Specifications Table for EWWD-J-SS

EWWD120J-SS EWWD140J-SS EWWD150J-SS EWWD180J-SS EWWD210J-SS EWWD250J-SS EWWD280J-SS EWWD310J-SS EWWD330J-SS EWWD360J-SS EWWD380J-SS EWWD400J-SS EWWD450J-SS EWWD500J-SS EWWD530J-SS EWWD560J-SS
Cooling capacity Nom. kW 119.7 145.7 154.3 177.3 207.3 255.3 284.1 309 (1) 333 (1) 356 (1) 385 (1) 415 (1) 463 (1) 512 (1) 540 (1) 568 (1)
Heating capacity Nom. kW 144.2 175.4 189.8 217.8 252.2 308.4 347.4 388 (2) 417 (2) 446 (2) 486 (2) 515 (2) 573 (2) 631 (2) 669 (2) 709 (2)
Capacity control Method   Stepless Stepless Stepless Stepless Stepless Stepless Stepless Stepless Stepless Stepless Stepless Stepless Stepless Stepless Stepless Stepless
  Minimum capacity % 25 25 25 25 25 25 25 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5
Power input Cooling Nom. kW 28 34 39.5 45.3 50.4 59.9 70 78.8 (1) 84.6 (1) 90.3 (1) 101 (1) 101 (1) 110 (1) 120 (1) 130 (1) 140 (1)
  Heating Nom. kW 27.7 33.7 39.2 44.9 50.1 59.7 69.7 78.8 (2) 84.6 (2) 90.3 (2) 101 (2) 101 (2) 110 (2) 120 (2) 130 (2) 140 (2)
EER 4.28 4.28 3.91 3.92 4.11 4.26 4.06 3.92 (1) 3.94 (1) 3.94 (1) 3.82 (1) 4.12 (1) 4.20 (1) 4.28 (1) 4.16 (1) 4.05 (1)
COP 5.2 5.2 4.84 4.85 5.04 5.17 4.98 4.92 (2) 4.94 (2) 4.94 (2) 4.82 (2) 5.12 (2) 5.20 (2) 5.28 (2) 5.16 (2) 5.05 (2)
ESEER               4.32 4.35 4.50 4.31 4.65 4.74 4.83 4.73 4.33
Dimensions Unit Depth mm 2684 2684 2684 2684 2684 2684 2684 2684 2684 2684 2684 2684 2684 2684 2684 2684
    Height mm 1020 1020 1020 1020 1020 1020 1020 2000 2000 2000 2000 2000 2000 2000 2000 2000
    Width mm 913 913 913 913 913 913 913 913 913 913 913 913 913 913 913 913
Weight Unit kg 1177 1233 1334 1366 1416 1600 1607 2668 2700 2732 2782 2832 3016 3200 3207 3215
  Operation weight kg 1211 1276 1378 1415 1473 1663 1675 2755 2792 2830 2888 2946 3136 3327 3338 3350
Water heat exchanger - evaporator Type   Plate heat exchanger Plate heat exchanger Plate heat exchanger Plate heat exchanger Plate heat exchanger Plate heat exchanger Plate heat exchanger Plate heat exchanger Plate heat exchanger Plate heat exchanger Plate heat exchanger Plate heat exchanger Plate heat exchanger Plate heat exchanger Plate heat exchanger Plate heat exchanger
  Water volume l 14 18 14 17 20 26 26 29 31 33 37 41 46 52 52 52
  Water flow rate Nom. l/s 5.7 7 7.4 8.5 9.9 12.2 13.6 14.8 15.9 17.0 18.4 19.8 22.1 24.5 25.8 27.2
Water heat exchanger - condenser Type                 Single pass shell and tube Single pass shell and tube Single pass shell and tube Single pass shell and tube Single pass shell and tube Single pass shell and tube Single pass shell and tube Single pass shell and tube Single pass shell and tube
  Water flow rate Nom. l/s               9.3 9.3 10.7 11.0 12.4 12.4 15.2 15.3 17.0
Compressor Type   Single screw compressor Single screw compressor Single screw compressor Single screw compressor Single screw compressor Single screw compressor Single screw compressor Single screw compressor Single screw compressor Single screw compressor Single screw compressor Single screw compressor Single screw compressor Single screw compressor Single screw compressor Single screw compressor
  Quantity   1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 2
