Specifications Table for RXYQ-UD

RXYQ8U5Y1BD RXYQ10U5Y1BD RXYQ12U5Y1BD RXYQ14U5Y1BD RXYQ16U5Y1BD RXYQ18U5Y1BD RXYQ20U5Y1BD RXYQ22U5Y1BD RXYQ24U5Y1BD RXYQ26U5Y1BD RXYQ28U5Y1BD RXYQ30U5Y1BD RXYQ32U5Y1BD RXYQ34U5Y1BD RXYQ36U5Y1BD RXYQ38U5Y1BD RXYQ40U5Y1BD RXYQ42U5Y1BD RXYQ44U5Y1BD RXYQ46U5Y1BD RXYQ48U5Y1BD RXYQ50U5Y1BD RXYQ52U5Y1BD RXYQ54U5Y1BD
Sound pressure level Cooling Nom. dBA               62.5 (5) 64.0 (5) 63.5 (5) 65.1 (5) 64.5 (5) 66.0 (5) 65.5 (5) 67.1 (5) 66.2 (5) 65.2 (5) 66.5 (5) 67.2 (5) 67.0 (5) 67.8 (5) 67.5 (5) 67.1 (5) 66.8 (5)
Standard Accessories Installation manual 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
  Operation manual 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
  Connection pipes 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
SEER recommended combination 2 6.9 6.8 5.9 6.3 5.9 6 5.9 6.7 6.6 6.5 6.3 6.3 6.3 6.3 6.3 6.8 6.6 6.6 6.3 6.4 6.3 6.3 6.4 6.4
SEER recommended combination 3 7.5 6.8 6.2 6.2 5.8 6.0 5.9 6.9 6.7 6.6 6.4 6.5 6.2 6.3 6.3 6.9 6.7 6.5 6.3 6.3 6.2 6.3 6.4 6.4
Capacity range HP 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54
ηs,c %               274.5 269.9 264.2 257.8 256.8 251.7 253.3 250.8 272.4 263.5 261.2 255.9 254.9 251.7 252.8 253.7 254.1
Maximum number of connectable indoor units 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3) 64 (3)
Space cooling B Condition (30°C - 27/19) Pdc kW               45.3 49.7 54.2 57.8 61.8 66.3 70.3 71.5 75.5 82.5 86.9 91.0 95.8 99.5 103.4 107.4 111.4
    EERd                 4.8 4.6 4.6 4.4 4.3 4.3 4.2 4.1 4.5 4.5 4.4 4.4 4.4 4.3 4.2 4.2 4.1
  D Condition (20°C - 27/19) Pdc kW               18.8 15.8 16.2 16.5 21.0 19.0 20.1 20.4 21.6 23.6 24.8 26.0 27.4 28.4 29.6 30.7 34.4
    EERd                 16.0 15.2 14.2 14.3 16.8 14.3 16.8 16.7 17.9 16.0 15.4 14.4 14.3 14.3 15.9 17.6 19.1
  A Condition (35°C - 27/19) EERd                 2.6 2.5 2.6 2.3 2.1 2.3 2.1 2.1 2.4 2.2 2.3 2.3 2.4 2.3 2.1 2.0 1.9
    Pdc kW               61.5 67.4 73.5 78.5 83.9 90.0 95.4 97.0 102.4 111.9 118.0 123.5 130.0 135.0 140.4 145.8 151.2
  C Condition (25°C - 27/19) EERd                 8.5 8.6 8.2 8.1 8.2 8.1 8.1 7.9 8.5 8.3 8.2 8.1 8.1 8.1 8.1 8.1 8.1
    Pdc kW               29.1 31.9 34.8 37.2 39.7 42.6 45.2 45.9 48.5 53.0 55.9 58.5 61.6 64.0 66.5 69.1 71.6
SCOP 4.3 4.3 4.1 4.0 4.0 4.2 4.0 4.4 4.3 4.2 4.2 4.3 4.2 4.2 4.1 4.3 4.3 4.2 4.2 4.1 4.1 4.2 4.3 4.3
Refrigerant GWP                 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5
  Type                 R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A
Space cooling recommended combination 3 B Condition (30°C - 27/19) Pdc kW               45.3 49.7 54.2 57.8 61.8 66.3 70.3 71.5 75.5 82.5 87.0 91.0 95.8 99.5 103.5 107.4 111.4
    EERd                 4.8 4.5 4.5 4.3 4.3 4.1 4.1 4.0 4.5 4.4 4.3 4.3 4.2 4.1 4.1 4.1 4.1
  D Condition (20°C - 27/19) Pdc kW               18.8 15.7 16.0 16.6 21.0 19.0 20.1 20.4 21.6 23.6 24.8 26.0 27.4 28.4 29.6 30.7 34.7
    EERd                 15.8 15.2 14.0 14.1 16.6 13.8 16.6 16.5 17.9 16.1 15.2 14.2 13.9 13.8 15.6 17.5 19.1
  A Condition (35°C - 27/19) EERd                 2.5 2.5 2.5 2.3 2.1 2.2 2.1 2.1 2.4 2.2 2.3 2.3 2.3 2.2 2.1 2.0 1.9
    Pdc kW               61.5 67.4 73.5 78.5 83.9 90.0 95.4 97.0 102.4 111.9 118.0 123.5 130.0 135.0 140.4 145.8 151.2
