| HXHD125A8V1B | HXHD200A8Y1B | |||||
|---|---|---|---|---|---|---|
| Casing | Colour | Metallic grey | Metallic grey | |||
| Material | Precoated sheet metal | Precoated sheet metal | ||||
| Dimensions | Unit | Height | mm | 705 | 705 | |
| Width | mm | 600 | 600 | |||
| Depth | mm | 695 | 695 | |||
| Weight | Unit | kg | 92 | 147 | ||
| Refrigerant | Type | R-134a | R-134a | |||
| Charge | kg | 2 | 2.6 | |||
| Sound power level | Nom. | dBA | 55 | 60 | ||
| Sound pressure level | Nom. | dBA | 42, 43 | 46, 46 | ||
| Operation range | Heating | Water side | Min. | °C | 25 | 25 |
| Max. | °C | 80.0 | 80.0 | |||
| Power supply | Phase | 1~ | 3~ | |||
| Frequency | Hz | 50 | 50 | |||
| Voltage | V | 220-240 | 380-415 | |||
| Current | Recommended fuses | A | 20 | 16 | ||
| Notes | (1) - EW 40°C; LW 45°C; Dt 5°C; ambient conditions: 7°CDB/6°CWB | (1) - EW 40°C; LW 45°C; Dt 5°C; ambient conditions: 7°CDB/6°CWB | ||||
| (2) - For water Dt 5°C | (2) - For water Dt 10°C | |||||
| (3) - Sound levels are measured at: EW 55°C; LW 65°C | (3) - Sound levels are measured at: EW 55°C; LW 65°C | |||||
| (4) - Sound levels are measured at: EW 70°C; LW 80°C | (4) - Sound levels are measured at: EW 70°C; LW 80°C | |||||
| (5) - Field setting | (5) - Field setting | |||||
| (6) - In accordance with EN/IEC 61000-3-11, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply with Zsys (system impedance) ≤ Zmax | (6) - In accordance with EN/IEC 61000-3-11, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply with Zsys (system impedance) ≤ Zmax | |||||
| (7) - European/International Technical Standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated current ≤ 75A. | (7) - European/International Technical Standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated current ≤ 75A. | |||||
| (8) - Zsys: system impedance | (8) - Zsys: system impedance | |||||
| (9) - Short-circuit power | (9) - Short-circuit power | |||||