Specifications Table for FWC-DF

FWC07DAFN5V3--
Cooling capacity (standard conditions) Sensible capacity 4-pipe Low kW 3.26
    High kW 5.58
  Total capacity 4-pipe Low kW 4.35
    High kW 7.15
Heating capacity (standard conditions) Capacity 4-pipe Low kW 5.34
    High kW 8.82
Power input Low kW 0.02
  High kW 0.069
Dimensions Unit Height mm 287
    Width mm 837
    Depth mm 921
Weight Unit kg 27
Fan Air flow rate Low m³/h 686
    High m³/h 1296
Total sound power level Low dBA 36
  High dBA 52
Sound pressure level Low dBA 23
  High dBA 39
Water flow Cooling Low l/h 776
    High l/h 1295
  Heating Low l/h 459
    High l/h 759
  Water pressure drop Cooling Low kPa 13
      High kPa 25
    Heating Low kPa 13
      High kPa 24
Piping connections Water Inlet   3/4" BSP (female thread)
    Outlet   3/4" BSP (female thread)
  Drain OD mm VP25 (External dia.32; internal dia. 25)
Power supply Type   230 / 1 / 50
  Phase   1~
  Frequency Hz 50
  Voltage V 230
Notes (1) - Cooling: air 27°CDB, 19°CWB; entering water 7°C; leaving water 12°C
  (2) - Heating: 2 pipe: air 20°CDB, 15°CWB; entering water 45°C; leaving water 40°C
  (3) - Heating: 4 pipe: air 20°CDB, 15°CWB; entering water 65°C; leaving water 55°C
  (4) - Do not let water of less than 5°C or more than 90°C enter the unit, this may damage the unit ..
  (5) - Airflow: 20°C DB, 15°C WB; 230V 50Hz 0Pa ..