  C Condition (25°C - 27/19) EERd                 8.5 8.4 8.1 8.0 8.2 7.8 8.0 7.8 8.5 8.4 8.0 7.9 7.9 7.8 7.9 8.0 8.2
    Pdc kW               29.1 31.9 34.8 37.2 39.7 42.6 45.2 45.9 48.5 53.0 55.9 58.5 61.6 63.9 66.5 69.1 71.6
SCOP recommended combination 3 4.2 4.1 4.1 4.0 4.0 4.1 3.9 4.3 4.2 4.2 4.2 4.3 4.1 4.2 4.1 4.2 4.3 4.2 4.2 4.1 4.1 4.2 4.2 4.2
Space cooling recommended combination 2 C Condition (25°C - 27/19) Pdc kW               29.1 31.9 34.8 37.2 39.7 42.6 45.2 45.9 48.5 53.0 55.9 58.5 61.6 63.9 66.5 69.0 71.6
    EERd                 8.2 8.4 7.9 7.8 7.9 8.0 8.1 7.9 8.4 8.1 8.2 7.9 8.1 8.0 8.0 8.1 8.1
  A Condition (35°C - 27/19) EERd                 2.6 2.4 2.6 2.3 2.1 2.2 2.1 2.1 2.3 2.2 2.3 2.3 2.3 2.2 2.1 2.0 1.9
    Pdc kW               61.5 67.4 73.5 78.5 83.9 90.0 95.4 97.0 102.4 111.9 118.0 123.5 130.0 135.0 140.4 145.8 151.2
  D Condition (20°C - 27/19) EERd                 15.6 14.7 13.6 13.8 16.1 14.0 16.5 16.5 17.8 15.9 15.3 14.0 14.0 14.0 15.6 17.4 18.9
    Pdc kW               18.4 15.4 15.7 16.5 20.5 18.9 20.1 20.4 21.6 23.6 24.8 26.0 27.4 28.4 29.6 30.7 34.1
  B Condition (30°C - 27/19) EERd                 4.6 4.5 4.4 4.3 4.2 4.2 4.2 4.1 4.5 4.4 4.4 4.3 4.3 4.2 4.2 4.1 4.1
    Pdc kW               45.3 49.7 54.1 57.8 61.8 66.3 70.3 71.5 75.4 82.4 86.9 91.0 95.8 99.5 103.5 107.4 111.4
System Outdoor unit module 2                 RXYQ12U RXYQ16U RXYQ14U RXYQ16U RXYQ18U RXYQ16U RXYQ18U RXYQ20U RXYQ10U RXYQ12U RXYQ16U RXYQ16U RXYQ16U RXYQ16U RXYQ16U RXYQ18U RXYQ18U
  Outdoor unit module 3                                 RXYQ20U RXYQ18U RXYQ16U RXYQ16U RXYQ16U RXYQ16U RXYQ18U RXYQ18U RXYQ18U
  Outdoor unit module 1                 RXYQ10U RXYQ8U RXYQ12U RXYQ12U RXYQ12U RXYQ16U RXYQ16U RXYQ16U RXYQ8U RXYQ10U RXYQ10U RXYQ12U RXYQ14U RXYQ16U RXYQ16U RXYQ16U RXYQ18U
Recommended combination 3 4 x FXMQ50P7VEB 4 x FXMQ63P7VEB 6 x FXMQ50P7VEB 1 x FXMQ50P7VEB + 5 x FXMQ63P7VEB 4 x FXMQ63P7VEB + 2 x FXMQ80P7VEB 3 x FXMQ50P7VEB + 5 x FXMQ63P7VEB 2 x FXMQ50P7VEB + 6 x FXMQ63P7VEB 6 x FXMQ50P7VEB + 4 x FXMQ63P7VEB 4 x FXMQ50P7VEB + 4 x FXMQ63P7VEB + 2 x FXMQ80P7VEB 7 x FXMQ50P7VEB + 5 x FXMQ63P7VEB 6 x FXMQ50P7VEB + 4 x FXMQ63P7VEB + 2 x FXMQ80P7VEB 9 x FXMQ50P7VEB + 5 x FXMQ63P7VEB 8 x FXMQ63P7VEB + 4 x FXMQ80P7VEB 3 x FXMQ50P7VEB + 9 x FXMQ63P7VEB + 2 x FXMQ80P7VEB 2 x FXMQ50P7VEB + 10 x FXMQ63P7VEB + 2 x FXMQ80P7VEB 6 x FXMQ50P7VEB + 10 x FXMQ63P7VEB 9 x FXMQ50P7VEB + 9 x FXMQ63P7VEB 12 x FXMQ63P7VEB + 4 x FXMQ80P7VEB 6 x FXMQ50P7VEB + 8 x FXMQ63P7VEB + 4 x FXMQ80P7VEB 1 x FXMQ50P7VEB + 13 x FXMQ63P7VEB + 4 x FXMQ80P7VEB 12 x FXMQ63P7VEB + 6 x FXMQ80P7VEB 3 x FXMQ50P7VEB + 13 x FXMQ63P7VEB + 4 x FXMQ80P7VEB 6 x FXMQ50P7VEB + 14 x FXMQ63P7VEB + 2 x FXMQ80P7VEB 9 x FXMQ50P7VEB + 15 x FXMQ63P7VEB
Recommended combination 2 4 x FXSQ50A2VEB 4 x FXSQ63A2VEB 6 x FXSQ50A2VEB 1 x FXSQ50A2VEB + 5 x FXSQ63A2VEB 4 x FXSQ63A2VEB + 2 x FXSQ80A2VEB 3 x FXSQ50A2VEB + 5 x FXSQ63A2VEB 2 x FXSQ50A2VEB + 6 x FXSQ63A2VEB 6 x FXSQ50A2VEB + 4 x FXSQ63A2VEB 4 x FXSQ50A2VEB + 4 x FXSQ63A2VEB + 2 x FXSQ80A2VEB 7 x FXSQ50A2VEB + 5 x FXSQ63A2VEB 6 x FXSQ50A2VEB + 4 x FXSQ63A2VEB + 2 x FXSQ80A2VEB 9 x FXSQ50A2VEB + 5 x FXSQ63A2VEB 8 x FXSQ63A2VEB + 4 x FXSQ80A2VEB 3 x FXSQ50A2VEB + 9 x FXSQ63A2VEB + 2 x FXSQ80A2VEB 2 x FXSQ50A2VEB + 10 x FXSQ63A2VEB + 2 x FXSQ80A2VEB 6 x FXSQ50A2VEB + 10 x FXSQ63A2VEB 9 x FXSQ50A2VEB + 9 x FXSQ63A2VEB 12 x FXSQ63A2VEB + 4 x FXSQ80A2VEB 6 x FXSQ50A2VEB + 8 x FXSQ63A2VEB + 4 x FXSQ80A2VEB 1 x FXSQ50A2VEB + 13 x FXSQ63A2VEB + 4 x FXSQ80A2VEB 12 x FXSQ63A2VEB + 6 x FXSQ80A2VEB 3 x FXSQ50A2VEB + 13 x FXSQ63A2VEB + 4 x FXSQ80A2VEB 6 x FXSQ50A2VEB + 14 x FXSQ63A2VEB + 2 x FXSQ80A2VEB 9 x FXSQ50A2VEB + 15 x FXSQ63A2VEB
