Specifications Table for REYA-A

REYA8A7Y1B REYA10A7Y1B. REYA10A7Y1B REYA12A7Y1B REYA13A7Y1B REYA14A7Y1B REYA16A7Y1B. REYA16A7Y1B REYA18A7Y1B. REYA18A7Y1B REYA20A7Y1B REYA20A7Y1B. REYA22A7Y1B REYA24A7Y1B REYA26A7Y1B REYA28A7Y1B
System Outdoor unit module 1           REMA5A   REYA8A   REYA8A       REYA10A REYA8A REYA12A REYA12A
  Outdoor unit module 2           REYA8A   REYA8A   REYA10A       REYA12A REYA16A REYA14A REYA16A
Recommended combination 4 x FXFA50A2VEB 4 x FXFA63A2VEB 4 x FXFA63A2VEB 6 x FXFA50A2VEB 3 x FXFA50A2VEB + 3 x FXFA63A2VEB 1 x FXFA50A2VEB + 5 x FXFA63A2VEB 4 x FXFA63A2VEB + 2 x FXFA80A2VEB 4 x FXFA63A2VEB + 2 x FXFA80A2VEB 4 x FXFA50A2VEB + 4 x FXFA63A2VEB 3 x FXFA50A2VEB + 5 x FXFA63A2VEB 8 x FXFA63A2VEB 10 x FXFA50A2VEB 6 x FXFA50A2VEB + 4 x FXFA63A2VEB 4 x FXFA50A2VEB + 4 x FXFA63A2VEB + 2 x FXFA80A2VEB 7 x FXFA50A2VEB + 5 x FXFA63A2VEB 6 x FXFA50A2VEB + 4 x FXFA63A2VEB + 2 x FXFA80A2VEB
Recommended combination 2 4 x FXSA50A2VEB 4 x FXSA63A2VEB 4 x FXSA63A2VEB 6 x FXSA50A2VEB 3 x FXSA50A2VEB + 3 x FXSA63A2VEB 1 x FXSA50A2VEB + 5 x FXSA63A2VEB 4 x FXSA63A2VEB + 2 x FXSA80A2VEB 4 x FXSA63A2VEB + 2 x FXSA80A2VEB 4 x FXSA50A2VEB + 4 x FXSA63A2VEB 3 x FXSA50A2VEB + 5 x FXSA63A2VEB 8 x FXSA63A2VEB 10 x FXSA50A2VEB 6 x FXSA50A2VEB + 4 x FXSA63A2VEB 4 x FXSA50A2VEB + 4 x FXSA63A2VEB + 2 x FXSA80A2VEB 7 x FXSA50A2VEB + 5 x FXSA63A2VEB 6 x FXSA50A2VEB + 4 x FXSA63A2VEB + 2 x FXSA80A2VEB
Recommended combination 3 4 x FXMA50A5VEB 4 x FXMA63A5VEB 4 x FXMA63A5VEB 6 x FXMA50A5VEB 3 x FXMA50A5VEB + 3 x FXMA50A5VEB 1 x FXMA50A5VEB + 5 x FXMA63A5VEB 4 x FXMA63A5VEB + 2 x FXMA80A5VEB 4 x FXMA63A5VEB + 2 x FXMA80A5VEB 4 x FXMA50A5VEB + 4 x FXMA63A5VEB 3 x FXMA50A5VEB + 5 x FXMA63A5VEB 8 x FXMA63A5VEB 10 x FXMA50A5VEB 6 x FXMA50A5VEB + 4 x FXMA63A5VEB 4 x FXMA50A5VEB + 4 x FXMA63A5VEB + 2 x FXMA80A5VEB 7 x FXMA50A5VEB + 5 x FXMA63A5VEB 6 x FXMA50A5VEB + 4 x FXMA63A5VEB + 2 x FXMA80A5VEB
Continuous heating   Yes     Yes   Yes   Yes     Yes Yes Yes Yes Yes
Heating capacity Nom. 6°CWB kW 22.4 (2)     33.5 (2) 36.4 (2) 40.0 (2) 44.8 (2) 45.0 (2) 50.4 (2) 50.4 (2)     61.5 (2) 67.4 (2) 73.5 (2) 78.5 (2)
COP at nom. capacity 6°CWB kW/kW 3.83 (2)     3.46 (2) 3.76 (2) 3.57 (2) 3.72 (2) 3.52 (2) 3.61 (2) 3.66 (2)     3.46 (2) 3.62 (2) 3.52 (2) 3.49 (2)
SCOP 4.11 4.09 4.33 4.49 4.11 4.28 4.35 4.26 4.34 4.39 4.14 4.38 4.41 4.20 4.38 4.36
SCOP recommended combination 2 4.10 4.14 4.34 4.56 4.19 4.33 4.38 4.33 4.40 4.33 4.11 4.48 4.45 4.24 4.44 4.43
SCOP recommended combination 3 4.15 4.16 4.40 4.56 4.22 4.33 4.37 4.32 4.46 4.39 4.14 4.50 4.48 4.25 4.44 4.43
SEER 7.35 7.62 7.14 7.21 7.49 7.73 7.40 7.10 7.26 7.09 6.63 7.27 7.17 7.16 7.48 7.15
SEER recommended combination 2 7.07 7.3 6.87 6.90 7.15 7.53 6.93 7.01 6.95 6.94 6.57 6.94 6.88 7.01 7.23 6.96
SEER recommended combination 3 7.49 7.61 7.15 7.41 7.57 7.78 7.31 7.15 7.30 7.11 6.64 7.48 7.28 7.29 7.61 7.26
Space cooling A Condition (35°C - 27/19) EERd   3.25     3.24 3.46 3.26 3.25 3.23 3.26 2.73     3.25 3.24 3.25 3.23
    Pdc kW 22.4     33.5 36.4 40.0 44.8 45.0 50.4 50.4     61.5 67.4 73.5 78.5
  B Condition (30°C - 27/19) EERd   5.23     4.60 6.08 4.92 5.41 4.58 5.18 4.47     4.78 4.78 4.77 4.59
    Pdc kW 16.5     24.7 26.8 29.5 33.0 33.2 37.1 37.1     45.3 49.7 54.2 57.8
  C Condition (25°C - 27/19) EERd   9.11     8.45 9.04 8.74 9.11 8.25 8.76 8.15     8.47 8.52 8.61 8.33