Sound power level Cooling Nom. dBA 95.0 95.0 95.0 95.0 95.0 95.0 95.0 94 94 94 94 94 94 94 94 94
Sound pressure level Cooling Nom. dBA 79.0 79.0 79.0 79.0 79.0 79.0 79.0 82 (3) 82 (3) 82 (3) 82 (3) 82 (3) 82 (3) 82 (3) 82 (3) 82 (3)
Operation range Evaporator Cooling Min. °CDB               -10 -10 -10 -10 -10 -10 -10 -10 -10
      Max. °CDB               15 15 15 15 15 15 15 15 15
  Condenser Cooling Min. °CDB               23 23 23 23 23 23 23 23 23
      Max. °CDB               60 60 60 60 60 60 60 60 60
Refrigerant Type   R-134a R-134a R-134a R-134a R-134a R-134a R-134a R-134a R-134a R-134a R-134a R-134a R-134a R-134a R-134a R-134a
  Charge kg 18 35 34 37 37 38 38
  Circuits Quantity   1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 2
  GWP   1,430.0 1,430.0 1,430.0 1,430.0 1,430.0 1,430.0 1,430.0 1430 1430 1430 1430 1430 1430 1430 1430 1430
Refrigerant charge Per circuit kg               33.0 33.5 34.0 35.0 36.0 37.0 38.0 38.0 38.0
  Per circuit tCO2Eq               47.2 47.9 48.6 50.1 51.5 52.9 54.3 54.3 54.3
Space heating Average climate water outlet 55°C General SCOP   4.03 4.11 4.16 4.17 4.17 4.23 3.83
  Average climate water outlet 35°C General SCOP                 4.04
Energy Efficiency Range Space Heating A+++ ~ D, Water Heating A+ ~ F Space Heating A+++ ~ D, Water Heating A+ ~ F Space Heating A+++ ~ D, Water Heating A+ ~ F Space Heating A+++ ~ D, Water Heating A+ ~ F Space Heating A+++ ~ D, Water Heating A+ ~ F Space Heating A+++ ~ D, Water Heating A+ ~ F Space Heating A+++ ~ D, Water Heating A+ ~ F Space Heating A+++ ~ D, Water Heating A+ ~ F Space Heating A+++ ~ D, Water Heating A+ ~ F Space Heating A+++ ~ D, Water Heating A+ ~ F Space Heating A+++ ~ D, Water Heating A+ ~ F Space Heating A+++ ~ D, Water Heating A+ ~ F Space Heating A+++ ~ D, Water Heating A+ ~ F Space Heating A+++ ~ D, Water Heating A+ ~ F Space Heating A+++ ~ D, Water Heating A+ ~ F Space Heating A+++ ~ D, Water Heating A+ ~ F
Power supply Phase   3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~
  Frequency Hz 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
  Voltage V 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400
Notes (1) - Cooling: EW 12°C; LW 7°C; ambient conditions: 35°CDB (1) - Cooling: EW 12°C; LW 7°C; ambient conditions: 35°CDB (1) - Cooling: EW 12°C; LW 7°C; ambient conditions: 35°CDB (1) - Cooling: EW 12°C; LW 7°C; ambient conditions: 35°CDB (1) - Cooling: EW 12°C; LW 7°C; ambient conditions: 35°CDB (1) - Cooling: EW 12°C; LW 7°C; ambient conditions: 35°CDB (1) - Cooling: EW 12°C; LW 7°C; ambient conditions: 35°CDB (1) - Cooling: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation. (1) - Cooling: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation. (1) - Cooling: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation. (1) - Cooling: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation. (1) - Cooling: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation. (1) - Cooling: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation. (1) - Cooling: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation. (1) - Cooling: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation. (1) - Cooling: entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation.