SCOP recommended combination 2 4.2 4.3 4.1 4 4.1 4.2 4 4.4 4.3 4.2 4.2 4.3 4.2 4.3 4.2 4.3 4.4 4.3 4.2 4.2 4.2 4.2 4.3 4.3
Power input - 50Hz Heating Nom. 6°CWB kW               17.23 (2) 17.94 (2) 20.33 (2) 22.19 (2) 23.87 (2) 25.08 (2) 26.76 (2) 30.02 (2) 30.45 (2) 31.45 (2) 32.66 (2) 34.73 (2) 35.77 (2) 37.62 (2) 39.30 (2) 40.98 (2) 42.66 (2)
Indoor index connection Min.                 275.0 300.0 325.0 350.0 375.0 400.0 425.0 450.0 475.0 500.0 525.0 550.0 575.0 600.0 625.0 650.0 675.0
  Max.                 715.0 780.0 845.0 910.0 975.0 1,040.0 1,105.0 1,170.0 1,235.0 1,300.0 1,365.0 1,430.0 1,495.0 1,560.0 1,625.0 1,690.0 1,755.0
Cooling capacity Prated,c kW               61.5 (1) 67.4 (1) 73.5 (1) 78.5 (1) 83.9 (1) 90.0 (1) 95.4 (1) 97.0 (1) 102.4 (1) 111.9 (1) 118.0 (1) 123.5 (1) 130.0 (1) 135.0 (1) 140.4 (1) 145.8 (1) 151.2 (1)
COP at nom. capacity 6°CWB kW/kW               3.57 (2) 3.76 (2) 3.61 (2) 3.54 (2) 3.51 (2) 3.59 (2) 3.56 (2) 3.36 (2) 3.49 (2) 3.56 (2) 3.61 (2) 3.56 (2) 3.63 (2) 3.59 (2) 3.57 (2) 3.56 (2) 3.54 (2)
Recommended combination 4 x FXFQ50AVEB 4 x FXFQ63AVEB 6 x FXFQ50AVEB 1 x FXFQ50AVEB + 5 x FXFQ63AVEB 4 x FXFQ63AVEB + 2 x FXFQ80AVEB 3 x FXFQ50AVEB + 5 x FXFQ63AVEB 2 x FXFQ50AVEB + 6 x FXFQ63AVEB 6 x FXFQ50AVEB + 4 x FXFQ63AVEB 4 x FXFQ50AVEB + 4 x FXFQ63AVEB + 2 x FXFQ80AVEB 7 x FXFQ50AVEB + 5 x FXFQ63AVEB 6 x FXFQ50AVEB + 4 x FXFQ63AVEB + 2 x FXFQ80AVEB 9 x FXFQ50AVEB + 5 x FXFQ63AVEB 8 x FXFQ63AVEB + 4 x FXFQ80AVEB 3 x FXFQ50AVEB + 9 x FXFQ63AVEB + 2 x FXFQ80AVEB 2 x FXFQ50AVEB + 10 x FXFQ63AVEB + 2 x FXFQ80AVEB 6 x FXFQ50AVEB + 10 x FXFQ63AVEB 9 x FXFQ50AVEB + 9 x FXFQ63AVEB 12 x FXFQ63AVEB + 4 x FXFQ80AVEB 6 x FXFQ50AVEB + 8 x FXFQ63AVEB + 4 x FXFQ80AVEB 1 x FXFQ50AVEB + 13 x FXFQ63AVEB + 4 x FXFQ80AVEB 12 x FXFQ63AVEB + 6 x FXFQ80AVEB 3 x FXFQ50AVEB + 13 x FXFQ63AVEB + 4 x FXFQ80AVEB 6 x FXFQ50AVEB + 14 x FXFQ63AVEB + 2 x FXFQ80AVEB 9 x FXFQ50AVEB + 15 x FXFQ63AVEB
Space heating (Average climate) TOL COPd (declared COP)                 2.3 2.5 2.3 2.2 2.1 2.4 2.2 2.1 2.2 2.2 2.4 2.3 2.4 2.4 2.3 2.2 2.1
    Pdh (declared heating cap) kW               34.4 36.9 39.0 41.6 46.3 46.4 51.1 54.2 60.7 62.3 62.4 64.8 67.0 69.6 74.3 79.0 83.7
    Tol (temperature operating limit) °C               -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10
  D Condition (12°C) Pdh (declared heating cap) kW               6.0 5.7 6.0 6.4 7.1 7.1 7.9 8.3 13.1 13.1 9.9 10.0 10.3 10.7 12.0 14.2 14.2
    COPd (declared COP)                 8.2 8.9 8.8 9.0 9.0 9.0 8.8 8.6 8.7 8.7 8.6 8.6 8.7 8.8 8.9 9.0 9.0
  B Condition (2°C) COPd (declared COP)                 4.0 3.7 3.8 3.8 3.9 3.6 3.7 3.7 3.9 4.0 3.7 3.7 3.6 3.6 3.7 3.8 3.9
    Pdh (declared heating cap) kW               18.5 19.9 21.0 22.4 24.9 25.0 27.5 29.2 32.7 33.5 33.6 34.9 36.1 37.5 40.0 42.5 45.1