    Pdc kW 10.6     15.9 18.0 18.9 21.2 21.3 23.9 23.9     29.1 31.9 34.8 37.2
  D Condition (20°C - 27/19) EERd   15.3     17.7 13.9 22.5 15.0 16.7 15.0 20.7     16.2 16.0 20.1 17.1
    Pdc kW 8.13     8.57 15.5 10.9 15.9 11.1 16.3 12.0     16.8 19.2 19.5 19.7
Space cooling recommended combination 2 A Condition (35°C - 27/19) EERd   3.23     3.00 3.36 3.23 3.14 3.06 3.23 2.64     3.10 3.11 3.12 3.03
    Pdc kW 22.4     33.5 36.4 40.0 44.8 45.0 50.4 50.4     61.5 67.4 73.5 78.5
  B Condition (30°C - 27/19) EERd   5.09     4.54 5.78 4.85 5.00 4.64 4.94 4.43     4.67 4.78 4.71 4.60
    Pdc kW 16.5     24.7 26.8 29.5 33.0 33.2 37.1 37.1     45.3 49.7 54.2 57.8
  C Condition (25°C - 27/19) EERd   8.55     7.94 8.53 8.38 8.36 8.11 8.27 7.87     8.00 8.25 8.17 8.04
    Pdc kW 10.6     15.9 17.8 18.9 21.2 21.3 23.9 23.9     29.1 31.9 34.8 37.2
  D Condition (20°C - 27/19) EERd   14.6     16.9 13.3 21.7 14.3 16.5 14.3 20.0     15.4 15.6 19.3 16.7
    Pdc kW 7.84     8.20 15.0 10.6 15.5 10.8 15.8 11.6     16.2 18.6 18.8 19.0
Space cooling recommended combination 3 A Condition (35°C - 27/19) EERd   3.22     3.23 3.41 3.30 3.18 3.04 3.25 2.66     3.25 3.13 3.27 3.12
    Pdc kW 22.4     33.5 36.4 40.0 44.8 45.0 50.4 50.4     61.5 67.4 73.5 78.5
  B Condition (30°C - 27/19) EERd   5.31     4.69 6.12 4.93 5.24 4.64 5.08 4.49     4.79 4.94 4.82 4.66
    Pdc kW 16.5     24.7 26.8 29.5 33.0 33.2 37.1 37.1     45.3 49.7 54.1 57.8
  C Condition (25°C - 27/19) EERd   9.41     8.82 9.22 8.84 9.04 8.50 8.94 8.22     8.71 8.77 8.83 8.64
    Pdc kW 10.6     15.9 18.1 18.9 21.2 21.3 23.9 23.9     29.1 31.9 34.8 37.2
  D Condition (20°C - 27/19) EERd   15.7     18.5 14.2 22.4 15.2 16.7 15.4 20.9     16.6 16.2 20.5 17.5
    Pdc kW 8.19     8.50 15.5 10.9 16.0 10.7 16.3 11.9     16.6 18.9 19.4 19.3
Space heating (Average climate) TBivalent COPd (declared COP)   2.80     2.38 2.74 2.57 2.87 2.53 2.51 2.36     2.33 2.62 2.48 2.46
    Pdh (declared heating cap) kW 13.7     18.4 21.7 20.6 23.2 23.2 27.9 27.9     34.4 36.9 39.0 41.6
    Tbiv (bivalent temperature) °C -10     -10 -10 -10 -10 -10 -10 -10     -10 -10 -10 -10
  TOL COPd (declared COP)   2.80     2.38 2.74 2.57 2.87 2.53 2.51 2.36     2.33 2.62 2.48 2.46
    Pdh (declared heating cap) kW 13.7     18.4 21.7 20.6 23.2 23.2 27.9 27.9     34.4 36.9 39.0 41.6
    Tol (temperature operating limit) °C -10     -10 -10 -10 -10 -10 -10 -10     -10 -10 -10 -10
  A Condition (-7°C) COPd (declared COP)   3.06     2.84 3.03 2.94 3.18 2.87 2.87 2.70     2.76 2.94 2.89 2.85
    Pdh (declared heating cap) kW 12.1     16.3 19.2 18.2 20.5 20.5 24.7 24.7     30.4 32.6 34.5 36.8
  B Condition (2°C) COPd (declared COP)   3.81     4.15 4.02 3.86 4.17 3.93 4.20 4.19     4.19 3.89 3.99 4.03
    Pdh (declared heating cap) kW 7.38     9.89 11.7 11.1 12.5 12.5 15.0 15.0     18.5 19.9 21.0 22.4
  C Condition (7°C) COPd (declared COP)   5.27     6.32 5.11 6.31 5.45 6.21 5.60 6.22     6.02 5.82 6.32 6.26
    Pdh (declared heating cap) kW 4.76     6.36 8.40 7.13 8.05 8.03 9.66 9.66     11.9 12.8 13.5 14.4
  D Condition (12°C) COPd (declared COP)   7.04     9.14 6.47 6.68 6.93 6.04 7.49 6.85     8.49 6.47 7.76 7.33
    Pdh (declared heating cap) kW 4.51     5.52 8.93 5.15 9.04 5.07 9.97 6.24     11.0 9.58 10.7 10.6
Space heating (Average climate) recommended combination 2 A Condition (-7°C) COPd (declared COP)   3.00     2.83 3.05 2.95 3.18 2.89 2.86 2.62     2.73 2.93 2.89 2.86