  (2) - Cooling: EW 23°C; LW 18°C; ambient conditions: 35°CDB (2) - Cooling: EW 23°C; LW 18°C; ambient conditions: 35°CDB (2) - Cooling: EW 23°C; LW 18°C; ambient conditions: 35°CDB (2) - Cooling: EW 23°C; LW 18°C; ambient conditions: 35°CDB (2) - Cooling: EW 23°C; LW 18°C; ambient conditions: 35°CDB (2) - Cooling: EW 23°C; LW 18°C; ambient conditions: 35°CDB (2) - Cooling: EW 23°C; LW 18°C; ambient conditions: 35°CDB (2) - Heating capacity, unit power input and COP are based on the following conditions: evaporator 15/10°C; condensor 40/45°C, unit at full load operation (2) - Heating capacity, unit power input and COP are based on the following conditions: evaporator 15/10°C; condensor 40/45°C, unit at full load operation (2) - Heating capacity, unit power input and COP are based on the following conditions: evaporator 15/10°C; condensor 40/45°C, unit at full load operation (2) - Heating capacity, unit power input and COP are based on the following conditions: evaporator 15/10°C; condensor 40/45°C, unit at full load operation (2) - Heating capacity, unit power input and COP are based on the following conditions: evaporator 15/10°C; condensor 40/45°C, unit at full load operation (2) - Heating capacity, unit power input and COP are based on the following conditions: evaporator 15/10°C; condensor 40/45°C, unit at full load operation (2) - Heating capacity, unit power input and COP are based on the following conditions: evaporator 15/10°C; condensor 40/45°C, unit at full load operation (2) - Heating capacity, unit power input and COP are based on the following conditions: evaporator 15/10°C; condensor 40/45°C, unit at full load operation (2) - Heating capacity, unit power input and COP are based on the following conditions: evaporator 15/10°C; condensor 40/45°C, unit at full load operation
  (3) - Condition: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) (3) - Condition: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) (3) - Condition: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) (3) - Condition: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) (3) - Condition: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) (3) - Condition: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) (3) - Condition: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) (3) - Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744 (3) - Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744 (3) - Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744 (3) - Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744 (3) - Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744 (3) - Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744 (3) - Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744 (3) - Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744 (3) - Sound level data are measured at entering evaporator water temp. 12°C; leaving evaporator water temp. 7°C; entering condenser water temp. 30°C; leaving condenser water temp. 35°C; full load operation; standard: ISO3744
  (4) - Condition: Ta DB/WB 7°C/6°C - LWC 45°C (Dt=5°C) (4) - Condition: Ta DB/WB 7°C/6°C - LWC 45°C (Dt=5°C) (4) - Condition: Ta DB/WB 7°C/6°C - LWC 45°C (Dt=5°C) (4) - Condition: Ta DB/WB 7°C/6°C - LWC 45°C (Dt=5°C) (4) - Condition: Ta DB/WB 7°C/6°C - LWC 45°C (Dt=5°C) (4) - Condition: Ta DB/WB 7°C/6°C - LWC 45°C (Dt=5°C) (4) - Condition: Ta DB/WB 7°C/6°C - LWC 45°C (Dt=5°C) (4) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (4) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (4) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (4) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (4) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (4) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (4) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (4) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (4) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
  (5) - According to EN14825 (5) - According to EN14825 (5) - According to EN14825 (5) - According to EN14825 (5) - According to EN14825 (5) - According to EN14825 (5) - According to EN14825 (5) - Maximum starting current: starting current of biggest compressor + current of the other compressor at 75 % of maximum load (5) - Maximum starting current: starting current of biggest compressor + current of the other compressor at 75 % of maximum load (5) - Maximum starting current: starting current of biggest compressor + current of the other compressor at 75 % of maximum load (5) - Maximum starting current: starting current of biggest compressor + current of the other compressor at 75 % of maximum load (5) - Maximum starting current: starting current of biggest compressor + current of the other compressor at 75 % of maximum load (5) - Maximum starting current: starting current of biggest compressor + current of the other compressor at 75 % of maximum load (5) - Maximum starting current: starting current of biggest compressor + current of the other compressor at 75 % of maximum load (5) - Maximum starting current: starting current of biggest compressor + current of the other compressor at 75 % of maximum load (5) - Maximum starting current: starting current of biggest compressor + current of the other compressor at 75 % of maximum load
