JEHSCU0360CM3 |
JEHSCU0800CM3 |
JEHSCU1000CM3 |
JEHSCU0200CM3 |
JEHSCU0250CM3 |
JEHSCU0300CM3 |
JEHSCU0350CM3 |
JEHSCU0400CM3 |
JEHSCU0500CM3 |
JEHSCU0600CM3 |
JEHSCU0680CM3 |
Refrigerating capacity
|
Medium temperature
|
R-407A
|
Nom
|
kW
|
5.77
|
12.95
|
|
3.45
|
4.05
|
4.69
|
|
6.76
|
8.28
|
9.54
|
10.70
|
|
|
R-134a
|
Nom
|
kW
|
3.80
|
8.21
|
10.75
|
2.24
|
|
|
3.48
|
4.37
|
|
|
R-407F
|
Nom
|
kW
|
5.73
|
12.90
|
|
3.33
|
3.94
|
4.58
|
|
6.75
|
8.18
|
9.59
|
Annual electricity consumption Q
|
R-407A
|
Te -10°C
|
kWh/a
|
10,186.80
|
25,490.84
|
|
|
|
|
|
10,972.69
|
15,847.87
|
18,407.87
|
22,239.63
|
|
R-134a
|
Te -10°C
|
kWh/a
|
|
16,256.53
|
19,586.43
|
|
R-407F
|
Te -10°C
|
kWh/a
|
10,932.85
|
26,882.45
|
|
|
|
|
|
11,873.19
|
16,401.48
|
18,902.83
|
Parameters at full load and ambient temp. 43°C
|
R-134a
|
Te -10°C
|
Power input (D3)
|
kW
|
|
4.56
|
5.92
|
|
|
|
2.02
|
|
|
|
Declared COP (COP3)
|
|
|
1.59
|
1.60
|
|
|
|
1.52
|
|
|
|
Cooling capacity (P3)
|
kW
|
|
7.26
|
9.46
|
|
|
|
3.06
|
Weight
|
Unit
|
kg
|
112
|
204
|
226
|
69.7
|
71.7
|
73.7
|
73.7
|
119
|
123
|
125
|
126
|
Parameters at full load and ambient temp. 25°C
|
R-407A
|
Te -10°C
|
Declared COP (COP2)
|
|
|
|
|
2.55
|
2.36
|
2.26
|
|
|
|
Power input (D2)
|
kW
|
|
|
|
1.44
|
1.82
|
2.22
|
|
|
|
Cooling capacity (P2)
|
kW
|
|
|
|
3.69
|
4.31
|
5.00
|
|
R-407F
|
Te -10°C
|
Power input (D2)
|
kW
|
|
|
|
1.52
|
1.88
|
2.36
|
|
|
|
Cooling capacity (P2)
|
kW
|
|
|
|
3.64
|
4.31
|
5.06
|
|
|
|
Declared COP (COP2)
|
|
|
|
|
2.39
|
2.29
|
2.14
|
|
R-134a
|
Te -10°C
|
Cooling capacity (P2)
|
kW
|
4.06
|
|
|
2.38
|
|
|
3.71
|
4.70
|
|
|
|
Declared COP (COP2)
|
|
2.86
|
|
|
2.62
|
|
|
2.46
|
2.90
|
|
|
|
Power input (D2)
|
kW
|
1.42
|
|
|
0.91
|
|
|
1.51
|
1.62
|
Seasonal energy performance ratio SEPR
|
R-407F
|
Te -10°C
|
|
3.22
|
2.95
|
|
|
|
|
|
3.50
|
3.07
|
3.12
|
|
R-407A
|
Te -10°C
|
|
3.48
|
3.12
|
|
|
|
|
|
3.79
|
3.21
|
3.19
|
2.96
|
|
R-134a
|
Te -10°C
|
|
|
3.10
|
3.37
|
Refrigerant
|
GWP Type 4
|
|
1,495
|
1,495
|
|
1,495
|
1,495
|
1,495
|
|
1,495
|
|
1,495
|
1,495
|
|
GWP Type 5
|
|
1,387
|
1,387
|
1,387
|
1,387
|
1,387
|
1,387
|
1,387
|
1,387
|
1,387
|
1,387
|
1,387
|
|
GWP Type 2
|
|
2,107
|
2,107
|
|
2,107
|
2,107
|
2,107
|
|
2,107
|
2,107
|
2,107
|
2,107
|
|
GWP Type 3
|
|
1,825
|
1,825
|
|
1,825
|
1,825
|
1,825
|
|
1,825
|
1,825
|
1,825
|
|
GWP
|
|
1,430
|
1,430
|
1,430
|
1,430
|
|
|
1,430
|
1,430
|
|
Type 3
|
|
R-407F
|
R-407F
|
|
R-407F
|
R-407F
|
R-407F
|
|
R-407F
|
R-407F
|
R-407F
|
|
Type 2
|
|
R-407A
|
R-407A
|
|
R-407A
|
R-407A
|
R-407A
|
|
R-407A
|
R-407A
|
R-407A
|
R-407A
|
|
Type 5
|
|
R-448A
|
R-448A
|
R-448A
|
R-448A
|
R-448A
|
R-448A
|
R-448A
|
R-448A
|
R-448A
|
R-448A
|
R-448A
|
|
Type 4
|
|
R-407H
|
R-407H
|
|
R-407H
|
