 2,241 2,281 2,277 2,318 2,577 2,614 2,751 2,655 2,821 2,698 2,780 2,848 2,916 3,324 3,268 3,421 3,538 3,497 3,675 4,003 4,115 3,916 4,148 4,223 4,290 4,550 4,432 4,692 4,801 4,909 5,697 5,806 6,549
  Unit kg 744 747 837 840 961 959 1,732 1,736 1,072 1,076 1,763 1,766 1,790 1,802 1,977 2,082 2,054 2,090 2,020 2,192 2,231 2,212 2,318 2,220 2,262 2,247 2,299 2,550 2,590 2,731 2,627 2,801 2,670 2,740 2,811 2,888 3,290 3,237 3,393 3,480 3,458 3,633 3,940 4,060 3,873 4,106 4,160 4,248 4,500 4,396 4,642 4,720 4,830 5,620 5,730 6,450
Air heat exchanger Type   Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel Microchannel
EER 2.64 2.66 2.78 2.79 2.88 2.89 2.84 2.84 2.35 2.36 2.68 2.69 2.58 2.58 2.83 2.84 2.76 2.73 2.977 2.87 2.87 2.71 2.72 2.76 2.76 2.63 2.63 3.135 2.7 2.71 2.66 2.67 2.929 2.869 2.68 2.69 3.052 2.68 2.69 3.019 2.66 2.64 3.262 3.119 2.74 2.76 2.990 2.76 2.77 2.71 2.72 3.107 3.003 3.067 2.979 2.985
ESEER 4.02   4.18   4.08   4.24   4.04   4.21   4.17   4.16   4.15     4.34   4.31   4.12   4.04     4.24   4.15       4.15     4.12     4.2       4.21     4.25   4.23
Refrigerant GWP   675   675   675   675 675 675   675   675   675   675     675   675   675 675 675     675   675       675     675     675       675     675   675
  Type   R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32 R-32
  Circuits Quantity   1   1   1   2 2 1   2   2   1   2     2   1   2 2 2     1   2       2     2     2       2     2   2
  Charge kg 10.5 8.4 12.5 9.1 15 10.3 30 12 16 11.8 36 19.1 37 18.9 30 22.7 42 22.5 44.0 48 28.7 36 27.3 50 28 52 26.6 50.0 50 30 58 33.2 55.0 30.5 62 35 30.5 70 40.9 39.5 78 48.2 42.0 45.0 80 51.5 49.0 92 59.2 100 62 55.0 57.5 62.5 67.0 75.0
Cooling capacity Nom. kW 81.68 82 108.36 109 135.38 136 167.75 168 165.77 166 187.07 188 207.97 208 223.94 225 238.24 238 241.40 264.17 265 284.03 285 283.97 285 301.05 302 313.20 327.53 329 345.32 346 355.68 370.32 393.29 394 431.43 437.99 440 489.48 500 502 520.68 563.54 569.48 572 603.94 618.9 621 656.69 659 687.57 729.00 800.94 842.34 965.50
Water heat exchanger Water volume l 5   6   9   11 11 12   11   11   16   14     19   20   19 19 19     20   20       28     28     42       42     50   50
  Type   Brazed plate   Brazed plate   Brazed plate   Brazed plate Brazed plate Brazed plate   Brazed plate   Brazed plate   Brazed plate   Brazed plate     Brazed plate   Brazed plate   Brazed plate Brazed plate Brazed plate     Brazed plate   Brazed plate       Brazed plate     Brazed plate     Brazed plate       Brazed plate     Brazed plate   Brazed plate
Power input Cooling Nom. kW 30.9   39   47   59.1 59.1 70.5   69.8   80.7   79.2   86.4     92.2   104   103 103 114     121   130       146     163     188       207     224   242
Sound power level Cooling Nom. dBA 77.9 77.9 (1) 81.9 81.9 (1) 84 84 (1) 84.2 84.2 (1) 86 86 (1) 84.5 84.5 (1) 84.8 84.8 (1) 86.2 86.2 (1) 85.8 85.8 (1) 84.0 86.6 86.6 (1) 87 87 (1) 86.7 86.7 (1) 86.9 86.9 (1) 85.4 87.7 87.7 (1) 87.6 87.6 (1) 85.7 85.6 88.3 88.3 (1) 86.8 88.9 88.9 (1) 87.0 89.3 89.3 (1) 87.6 87.8 90 90 (1) 87.9 90.4 90.4 (1) 90.7 90.7 (1) 88.6 88.7 89.3 89.4 90.0
Dimensions Unit Width mm 1,204 1,204 1,204 1,204 1,204 1,204 2,236 2,236 1,204 1,204 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,238 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,236 2,238 2,236 2,236 2,236 2,236 2,238 2,238 2,236 2,236 2,238 2,236 2,236 2,238 2,236 2,236 2,238 2,238 2,236 2,236 2,238 2,236 2,236 2,236 2,236 2,238 2,238 2,238 2,238 2,238
    Depth mm 2,660 2,660 3,180 3,180 3,780 3,780 2,326 2,326 3,780 3,780 2,326 2,326 2,326 2,326 3,226 3,226 3,226 3,226 2,510 3,226 3,226 3,226 3,226 3,226 3,226 3,226 3,226 53,600 4,126 4,126 4,126 4,126 3,590 3,590 4,126 4,126 4,670 5,025 5,025 4,670 5,025 5,025 5,750 5,750 5,874 5,874 5,750 6,774 6,774 6,774 6,774 6,830 6,830 8,010 8,010 9,090
    Height mm 1,801 1,801 1,801 1,801 1,822 1,822 2,540 2,540 1,822 1,822 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,535 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,540 2,535 2,540 2,540 2,540 2,540 2,535 2,535 2,540 2,540 2,535 2,540 2,540 2,535 2,540 2,540 2,535 2,535 2,540 2,540 2,535 2,540 2,540 2,540 2,540 2,535 2,535 2,535 2,535 2,535
Capacity control Minimum capacity % 50 50 38 38 50 50 25 25 38 38 21 21 19 19 50 50 17 17 50 16 16 24 24 14 14 22 22 22 33 33 19 19 19 18 17 17 16 25 25 25 14 14 14 22 12 12 20 11 11 17 17 18 17 15 14 25
  Method   Staged Step Staged Step Staged Step Variable Step Staged Step Variable Step Variable Step Staged Step Variable Step Step Variable Step Variable Step Variable Step Variable Step Step Variable Step Variable Step Step Step Variable Step Step Variable Step Step Variable Step Step Step Variable Step Step Variable Step Variable Step Step Step Step Step Step
Water heat exchanger - evaporator Water pressure drop Cooling Nom. kPa                                     31.24                 51.60         58.41 55.59     74.92     16.26     18.26 21.17     24.12         20.74 23.17 27.72 30.55 31.46
  Water volume l                                     23                 23         27 35     35     59     59 59     59         76 76 76 76 92
Fan Air flow rate Nom. l/s 6,673   8,896   11,122   15,054 15,054 11,122   15,054   15,054   18,819   18,818     22,582   22,582   22,582 22,582 22,582     26,346   26,346       30,110     33,874     37,637       45,164     48,928   52,692