  (6) - Depends on operation mode, refer to installation manual. (6) - Depends on operation mode, refer to installation manual. (6) - Depends on operation mode, refer to installation manual. (6) - Depends on operation mode, refer to installation manual. (6) - Depends on operation mode, refer to installation manual. (6) - Depends on operation mode, refer to installation manual. (6) - Depends on operation mode, refer to installation manual. (6) - Nominal current cooling mode is referred to the following conditions: evaporator 12/7°C; condenser 30/35°C; compressors current (6) - Nominal current cooling mode is referred to the following conditions: evaporator 12/7°C; condenser 30/35°C; compressors current (6) - Nominal current cooling mode is referred to the following conditions: evaporator 12/7°C; condenser 30/35°C; compressors current (6) - Nominal current cooling mode is referred to the following conditions: evaporator 12/7°C; condenser 30/35°C; compressors current (6) - Nominal current cooling mode is referred to the following conditions: evaporator 12/7°C; condenser 30/35°C; compressors current (6) - Nominal current cooling mode is referred to the following conditions: evaporator 12/7°C; condenser 30/35°C; compressors current (6) - Nominal current cooling mode is referred to the following conditions: evaporator 12/7°C; condenser 30/35°C; compressors current (6) - Nominal current cooling mode is referred to the following conditions: evaporator 12/7°C; condenser 30/35°C; compressors current (6) - Nominal current cooling mode is referred to the following conditions: evaporator 12/7°C; condenser 30/35°C; compressors current
  (7) - For more details, see operation range drawing (7) - For more details, see operation range drawing (7) - For more details, see operation range drawing (7) - For more details, see operation range drawing (7) - For more details, see operation range drawing (7) - For more details, see operation range drawing (7) - For more details, see operation range drawing (7) - Maximum running current is based on max compressor absorbed current in its envelope (7) - Maximum running current is based on max compressor absorbed current in its envelope (7) - Maximum running current is based on max compressor absorbed current in its envelope (7) - Maximum running current is based on max compressor absorbed current in its envelope (7) - Maximum running current is based on max compressor absorbed current in its envelope (7) - Maximum running current is based on max compressor absorbed current in its envelope (7) - Maximum running current is based on max compressor absorbed current in its envelope (7) - Maximum running current is based on max compressor absorbed current in its envelope (7) - Maximum running current is based on max compressor absorbed current in its envelope
                (8) - Maximum unit current for wires sizing is based on minimum allowed voltage. (8) - Maximum unit current for wires sizing is based on minimum allowed voltage. (8) - Maximum unit current for wires sizing is based on minimum allowed voltage. (8) - Maximum unit current for wires sizing is based on minimum allowed voltage. (8) - Maximum unit current for wires sizing is based on minimum allowed voltage. (8) - Maximum unit current for wires sizing is based on minimum allowed voltage. (8) - Maximum unit current for wires sizing is based on minimum allowed voltage. (8) - Maximum unit current for wires sizing is based on minimum allowed voltage. (8) - Maximum unit current for wires sizing is based on minimum allowed voltage.
                (9) - Maximum current for wires sizing: compressor full load ampere x 1.1 (9) - Maximum current for wires sizing: compressor full load ampere x 1.1 (9) - Maximum current for wires sizing: compressor full load ampere x 1.1 (9) - Maximum current for wires sizing: compressor full load ampere x 1.1 (9) - Maximum current for wires sizing: compressor full load ampere x 1.1 (9) - Maximum current for wires sizing: compressor full load ampere x 1.1 (9) - Maximum current for wires sizing: compressor full load ampere x 1.1 (9) - Maximum current for wires sizing: compressor full load ampere x 1.1 (9) - Maximum current for wires sizing: compressor full load ampere x 1.1
                (10) - Fluid: Water (10) - Fluid: Water (10) - Fluid: Water (10) - Fluid: Water (10) - Fluid: Water (10) - Fluid: Water (10) - Fluid: Water (10) - Fluid: Water (10) - Fluid: Water
                (11) - For more details on the operating limits please refer to the Chiller Selection Software (CSS). (11) - For more details on the operating limits please refer to the Chiller Selection Software (CSS). (11) - For more details on the operating limits please refer to the Chiller Selection Software (CSS). (11) - For more details on the operating limits please refer to the Chiller Selection Software (CSS). (11) - For more details on the operating limits please refer to the Chiller Selection Software (CSS). (11) - For more details on the operating limits please refer to the Chiller Selection Software (CSS). (11) - For more details on the operating limits please refer to the Chiller Selection Software (CSS). (11) - For more details on the operating limits please refer to the Chiller Selection Software (CSS). (11) - For more details on the operating limits please refer to the Chiller Selection Software (CSS).
                (12) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels. (12) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels. (12) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels. (12) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels. (12) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels. (12) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels. (12) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels. (12) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels. (12) - Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction, details can be found on the unit labels.