Specifications Table for FDXM-F9 / RXM-R9

FDXM25F3V1B9 / RXM25R5V1B9 FDXM35F3V1B9 / RXM35R5V1B9
Cooling capacity Min. kW 1.30 1.40
  Nom. kW 2.40 3.40
  Max. kW 3.00 3.80
Heating capacity Min. kW 1.30 1.40
  Nom. kW 3.20 4.00
  Max. kW 4.50 5.00
Nominal efficiency Annual energy consumption kWh 318 570
  COP   4.00 3.48
  EER   3.77 2.98
  Energy labeling Directive Cooling   A C
    Heating   A B
Space cooling Annual energy consumption kWh/a 148 226
  Energy efficiency class   A+ A
  Capacity Pdesign kW 2.40 3.40
  SEER   5.68 5.26
Space heating (Average climate) Annual energy consumption kWh/a 858 1,046
  Capacity Pdesign kW 2.60 2.90
  Energy efficiency class   A+ A
  Pdh Heating capacity at -10° kW 2.16
  SCOP/A   4.24 3.88
Notes (1) - See separate drawing for electrical data (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m.
  (2) - See separate drawing for operation range (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m.
  (3) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. (3) - See separate drawing for operation range
  (4) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. (4) - See separate drawing for electrical data