  C Condition (7°C) COPd (declared COP)                 6.3 6.3 6.1 6.2 6.5 6.3 6.5 6.4 6.5 6.5 6.3 6.3 6.2 6.3 6.5 6.6 6.8
    Pdh (declared heating cap) kW               11.9 13.0 13.5 14.4 16.0 16.1 17.7 18.8 21.3 21.6 21.6 22.4 23.2 24.1 25.7 27.4 29.0
  A Condition (-7°C) COPd (declared COP)                 2.6 2.8 2.6 2.6 2.6 2.7 2.6 2.5 2.5 2.6 2.7 2.7 2.7 2.7 2.7 2.6 2.6
    Pdh (declared heating cap) kW               30.4 32.6 34.5 36.8 41.0 41.0 45.2 47.9 53.7 55.1 55.2 57.3 59.3 61.6 65.7 69.9 74.0
  TBivalent Pdh (declared heating cap) kW               34.4 36.9 39.0 41.6 46.3 46.4 51.1 54.2 60.7 62.3 62.4 64.8 67.0 69.6 74.3 79.0 83.7
    Tbiv (bivalent temperature) °C               -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10
    COPd (declared COP)                 2.3 2.5 2.3 2.2 2.1 2.4 2.2 2.1 2.2 2.2 2.4 2.3 2.4 2.4 2.3 2.2 2.1
Piping connections Liquid OD mm               15.9 15.9 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1
    Type                 Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection
  Total piping length System Actual m               1,000 (6) 1,000 (6) 1,000 (6) 1,000 (6) 1,000 (6) 1,000 (6) 1,000 (6) 1,000 (6) 1,000 (6) 1,000 (6) 1,000 (6) 1,000 (6) 1,000 (6) 1,000 (6) 1,000 (6) 1,000 (6) 1,000 (6)
  Gas OD mm               28.6 34.9 34.9 34.9 34.9 34.9 34.9 41.3 41.3 41.3 41.3 41.3 41.3 41.3 41.3 41.3 41.3
    Type                 Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection
SEER 7.6 6.8 6.3 6.3 6.0 6.0 5.9 6.9 6.8 6.7 6.5 6.5 6.4 6.4 6.3 6.9 6.7 6.6 6.5 6.4 6.4 6.4 6.4 6.4
Space heating (Average climate) recommended combination 2 B Condition (2°C) Pdh (declared heating cap) kW               18.5 19.9 21.0 22.4 24.9 25.0 27.5 29.2 32.7 33.5 33.6 34.9 36.1 37.5 40.0 42.6 45.1
    COPd (declared COP)                 4.1 3.7 3.8 3.8 3.9 3.6 3.8 3.7 3.9 4.0 3.7 3.7 3.6 3.6 3.7 3.8 3.9
  C Condition (7°C) Pdh (declared heating cap) kW               11.9 13.1 13.1 14.4 16.0 16.1 17.7 18.8 21.3 21.6 21.6 22.4 22.8 24.1 25.7 27.4 29.0
    COPd (declared COP)                 6.3 6.3 6.1 6.3 6.6 6.3 6.6 6.5 6.5 6.5 6.4 6.3 6.3 6.3 6.5 6.7 6.8
  A Condition (-7°C) COPd (declared COP)                 2.6 2.7 2.6 2.6 2.6 2.7 2.6 2.5 2.5 2.6 2.7 2.7 2.7 2.7 2.7 2.6 2.6
    Pdh (declared heating cap) kW               30.4 32.6 34.5 36.8 41.0 41.0 45.2 47.9 53.7 55.1 55.2 57.3 59.3 61.6 65.7 69.9 74.0
  TOL Pdh (declared heating cap) kW               34.4 36.9 39.0 41.6 46.3 46.4 51.1 54.2 60.7 62.3 62.4 64.8 67.0 69.6 74.3 79.0 83.7
    COPd (declared COP)                 2.2 2.4 2.2 2.2 2.1 2.4 2.2 2.2 2.3 2.2 2.4 2.3 2.4 2.4 2.3 2.2 2.1
    Tol (temperature operating limit) °C               -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10
  D Condition (12°C) Pdh (declared heating cap) kW               6.0 5.7 6.0 6.4 7.2 7.1 7.9 8.3 13.2 13.2 10.0 10.0 10.3 10.7 12.2 14.4 14.4
    COPd (declared COP)                 8.4 9.0 8.9 9.1 9.1 9.1 8.9 8.8 8.8 8.8 8.7 8.7 8.8 8.9 9.0 9.1 9.1
  TBivalent Pdh (declared heating cap) kW               34.4 36.9 39.0 41.6 46.3 46.4 51.1 54.2 60.7 62.3 62.4 64.8 67.0 69.6 74.3 79.0 83.7
    COPd (declared COP)                 2.2 2.4 2.2 2.2 2.1 2.4 2.2 2.2 2.3 2.2 2.4 2.3 2.4 2.4 2.3 2.2 2.1