R-407H
|
R-407H
|
|
R-407H
|
|
R-407H
|
R-407H
|
|
Type
|
|
R-134a
|
R-134a
|
R-134a
|
R-134a
|
|
|
R-134a
|
R-134a
|
Parameters at full load and ambient temp. 32°C (Point A)
|
R-134a
|
Te -10°C
|
Rated COP (COPA)
|
|
2.36
|
2.20
|
2.21
|
2.18
|
|
|
2.08
|
2.36
|
|
|
|
Rated cooling capacity (PA)
|
kW
|
3.80
|
8.21
|
10.75
|
2.24
|
|
|
3.48
|
4.37
|
|
|
|
Rated power input (DA)
|
kW
|
1.61
|
3.74
|
4.86
|
1.02
|
|
|
1.68
|
1.85
|
|
R-407F
|
Te -10°C
|
Rated COP (COPA)
|
|
1.97
|
2.10
|
|
1.88
|
1.83
|
1.69
|
|
2.10
|
1.88
|
1.91
|
|
|
|
Rated cooling capacity (PA)
|
kW
|
5.73
|
12.90
|
|
3.33
|
3.94
|
4.58
|
|
6.75
|
8.18
|
9.59
|
|
|
|
Rated power input (DA)
|
kW
|
2.91
|
6.13
|
|
1.78
|
2.16
|
2.70
|
|
3.21
|
4.36
|
5.03
|
|
R-407A
|
Te -10°C
|
Rated power input (DA)
|
kW
|
2.58
|
6.24
|
|
1.62
|
2.04
|
2.44
|
|
2.97
|
3.93
|
4.65
|
5.54
|
|
|
|
Rated COP (COPA)
|
|
2.24
|
2.08
|
|
2.12
|
1.99
|
1.92
|
|
2.28
|
2.11
|
2.05
|
1.93
|
|
|
|
Rated cooling capacity (PA)
|
kW
|
5.77
|
12.95
|
|
3.45
|
4.05
|
4.69
|
|
6.76
|
8.28
|
9.54
|
10.70
|
Power input
|
Medium temperature
|
R-134a
|
Nom
|
kW
|
1.61
|
3.74
|
4.86
|
1.02
|
|
|
1.68
|
1.85
|
|
|
R-407F
|
Nom
|
kW
|
2.91
|
6.13
|
|
1.78
|
2.16
|
2.70
|
|
3.21
|
4.36
|
5.03
|
|
|
R-407A
|
Nom
|
kW
|
2.58
|
6.24
|
|
1.62
|
2.04
|
2.44
|
|
2.97
|
3.93
|
4.65
|
5.54
|
COP
|
Medium temperature
|
R-134a
|
|
2.36
|
2.20
|
2.21
|
2.18
|
|
|
2.08
|
2.36
|
|
|
R-407F
|
|
1.97
|
2.10
|
|
1.88
|
1.83
|
1.69
|
|
2.10
|
1.88
|
1.91
|
|
|
R-407A
|
|
2.24
|
2.08
|
|
2.12
|
1.99
|
1.92
|
|
2.28
|
2.11
|
2.05
|
1.93
|
Dimensions
|
Unit
|
Width
|
mm
|
1,353
|
1,348
|
1,348
|
1,101
|
1,101
|
1,101
|
1,101
|
1,353
|
1,353
|
1,353
|
1,353
|
|
|
Depth
|
mm
|
575
|
612
|
612
|
444
|
444
|
444
|
444
|
575
|
575
|
575
|
575
|
|
|
Height
|
mm
|
872
|
1,727
|
1,727
|
662
|
662
|
662
|
662
|
872
|
872
|
872
|
872
|
Casing
|
Colour
|
|
Light grey
|
Light grey
|
Light grey
|
Light grey
|
Light grey
|
Light grey
|
Light grey
|
Light grey
|
Light grey
|
Light grey
|
Light grey
|
Fan
|
Type
|
|
Axial
|
Axial
|
Axial
|
Axial
|
Axial
|
Axial
|
Axial
|
Axial
|
Axial
|
Axial
|
Axial
|
Power supply
|
Phase
|
|
3~
|
3~
|
3~
|
3~
|
3~
|
3~
|
3~
|
3~
|
3~
|
3~
|
3~
|
|
Frequency
|
Hz
|
50
|
50
|
50
|
50
|
50
|
50
|
50
|
50
|
50
|
50
|
50
|
|
Voltage
|
V
|
400
|
400
|
400
|
400
|
400
|
400
|
400
|
400
|
400
|
400
|
400
|
Notes
|
(1) - SRG 20°C, Ta=32°C, Te=-35°C
|
(1) - SRG 20°C, Ta=32°C, Te=-35°C
|
(1) - SRG 20°C, Ta=32°C, Te=-35°C
|
(1) - SRG 20°C, Ta=32°C, Te=-35°C
|
(1) - SRG 20°C, Ta=32°C, Te=-35°C
|
(1) - SRG 20°C, Ta=32°C, Te=-35°C
|
(1) - Refer to condition: Outside ambient temperature = 32°C, Evaporation temperature = -10°C and 10K superheat (medium temperature application)
|
(1) - SRG 20°C, Ta=32°C, Te=-35°C