    Pdh (declared heating cap) kW 12.1     16.3 19.2 18.2 20.5 20.5 24.7 24.7     30.4 32.6 34.5 36.8
  B Condition (2°C) COPd (declared COP)   3.80     4.26 4.12 3.89 4.18 3.96 4.27 4.07     4.25 3.90 4.06 4.09
    Pdh (declared heating cap) kW 7.45     9.89 11.7 11.1 12.5 12.5 15.0 15.0     18.5 19.9 21.0 22.4
  C Condition (7°C) COPd (declared COP)   5.35     6.39 5.24 6.45 5.57 6.41 5.78 6.19     6.10 5.97 6.42 6.40
    Pdh (declared heating cap) kW 4.76     6.36 8.54 7.14 8.08 8.04 9.65 9.65     11.9 12.8 13.5 14.4
  D Condition (12°C) COPd (declared COP)   7.04     9.39 6.58 6.94 6.97 6.47 7.59 8.15     8.60 6.72 8.03 7.72
    Pdh (declared heating cap) kW 4.71     5.80 9.17 5.33 9.24 5.36 10.3 7.68     11.4 10.1 11.1 11.2
  TBivalent COPd (declared COP)   2.73     2.38 2.26 2.58 2.38 2.54 2.27 2.28     2.26 2.17 2.24 2.20
    Pdh (declared heating cap) kW 13.7     18.4 21.7 20.6 23.2 23.2 27.9 27.9     34.4 36.9 39.0 41.6
    Tbiv (bivalent temperature) °C -10     -10 -10 -10 -10 -10 -10 -10     -10 -10 -10 -10
  TOL COPd (declared COP)   2.73     2.38 2.26 2.58 2.38 2.54 2.27 2.28     2.26 2.17 2.24 2.20
    Pdh (declared heating cap) kW 13.7     18.4 21.7 20.6 23.2 23.2 27.9 27.9     34.4 36.9 39.0 41.6
    Tol (temperature operating limit) °C -10     -10 -10 -10 -10 -10 -10 -10     -10 -10 -10 -10
Space heating (Average climate) recommended combination 3 A Condition (-7°C) COPd (declared COP)   3.05     2.85 3.07 2.96 3.17 2.88 2.91 2.73     2.77 2.95 2.91 2.87
    Pdh (declared heating cap) kW 12.1     16.3 19.2 18.2 20.5 20.5 24.7 24.8     30.5 32.7 34.6 36.9
  B Condition (2°C) COPd (declared COP)   3.86     4.24 4.14 3.89 4.19 3.95 4.35 4.25     4.28 3.92 4.05 4.08
    Pdh (declared heating cap) kW 7.39     9.89 11.7 11.1 12.5 12.5 15.0 15.0     18.5 19.9 21.0 22.4
  C Condition (7°C) COPd (declared COP)   5.35     6.43 5.25 6.43 5.52 6.34 5.77 6.39     6.12 5.93 6.43 6.38
    Pdh (declared heating cap) kW 4.75     6.36 8.49 7.15 8.04 8.03 9.67 9.66     11.9 12.8 13.5 14.4
  D Condition (12°C) COPd (declared COP)   7.14     9.37 6.64 6.84 6.94 6.44 7.69 5.48     8.65 6.75 7.95 7.68
    Pdh (declared heating cap) kW 4.65     5.67 9.13 5.29 9.17 5.32 10.2 5.80     11.2 9.97 11.0 11.0
  TBivalent COPd (declared COP)   2.78     2.41 2.78 2.58 2.86 2.54 2.53 2.39     2.35 2.62 2.50 2.48
    Pdh (declared heating cap) kW 13.7     18.4 21.7 20.6 23.2 23.2 27.9 28.0     34.4 36.9 39.0 41.6
    Tbiv (bivalent temperature) °C -10     -10 -10 -10 -10 -10 -10 -10     -10 -10 -10 -10
  TOL COPd (declared COP)   2.78     2.41 2.78 2.58 2.86 2.54 2.53 2.39     2.35 2.62 2.50 2.48
    Pdh (declared heating cap) kW 13.7     18.4 21.7 20.6 23.2 23.2 27.9 28.0     34.4 36.9 39.0 41.6
    Tol (temperature operating limit) °C -10     -10 -10 -10 -10 -10 -10 -10     -10 -10 -10 -10
Capacity range HP 8 10 10 12 13 14 16 16 18 18 20 20 22 24 26 28
Maximum number of connectable indoor units 64 (3) 64 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3)
Indoor index connection Min.   100     150 163 175 200 200 225 225     275 300 325 350
  Max.   260     390 423 455 520 520 585 585     715 780 845 910
Dimensions Unit Height mm 1,685     1,685   1,685   1,685   1,685
    Width mm 930     930   1,240   1,240   1,240
    Depth mm 765     765   765   765   765
Weight Unit kg 213     213   296   296   319