    Cooling Nom. l/s                                     18,900                 28,350         28,350 28,350     37,800     37,800     47,250 47,250     47,250         56,700 56,700 66,150 66,150 75,600
  Speed rpm 1,108   1,108   1,108   700 700 1,108   700   700   700   700     700   700   700 700 700     700   700       700     700     700       700     700   700
Compressor Starting method   Direct on line   Direct on line   Direct on line   Direct on line Direct on line Direct on line   Direct on line   Direct on line   Direct on line   Direct on line     Direct on line   Direct on line   Direct on line Direct on line Direct on line     Direct on line   Direct on line       Direct on line     Direct on line     Direct on line       Direct on line     Direct on line   Direct on line
Power supply Phase   3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~
  Voltage range Max. %   10   10   10       10   10   10   10   10 10   10   10       10 10   10   10 10 10   10 10   10 10   10 10 10   10 10   10   10 10 10 10 10 10
    Min. %   -10   -10   -10       -10   -10   -10   -10   -10 0   -10   -10       -10 0   -10   -10 0 0   -10 0   -10 0   -10 0 0   -10 0   -10   -10 0 0 0 0 0
  Frequency Hz 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
  Voltage V 400   400   400   400   400   400   400   400   400   400 400   400   400   400   400 400   400   400 400 400   400 400   400 400   400 400 400   400 400   400   400 400 400 400 400
Unit Max unit current for wires sizing A   79   109   108       178   182   210   184   209 219   253   267       278 280   275   285 327 332   358 390   365 437   449 451 498   534 545   542   549 606 653 763 763 871
  Starting current Max A   215   315   328       464   388   399   506   414 647   543   554       564 703   592   602 746 750   640 803   678 845   727 858 901   779 944   817   855 999 1,042 1,142 1,142 1,240
  Running current Cooling Nom. A   59   71   83       118   128   143   134   151 143   164   177       194 178   204   221 213 225   250 249   276 286   319 287 322   352 356   381   410 393 428 463 498 570
    Max A   75   87   100       134   160   171   176   186 199   213   224       235 255   262   273 298 302   311 355   348 397   397 410 453   449 496   487   525 551 594 694 694 792
Notes (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0   (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0   (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0     (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0   (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0   (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0     (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0   (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0 (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load operation, operating fluid: water, fouling factor = 0
  (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only   (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only   (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only     (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only   (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only   (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only     (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only   (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only (2) - In accordance with standard EN14825:2013 comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) No 2016/2281 (2) - The value refers to the pressure drop in the evaporator only
  (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1   (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1   (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1     (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1   (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1   (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1     (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1   (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 (3) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i (3) - Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1
  (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level. (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level. (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level. (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level. (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level. (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level. (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level. (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level. (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level.   (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level. (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level. (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level. (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level.   (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level. (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level.     (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level.   (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level.   (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level.     (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level.   (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level. (4) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (4) - The certification refers only to the overall sound power level.