|
(1) - SRG 20°C, Ta=32°C, Te=-35°C
|
(1) - SRG 20°C, Ta=32°C, Te=-35°C
|
(1) - SRG 20°C, Ta=32°C, Te=-35°C
|
|
(2) - Sound pressure level is measured at 10m in anechoic room
|
(2) - Sound pressure level is measured at 10m in anechoic room
|
(2) - Sound pressure level is measured at 10m in anechoic room
|
(2) - Sound pressure level is measured at 10m in anechoic room
|
(2) - Sound pressure level is measured at 10m in anechoic room
|
(2) - Sound pressure level is measured at 10m in anechoic room
|
(2) - Sound pressure level is measured at 10m in anechoic room
|
(2) - Sound pressure level is measured at 10m in anechoic room
|
(2) - Sound pressure level is measured at 10m in anechoic room
|
(2) - Sound pressure level is measured at 10m in anechoic room
|
(2) - Sound pressure level is measured at 10m in anechoic room
|
|
(3) - Its functioning relies on fluorinated greenhouse gases
|
(3) - Its functioning relies on fluorinated greenhouse gases
|
(3) - Its functioning relies on fluorinated greenhouse gases
|
(3) - Its functioning relies on fluorinated greenhouse gases
|
(3) - Its functioning relies on fluorinated greenhouse gases
|
(3) - Its functioning relies on fluorinated greenhouse gases
|
(3) - Its functioning relies on fluorinated greenhouse gases
|
(3) - Its functioning relies on fluorinated greenhouse gases
|
(3) - Its functioning relies on fluorinated greenhouse gases
|
(3) - Its functioning relies on fluorinated greenhouse gases
|
(3) - Its functioning relies on fluorinated greenhouse gases
|
|
(4) - Published data based on condition - Return Gas Temperature 20°C, except for R-407H
|
(4) - Published data based on condition - Return Gas Temperature 20°C, except for R-407H
|
|
(4) - Published data based on condition - Return Gas Temperature 20°C, except for R-407H
|
(4) - Published data based on condition - Return Gas Temperature 20°C, except for R-407H
|
(4) - Published data based on condition - Return Gas Temperature 20°C, except for R-407H
|
|
(4) - Published data based on condition - Return Gas Temperature 20°C, except for R-407H
|
|
(4) - Published data based on condition - Return Gas Temperature 20°C, except for R-407H
|
(4) - Published data based on condition - Return Gas Temperature 20°C, except for R-407H
|
|
(5) - Published data based on condition - SH10K for R-407H
|
(5) - Published data based on condition - SH10K for R-407H
|
|
(5) - Published data based on condition - SH10K for R-407H
|
(5) - Published data based on condition - SH10K for R-407H
|
(5) - Published data based on condition - SH10K for R-407H
|
|
(5) - Published data based on condition - SH10K for R-407H
|
|
(5) - Published data based on condition - SH10K for R-407H
|
(5) - Published data based on condition - SH10K for R-407H
|