Fan External static pressure Max. Pa 78     78   78   78   78
Compressor Type   Hermetically sealed scroll compressor     Hermetically sealed scroll compressor   Hermetically sealed scroll compressor   Hermetically sealed scroll compressor   Hermetically sealed scroll compressor
Operation range Cooling Min. °CDB -5     -5   -5   -5   -5
    Max. °CDB 46     46   46   46   46
  Heating Min. °CWB -20     -20   -20   -20   -20
    Max. °CWB 16     16   16   16   16
Sound power level Cooling Nom. dBA 78.3 (5)     82.5 (5) 81.3 (5) 78.7 (5) 81.3 (5) 83.7 (5) 81.6 (5) 83.4 (5)     84.0 (5) 84.8 (5) 84.0 (5) 86.2 (5)
Sound pressure level Cooling Nom. dBA 56.3 (6)     60.8 (6) 59.3 (6) 58.1 (6) 59.3 (6) 61.4 (6) 60.2 (6) 63.0 (6)     62.6 (6) 62.6 (6) 62.7 (6) 64.1 (6)
Refrigerant Type   R-32     R-32 R-32 R-32 R-32 R-32 R-32 R-32     R-32 R-32 R-32 R-32
  GWP   675.0     675.0 675.0 675.0 675.0 675.0 675.0 675.0     675.0 675.0 675.0 675.0
  Charge kg 9.00     9.00   10.6   10.6   10.6
Piping connections Liquid Type   Braze connection     Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection     Braze connection Braze connection Braze connection Braze connection
    OD mm 9.52     12.70 12.70 12.70 12.70 12.70 12.70 12.70     12.70 12.70 15.90 15.90
  Gas Type   Braze connection     Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection     Braze connection Braze connection Braze connection Braze connection
    OD mm 19.1     22.2 22.2 22.2 22.2 22.2 22.2 22.2     28.6 28.6 28.6 28.6
  HP/LP gas OD mm 15.90     19.10 19.10 19.10 19.10 19.10 19.10 19.10     22.20 22.20 22.20 22.20
  Total piping length System Actual m 1,000 (7)     1,000 (7) 500 (7) 1,000 (7) 500 (7) 1,000 (7) 500 (7) 1,000 (7)     1,000 (7) 1,000 (7) 1,000 (7) 1,000 (7)
Standard Accessories Installation and operation manual 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
  Connection pipes 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Power supply Name   Y1     Y1 Y1 Y1 Y1 Y1 Y1 Y1     Y1 Y1 Y1 Y1
  Phase   3N~     3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~     3N~ 3N~ 3N~ 3N~
  Frequency Hz 50     50 50 50 50 50 50 50     50 50 50 50
  Voltage V 380-415     380-415 380-415 380-415 380-415 380-415 380-415 380-415     380-415 380-415 380-415 380-415
Notes (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m   (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m
  (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m   (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m
  (3) - The actual number of units depends on the connection ratio (CR) and the restrictions for the system.   (3) - The actual number of units depends on the connection ratio (CR) and the restrictions for the system. (3) - The actual number of units depends on the connection ratio (CR) and the restrictions for the system. (3) - The actual number of units depends on the connection ratio (CR) and the restrictions for the system. (3) - The actual number of units depends on the connection ratio (CR) and the restrictions for the system. (3) - The actual number of units depends on the connection ratio (CR) and the restrictions for the system. (3) - The actual number of units depends on the connection ratio (CR) and the restrictions for the system. (3) - The actual number of units depends on the connection ratio (CR) and the restrictions