    Tbiv (bivalent temperature) °C               -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10
Space heating (Average climate) recommended combination 3 B Condition (2°C) Pdh (declared heating cap) kW               18.5 19.9 21.0 22.4 24.9 25.0 27.5 29.2 32.7 33.5 33.6 34.9 36.1 37.5 40.0 42.5 45.1
    COPd (declared COP)                 4.0 3.7 3.8 3.8 3.9 3.6 3.7 3.6 3.8 3.9 3.7 3.7 3.6 3.6 3.6 3.7 3.8
  C Condition (7°C) COPd (declared COP)                 6.2 6.3 6.1 6.2 6.3 6.3 6.4 6.3 6.3 6.4 6.3 6.2 6.2 6.3 6.4 6.4 6.5
    Pdh (declared heating cap) kW               11.9 12.9 13.5 14.4 16.0 16.1 17.7 18.8 21.2 21.6 21.6 22.4 23.2 24.1 25.7 27.3 29.0
  A Condition (-7°C) Pdh (declared heating cap) kW               30.4 32.6 34.5 36.8 41.0 41.0 45.2 47.9 53.7 55.1 55.2 57.3 59.3 61.6 65.7 69.9 74.0
    COPd (declared COP)                 2.6 2.7 2.6 2.6 2.5 2.7 2.6 2.4 2.5 2.6 2.7 2.6 2.7 2.7 2.6 2.6 2.5
  TOL Pdh (declared heating cap) kW               34.4 36.9 39.0 41.6 46.3 46.4 51.1 54.2 60.7 62.3 62.4 64.8 67.0 69.6 74.3 79.0 83.7
    Tol (temperature operating limit) °C               -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10
    COPd (declared COP)                 2.3 2.4 2.2 2.2 2.1 2.4 2.2 2.1 2.2 2.2 2.4 2.3 2.4 2.4 2.2 2.2 2.1
  D Condition (12°C) COPd (declared COP)                 8.2 8.9 8.8 9.0 8.6 9.0 8.9 8.3 8.5 8.4 8.6 8.6 8.7 8.8 8.7 8.7 8.7
    Pdh (declared heating cap) kW               6.0 5.7 6.0 6.4 7.1 7.1 7.9 8.3 12.9 12.8 9.9 10.0 10.3 10.7 11.8 13.7 13.7
  TBivalent Pdh (declared heating cap) kW               34.4 36.9 39.0 41.6 46.3 46.4 51.1 54.2 60.7 62.3 62.4 64.8 67.0 69.6 74.3 79.0 83.7
    COPd (declared COP)                 2.3 2.4 2.2 2.2 2.1 2.4 2.2 2.1 2.2 2.2 2.4 2.3 2.4 2.4 2.2 2.2 2.1
    Tbiv (bivalent temperature) °C               -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10
Sound power level Cooling Nom. dBA               84.8 (4) 86.3 (4) 85.3 (4) 87.6 (4) 86.6 (4) 88.6 (4) 87.8 (4) 89.9 (4) 88.8 (4) 87.3 (4) 89.1 (4) 89.8 (4) 89.3 (4) 90.4 (4) 89.8 (4) 89.3 (4) 88.6 (4)
ηs,h %               171.2 167.0 164.6 166.0 169.8 163.1 166.2 162.4 167.5 170.0 165.5 164.5 162.0 162.8 165.2 167.2 169.4
Heating capacity Prated,h kW               61.5 (2) 67.4 (2) 73.5 (2) 78.5 (2) 83.9 (2) 90.0 (2) 95.4 (2) 101.0 (2) 106.4 (2) 111.9 (2) 118.0 (2) 123.5 (2) 130.0 (2) 135.0 (2) 140.4 (2) 145.8 (2) 151.2 (2)
  Nom. 6°CWB kW               61.5 (2) 67.4 (2) 73.5 (2) 78.5 (2) 83.9 (2) 90.0 (2) 95.4 (2) 101.0 (2) 106.4 (2) 111.9 (2) 118.0 (2) 123.5 (2) 130.0 (2) 135.0 (2) 140.4 (2) 145.8 (2) 151.2 (2)
Power supply Phase                 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~
  Name                 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1 Y1
  Frequency Hz               50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
  Voltage V               380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415 380-415
Notes (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m
  (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m
  (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (3) - Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%)
  (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates.
  (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings.