  (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding   (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding   (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding     (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding   (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding   (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding     (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding   (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding (5) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (5) - The sound pressure level is calculated from the sound power level and is for information only and not considered binding
  (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition   (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition   (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition     (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition   (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition   (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition     (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition   (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition (6) - All data refers to the standard unit without options. (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition
  (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request.   (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request.   (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request.     (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request.   (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request.   (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request.     (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request.   (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. (7) - All data are subject to change without notice. Please refer to the unit nameplate data. (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request.
  (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water   (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water   (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water     (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water   (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water   (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water     (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water   (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water (8) - The value refers to the pressure drop in the evaporator only (8) - Fluid: Water
  (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.   (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.   (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.     (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.   (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.   (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.     (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.   (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (9) - Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous fan control, Multi-V units require opt 99 - VFD fans (9) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
  (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced.   (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced.   (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced.     (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced.   (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced.   (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced.     (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced.   (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced. (10) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (10) - Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load. In case of inverter driven units, no inrush current at start up is experienced.
  (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current   (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current   (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current     (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current   (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current   (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current     (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current   (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current (11) - In case of inverter driven units, no inrush current at start up is experienced. (11) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current
  (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.   (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.   (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.     (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.   (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.   (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.     (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.   (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. (12) - Nominal current in cooling mode: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; ambient air temp. 35°C. Compressor + fans current. (12) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current.
  (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage.   (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage.   (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage.     (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage.   (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage.   (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage.     (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage.   (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage. (13) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current (13) - Maximum unit current for wires sizing is based on minimum allowed voltage.
  (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1   (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1   (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1     (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1   (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1   (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1     (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1   (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (14) - Maximum unit current for wires sizing is based on minimum allowed voltage. (14) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1
  (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options. (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options. (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options. (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options. (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options. (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options. (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options. (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options. (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options.   (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options. (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options. (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options. (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options.   (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options. (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options.     (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options.   (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options.   (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options.     (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options.   (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options. (15) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 (15) - The data are referred to the unit without additional options.