for the system. (3) - The actual number of units depends on the connection ratio (CR) and the restrictions for the system. (3) - The actual number of units depends on the connection ratio (CR) and the restrictions for the system. (3) - The actual number of units depends on the connection ratio (CR) and the restrictions for the system. (3) - The actual number of units depends on the connection ratio (CR) and the restrictions for the system. (3) - The actual number of units depends on the connection ratio (CR) and the restrictions for the system. (3) - The actual number of units depends on the connection ratio (CR) and the restrictions for the system. (3) - The actual number of units depends on the connection ratio (CR) and the restrictions for the system.
  (4) - Air Flow Rate (AFR) of multi outdoor systems is sum of AFR of the individual systems it consists of   (4) - Sound power level is an absolute value that a sound source generates. (4) - Air Flow Rate (AFR) of multi outdoor systems is sum of AFR of the individual systems it consists of (4) - Air Flow Rate (AFR) of multi outdoor systems is sum of AFR of the individual systems it consists of (4) - Air Flow Rate (AFR) of multi outdoor systems is sum of AFR of the individual systems it consists of (4) - Air Flow Rate (AFR) of multi outdoor systems is sum of AFR of the individual systems it consists of (4) - Air Flow Rate (AFR) of multi outdoor systems is sum of AFR of the individual systems it consists of (4) - Air Flow Rate (AFR) of multi outdoor systems is sum of AFR of the individual systems it consists of (4) - Air Flow Rate (AFR) of multi outdoor systems is sum of AFR of the individual systems it consists of (4) - Sound power level is an absolute value that a sound source generates. (4) - Air Flow Rate (AFR) of multi outdoor systems is sum of AFR of the individual systems it consists of (4) - Air Flow Rate (AFR) of multi outdoor systems is sum of AFR of the individual systems it consists of (4) - Air Flow Rate (AFR) of multi outdoor systems is sum of AFR of the individual systems it consists of (4) - Air Flow Rate (AFR) of multi outdoor systems is sum of AFR of the individual systems it consists of (4) - Air Flow Rate (AFR) of multi outdoor systems is sum of AFR of the individual systems it consists of
  (5) - Sound power level is an absolute value that a sound source generates.   (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound power level is an absolute value that a sound source generates. (5) - Sound power level is an absolute value that a sound source generates. (5) - Sound power level is an absolute value that a sound source generates. (5) - Sound power level is an absolute value that a sound source generates. (5) - Sound power level is an absolute value that a sound source generates. (5) - Sound power level is an absolute value that a sound source generates. (5) - Sound power level is an absolute value that a sound source generates. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound power level is an absolute value that a sound source generates. (5) - Sound power level is an absolute value that a sound source generates. (5) - Sound power level is an absolute value that a sound source generates. (5) - Sound power level is an absolute value that a sound source generates. (5) - Sound power level is an absolute value that a sound source generates.