  (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual
  (7) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (7) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (7) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (7) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (7) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (7) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (7) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (7) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (7) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (7) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (7) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (7) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (7) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (7) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (7) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (7) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (7) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (7) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (7) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (7) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (7) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (7) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (7) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. (7) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current.
  (8) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (8) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (8) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (8) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (8) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (8) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (8) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (8) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (8) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (8) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (8) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (8) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (8) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (8) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (8) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (8) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (8) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (8) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (8) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (8) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (8) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (8) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (8) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value (8) - In accordance with EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply wih Ssc ≥ minimum Ssc value
  (9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (9) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (9) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (9) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (9) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (9) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (9) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (9) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (9) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (9) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (9) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (9) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (9) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (9) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (9) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (9) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (9) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (9) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (9) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current.
  (10) - FLA means the nominal running current of the fan (10) - FLA means the nominal running current of the fan (10) - FLA means the nominal running current of the fan (10) - FLA means the nominal running current of the fan (10) - FLA means the nominal running current of the fan (10) - FLA means the nominal running current of the fan (10) - FLA means the nominal running current of the fan (10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
                (11) - FLA means the nominal running current of the fan (11) - FLA means the nominal running current of the fan (11) - FLA means the nominal running current of the fan (11) - FLA means the nominal running current of the fan (11) - FLA means the nominal running current of the fan (11) - FLA means the nominal running current of the fan (11) - FLA means the nominal running current of the fan (11) - FLA means the nominal running current of the fan (11) - FLA means the nominal running current of the fan (11) - FLA means the nominal running current of the fan (11) - FLA means the nominal running current of the fan (11) - FLA means the nominal running current of the fan (11) - FLA means the nominal running current of the fan (11) - FLA means the nominal running current of the fan (11) - FLA means the nominal running current of the fan (11) - FLA means the nominal running current of the fan (11) - FLA means the nominal running current of the fan
                (12) - Maximum allowable voltage range variation between phases is 2%. (12) - Maximum allowable voltage range variation between phases is 2%. (12) - Maximum allowable voltage range variation between phases is 2%. (12) - Maximum allowable voltage range variation between phases is 2%. (12) - Maximum allowable voltage range variation between phases is 2%. (12) - Maximum allowable voltage range variation between phases is 2%. (12) - Maximum allowable voltage range variation between phases is 2%. (12) - Maximum allowable voltage range variation between phases is 2%. (12) - Maximum allowable voltage range variation between phases is 2%. (12) - Maximum allowable voltage range variation between phases is 2%. (12) - Maximum allowable voltage range variation between phases is 2%. (12) - Maximum allowable voltage range variation between phases is 2%. (12) - Maximum allowable voltage range variation between phases is 2%. (12) - Maximum allowable voltage range variation between phases is 2%. (12) - Maximum allowable voltage range variation between phases is 2%. (12) - Maximum allowable voltage range variation between phases is 2%. (12) - Maximum allowable voltage range variation between phases is 2%.