  (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book   (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book   (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book     (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book   (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book   (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book     (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book   (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book (16) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book
Space cooling ηs,c %   213.28   179.4   166.6       164.6   186.6   179   169   177     186.6   185.8       173.8     180.6   176.2       181.8     179     183       187.4     187.4   185.4
Refrigerant GWP     675   675   675       675   675   675   675   675 675   675   675       675 675   675   675 675 675   675 675   675 675   675 675 675   675 675   675   675 675 675 675 675 675
  Circuits Quantity     1   1   1       1   2   2   1   2 1   2   1       2 1   1   2 1 2   2 2   2 2   2 2 2   2 2   2   2 2 2 2 2 2
Fan motor Drive     Phase cut   Phase cut   Phase cut       Phase cut   VFD driven   VFD driven   VFD driven   VFD driven ON/OFF   VFD driven   VFD driven       VFD driven ON/OFF   VFD driven   VFD driven ON/OFF ON/OFF   VFD driven ON/OFF   VFD driven ON/OFF   VFD driven ON/OFF ON/OFF   VFD driven ON/OFF   VFD driven   VFD driven ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF
IPLV   4.74   5.1   4.76       4.72   5.05   4.97   4.86   4.91 5.340   5.08   4.78       4.62 5.525   5.04   4.95 5.487 5.317   4.88 5.446   4.72 5.528   4.96 5.630 5.620   5.04 5.601   5.07   5.08 5.649 5.605 5.613 5.605 5.576
Piping connections Evaporator water inlet/outlet (OD)     76.1   76.1   76.1       76.1   88.9   88.9   76.1   88.9 88.9mm   88.9   76.1       88.9 88.9mm   76.1   88.9 88.9mm 88.9mm   88.9 88.9mm   88.9 139.7mm   114.3 139.7mm 139.7mm   114.3 139.7mm   114.3   114.3 139.7mm 139.7mm 139.7mm 139.7mm 139.7mm
SEER   4.13   4.56   4.24       4.19   4.74   4.55   4.3   4.5 4.965   4.74   4.72       4.42 5.186   4.59   4.48 5.140 4.979   4.62 5.158   4.55 5.108   4.65 5.279 5.270   4.76 5.237   4.76   4.71 5.291 5.249 5.324 5.294 5.229
Power input Cooling Nom. kW   30.8   38.9   46.9       70.5   69.8   80.7   79.2   87.3 81.1   92.2   105       115 99.9   121   130 121.4 129.1   147 141.4   163 162.1   190 159.6 180.7   207 202.0   224   242 221.3 242.8 261.1 282.2 323.5
Casing Material     Galvanized and painted steel sheet   Galvanized and painted steel sheet   Galvanized and painted steel sheet       Galvanized and painted steel sheet   Galvanized and painted steel sheet   Galvanized and painted steel sheet   Galvanized and painted steel sheet   Galvanized and painted steel sheet Galvanized and painted steel sheet   Galvanized and painted steel sheet   Galvanized and painted steel sheet       Galvanized and painted steel sheet Galvanized and painted steel sheet   Galvanized and painted steel sheet   Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet   Galvanized and painted steel sheet Galvanized and painted steel sheet   Galvanized and painted steel sheet Galvanized and painted steel sheet   Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet   Galvanized and painted steel sheet Galvanized and painted steel sheet   Galvanized and painted steel sheet   Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet Galvanized and painted steel sheet
  Colour     Ivory white   Ivory white   Ivory white       Ivory white   Ivory white   Ivory white   Ivory white   Ivory white Ivory white   Ivory white   Ivory white       Ivory white Ivory white   Ivory white   Ivory white Ivory white Ivory white   Ivory white Ivory white   Ivory white Ivory white   Ivory white Ivory white Ivory white   Ivory white Ivory white   Ivory white   Ivory white Ivory white Ivory white Ivory white Ivory white Ivory white
Fan Type     Direct propeller   Direct propeller   Direct propeller       Direct propeller   Direct propeller   Direct propeller   Direct propeller   Direct propeller Direct propeller   Direct propeller   Direct propeller       Direct propeller Direct propeller   Direct propeller   Direct propeller Direct propeller Direct propeller   Direct propeller Direct propeller   Direct propeller Direct propeller   Direct propeller Direct propeller Direct propeller   Direct propeller Direct propeller   Direct propeller   Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller Direct propeller
  Quantity     6   8   10       10   4   4   5   5 4   6   6       6 6   7   7 6 6   8 8   9 8   10 10 10   12 10   13   14 12 12 14 14 16
Notes   (17) - All data are subject to change without notice. Please refer to the unit nameplate data.   (17) - All data are subject to change without notice. Please refer to the unit nameplate data.   (17) - All data are subject to change without notice. Please refer to the unit nameplate data.   (17) - All data are subject to change without notice. Please refer to the unit nameplate data.   (17) - All data are subject to change without notice. Please refer to the unit nameplate data.   (17) - All data are subject to change without notice. Please refer to the unit nameplate data.   (17) - All data are subject to change without notice. Please refer to the unit nameplate data.   (17) - All data are subject to change without notice. Please refer to the unit nameplate data.   (17) - All data are subject to change without notice. Please refer to the unit nameplate data.     (17) - All data are subject to change without notice. Please refer to the unit nameplate data.   (17) - All data are subject to change without notice. Please refer to the unit nameplate data.   (17) - All data are subject to change without notice. Please refer to the unit nameplate data.   (17) - All data are subject to change without notice. Please refer to the unit nameplate data.     (17) - All data are subject to change without notice. Please refer to the unit nameplate data.   (17) - All data are subject to change without notice. Please refer to the unit nameplate data.       (17) - All data are subject to change without notice. Please refer to the unit nameplate data.     (17) - All data are subject to change without notice. Please refer to the unit nameplate data.     (17) - All data are subject to change without notice. Please refer to the unit nameplate data.       (17) - All data are subject to change without notice. Please refer to the unit nameplate data.     (17) - All data are subject to change without notice. Please refer to the unit nameplate data.   (17) - All data are subject to change without notice. Please refer to the unit nameplate data.
Water heat exchanger - evaporator Type                                       Brazed plate                 Brazed plate         Brazed plate Brazed plate     Brazed plate     Brazed plate     Brazed plate Brazed plate     Brazed plate         Brazed plate Brazed plate Brazed plate Brazed plate Brazed plate
Operation range Air side Cooling Min. °CDB                                     -20                 -20         -20 -20     -20     -20     -20 -20     -20         -20 -20 -20 -20 -20
      Max. °CDB                                     52                 52         52 52     52     52     52 52     52         52 52 52 52 52
  Water side Evaporator Min. °CDB                                     -13                 -13         -13 -13     -13     -13     -13 -13     -13         -13 -13 -13 -13 -13
      Max. °CDB                                     30                 30         30 30     30     30     30 30     30         30 30 30 30 30