  (6) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings.   (6) - Refer to refrigerant pipe selection or installation manual (6) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (6) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (6) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (6) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (6) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (6) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (6) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (6) - Refer to refrigerant pipe selection or installation manual (6) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (6) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (6) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (6) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (6) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings.
  (7) - Refer to refrigerant pipe selection or installation manual   (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - Refer to refrigerant pipe selection or installation manual (7) - Refer to refrigerant pipe selection or installation manual (7) - Refer to refrigerant pipe selection or installation manual (7) - Refer to refrigerant pipe selection or installation manual (7) - Refer to refrigerant pipe selection or installation manual (7) - Refer to refrigerant pipe selection or installation manual (7) - Refer to refrigerant pipe selection or installation manual (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - Refer to refrigerant pipe selection or installation manual (7) - Refer to refrigerant pipe selection or installation manual (7) - Refer to refrigerant pipe selection or installation manual (7) - Refer to refrigerant pipe selection or installation manual (7) - Refer to refrigerant pipe selection or installation manual
  (8) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB   (8) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (8) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (8) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (8) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (8) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (8) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (8) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (8) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (8) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (8) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (8) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (8) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (8) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (8) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB
  (9) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current.   (9) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (9) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (9) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (9) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (9) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (9) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (9) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (9) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (9) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (9) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (9) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (9) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (9) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (9) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current.
  (10) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value   (10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (10) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (10) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (10) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (10) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (10) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (10) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (10) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (10) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (10) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (10) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (10) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (10) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value
  (11) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current.     (11) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (11) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (11) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (11) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (11) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (11) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (11) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current.   (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (11) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (11) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (11) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current.
  (12) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).     (12) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (12) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (12) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (12) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (12) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (12) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (12) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).     (12) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (12) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (12) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (12) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
  (13) - Maximum allowable voltage range variation between phases is 2%.     (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%.     (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%. (13) - Maximum allowable voltage range variation between phases is 2%.
  (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.     (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.     (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (14) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
  (15) - Sound values are measured in a semi-anechoic room.     (15) - Sound values are measured in a semi-anechoic room. (15) - Sound values are measured in a semi-anechoic room. (15) - Sound values are measured in a semi-anechoic room. (15) - Sound values are measured in a semi-anechoic room. (15) - Sound values are measured in a semi-anechoic room. (15) - Sound values are measured in a semi-anechoic room. (15) - Sound values are measured in a semi-anechoic room.     (15) - Sound values are measured in a semi-anechoic room. (15) - Sound values are measured in a semi-anechoic room. (15) - Sound values are measured in a semi-anechoic room. (15) - Sound values are measured in a semi-anechoic room.
  (16) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase     (16) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (16) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (16) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (16) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (16) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (16) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (16) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase     (16) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (16) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (16) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (16) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase
  (17) - Ssc: Short-circuit power     (17) - Ssc: Short-circuit power (17) - Ssc: Short-circuit power (17) - Ssc: Short-circuit power (17) - Ssc: Short-circuit power (17) - Ssc: Short-circuit power (17) - Ssc: Short-circuit power (17) - Ssc: Short-circuit power     (17) - Ssc: Short-circuit power (17) - Ssc: Short-circuit power (17) - Ssc: Short-circuit power (17) - Ssc: Short-circuit power
  (18) - For detailed contents of standard accessories, see installation/operation manual     (18) - For detailed contents of standard accessories, see installation/operation manual (18) - For detailed contents of standard accessories, see installation/operation manual (18) - For detailed contents of standard accessories, see installation/operation manual (18) - For detailed contents of standard accessories, see installation/operation manual (18) - For detailed contents of standard accessories, see installation/operation manual (18) - For detailed contents of standard accessories, see installation/operation manual (18) - For detailed contents of standard accessories, see installation/operation manual     (18) - For detailed contents of standard accessories, see installation/operation manual (18) - For detailed contents of standard accessories, see installation/operation manual (18) - For detailed contents of standard accessories, see installation/operation manual (18) - For detailed contents of standard accessories, see installation/operation manual
  (19) - Multi combination (10~28HP) data is corresponding with the standard multi combination     (19) - Multi combination (10~28HP) data is corresponding with the standard multi combination (19) - Multi combination (10~28HP) data is corresponding with the standard multi combination (19) - Multi combination (10~28HP) data is corresponding with the standard multi combination (19) - Multi combination (10~28HP) data is corresponding with the standard multi combination (19) - Multi combination (10~28HP) data is corresponding with the standard multi combination (19) - Multi combination (10~28HP) data is corresponding with the standard multi combination (19) - Multi combination (10~28HP) data is corresponding with the standard multi combination     (19) - Multi combination (10~28HP) data is corresponding with the standard multi combination (19) - Multi combination (10~28HP) data is corresponding with the standard multi combination (19) - Multi combination (10~28HP) data is corresponding with the standard multi combination (19) - Multi combination (10~28HP) data is corresponding with the standard multi combination
System Outdoor unit module 1     REMA5A                   REYA8A
  Outdoor unit module 2     REMA5A                   REYA12A
Cooling capacity Prated,c kW   28 28               56 55.9 (1)
Heating capacity Prated,h kW   28 28               56 55.9 (2)
  Nom. 6°CWB kW   28 28               56 55.9 (2)
COP at nom. capacity 6°CWB KW/KW   3.66 3.45 (2)               3.37 (2) 3.6
Space cooling A Condition (35°C - 27/19) EERd     3.81 3.26               2.57 3.24
    Pdc kW   28 28.0               56.0 55.9
  B Condition (30°C - 27/19) EERd     7.73 5.00               4.42 4.89
    Pdc kW   20.6 20.6               41.3 41.2
  C Condition (25°C - 27/19) EERd     8.99 8.50               7.70 8.7
    Pdc kW   13.5 13.3               26.5 26.5
  D Condition (20°C - 27/19) EERd     11.5 14.8               15.8 16.4
    Pdc kW   14.1 8.19               11.6 16.7
Space cooling recommended combination 2 A Condition (35°C - 27/19) EERd     3.67 3.23               2.52 3.09
    Pdc kW   28 28               56 55.9
  B Condition (30°C - 27/19) EERd     7.32 4.83               4.41 4.75
    Pdc kW   20.6 20.6               41.3 41.2
  C Condition (25°C - 27/19) EERd     8.54 8.06               7.41 8.17
    Pdc kW   13.3 13.3               26.5 26.5
  D Condition (20°C - 27/19) EERd     11.1 14.1               16.6 15.7
    Pdc kW   13.7 7.97               11.9 16
Space cooling recommended combination 3 A Condition (35°C - 27/19) EERd     3.71 3.27               2.50 3.27
    Pdc kW   28.0 28.0               56.0 55.9
  B Condition (30°C - 27/19) EERd     7.71 4.91               4.41 5.04
    Pdc kW   20.6 20.6               41.3 41.2
  C Condition (25°C - 27/19) EERd     8.99 8.59               7.71 9.03
    Pdc kW   13.5 13.3               26.5 26.5
  D Condition (20°C - 27/19) EERd     11.6 15.1               16.4 16.9
    Pdc kW   14.1 8.13               11.8 16.7
Space heating (Average climate) TBivalent COPd (declared COP)     2.69 2.28               2.23 2.55
    Pdh (declared heating cap) kW   16 16.0               31.0 31
    Tbiv (bivalent temperature) °C   -10 -10               -10 -10
  Space heating (Average climate)-=-E condition (-10°C) Space heating (Average climate)-=-E condition (-10°C)-=-COPd (declared COP)     2.69 2.28               2.23 2.55
    Space heating (Average climate)-=-E condition (-10°C)-=-Pdh (declared heating cap)-=-kW kW   16 16.0               31.0 31
  TOL Tol (temperature operating limit) °C   -10 -10               -10 -10
  A Condition (-7°C) COPd (declared COP)     3 2.67               2.60 2.95
    Pdh (declared heating cap) kW   14.2 14.2               27.4 27.4
  B Condition (2°C) COPd (declared COP)     4.37 4.23               3.84 4.09
    Pdh (declared heating cap) kW   8.6 8.62               16.7 16.7
  C Condition (7°C) COPd (declared COP)     4.7 5.70               5.89 5.9
    Pdh (declared heating cap) kW   7.17 5.54               10.7 10.7
  D Condition (12°C) COPd (declared COP)     5.57 7.92               7.70 8.06
    Pdh (declared heating cap) kW   8.74 5.46               7.34 10
Space heating (Average climate) recommended combination 2 TBivalent COPd (declared COP)     2.7 2.32               2.18 2.34
    Pdh (declared heating cap) kW   16 16               31 31
    Tbiv (bivalent temperature) °C   -10 -10               -10 -10
  TOL COPd (declared COP)     2.7 2.32               2.18 2.34
    Pdh (declared heating cap) kW   16 16               31 31
    Tol (temperature operating limit) °C   -10 -10               -10 -10
  A Condition (-7°C) COPd (declared COP)     3.02 2.62               2.54 2.96
    Pdh (declared heating cap) kW   14.2 14.2               27.5 27.4
  B Condition (2°C) COPd (declared COP)     4.43 4.24               3.79 4.21
    Pdh (declared heating cap) kW   8.64 8.61               16.7 16.7
  C Condition (7°C) COPd (declared COP)     4.76 5.79               5.98 6.07
    Pdh (declared heating cap) kW   7.31 5.54               10.7 10.7
  D Condition (12°C) COPd (declared COP)     5.62 7.91               7.81 8.3
    Pdh (declared heating cap) kW   8.87 5.6               7.69 10.5
Space heating (Average climate) recommended combination 3 TBivalent COPd (declared COP)     2.71 2.29               2.24 2.59
    Pdh (declared heating cap) kW   16.0 16.0               31.1 31.0
    Tbiv (bivalent temperature) °C   -10 -10               -10 -10
  TOL COPd (declared COP)     2.71 2.29               2.24 2.59
    Pdh (declared heating cap) kW   16.0 16.0               31.1 31.0
    Tol (temperature operating limit) °C   -10 -10               -10 -10
  A Condition (-7°C) COPd (declared COP)     3.03 2.68               2.60 2.99
    Pdh (declared heating cap) kW   14.2 14.2               27.5 27.5
  B Condition (2°C) COPd (declared COP)     4.48 4.32               3.88 4.22
    Pdh (declared heating cap) kW   8.61 8.62               16.7 16.7
  C Condition (7°C) COPd (declared COP)     4.76 5.80               6.07 6.07
    Pdh (declared heating cap) kW   7.28 5.55               10.7 10.7
  D Condition (12°C) COPd (declared COP)     5.62 8.02               6.15 8.32
    Pdh (declared heating cap) kW   8.85 5.56               5.91 10.3
Indoor index connection Min.     125 125               250 250
  Max.     325 325               650 650
Sound power level Cooling Nom. dBA   81.3 78.8 (5)               87.9 (5) 83.9 (5)
Sound pressure level Cooling Nom. dBA   59.3 58               67 62.1 (6)
Refrigerant Type     R-32 R-32               R-32 R-32
  GWP     675 675.0               675.0 675
Piping connections Liquid Type     Braze connection Braze connection               Braze connection Braze connection
    OD mm   9.52 9.52               12.7 12.7
  Gas Type     Braze connection Braze connection               Braze connection Braze connection
    OD mm   19.1 19.1               28.6 28.6
  HP/LP gas OD mm   15.90 15.90               22.20 22.20
  Total piping length System Actual m   500 1000 (7)               1000 (7) 500 (7)
Power supply Name     Y1 Y1               Y1 Y1
  Phase     3N~ 3N~               3N~ 3N~
  Frequency Hz   50 50               50 50
  Voltage V   380-415 380-415               380-415 380-415
Dimensions Unit Height mm     1685               1685
    Width mm     930               1240
    Depth mm     765               765
Weight Unit kg     213               319
Fan External static pressure Max. Pa     78               78
Compressor Type       Hermetically sealed scroll compressor               Hermetically sealed scroll compressor
Operation range Cooling Min. °CDB     -5               -5
    Max. °CDB     46               46
  Heating Min. °CWB     -20               -20
    Max. °CWB     16               16
Refrigerant Charge tCO2Eq     6.08               7.16
  Charge kg     9               10.6