                (13) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (13) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (13) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (13) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (13) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (13) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (13) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (13) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (13) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (13) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (13) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (13) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (13) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (13) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (13) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (13) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (13) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
                (14) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) (14) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) (14) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) (14) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) (14) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) (14) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) (14) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) (14) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) (14) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) (14) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) (14) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) (14) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) (14) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) (14) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) (14) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) (14) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature ) (14) - The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation funcitonality ( variable refrigerant temperature )
                (15) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (15) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (15) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (15) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (15) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (15) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (15) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (15) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (15) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (15) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (15) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (15) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (15) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (15) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (15) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (15) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (15) - The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality
                (16) - Sound values are measured in a semi-anechoic room. (16) - Sound values are measured in a semi-anechoic room. (16) - Sound values are measured in a semi-anechoic room. (16) - Sound values are measured in a semi-anechoic room. (16) - Sound values are measured in a semi-anechoic room. (16) - Sound values are measured in a semi-anechoic room. (16) - Sound values are measured in a semi-anechoic room. (16) - Sound values are measured in a semi-anechoic room. (16) - Sound values are measured in a semi-anechoic room. (16) - Sound values are measured in a semi-anechoic room. (16) - Sound values are measured in a semi-anechoic room. (16) - Sound values are measured in a semi-anechoic room. (16) - Sound values are measured in a semi-anechoic room. (16) - Sound values are measured in a semi-anechoic room. (16) - Sound values are measured in a semi-anechoic room. (16) - Sound values are measured in a semi-anechoic room. (16) - Sound values are measured in a semi-anechoic room.
                (17) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (17) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (17) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (17) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (17) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (17) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (17) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (17) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (17) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (17) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (17) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (17) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (17) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (17) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (17) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (17) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA (17) - Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA
                (18) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (18) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (18) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (18) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (18) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (18) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (18) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (18) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (18) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (18) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (18) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (18) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (18) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (18) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (18) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (18) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase (18) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase
                (19) - Ssc: Short-circuit power (19) - Ssc: Short-circuit power (19) - Ssc: Short-circuit power (19) - Ssc: Short-circuit power (19) - Ssc: Short-circuit power (19) - Ssc: Short-circuit power (19) - Ssc: Short-circuit power (19) - Ssc: Short-circuit power (19) - Ssc: Short-circuit power (19) - Ssc: Short-circuit power (19) - Ssc: Short-circuit power (19) - Ssc: Short-circuit power (19) - Ssc: Short-circuit power (19) - Ssc: Short-circuit power (19) - Ssc: Short-circuit power (19) - Ssc: Short-circuit power (19) - Ssc: Short-circuit power
                (20) - For detailed contents of standard accessories, see installation/operation manual (20) - For detailed contents of standard accessories, see installation/operation manual (20) - For detailed contents of standard accessories, see installation/operation manual (20) - For detailed contents of standard accessories, see installation/operation manual (20) - For detailed contents of standard accessories, see installation/operation manual (20) - For detailed contents of standard accessories, see installation/operation manual (20) - For detailed contents of standard accessories, see installation/operation manual (20) - For detailed contents of standard accessories, see installation/operation manual (20) - For detailed contents of standard accessories, see installation/operation manual (20) - For detailed contents of standard accessories, see installation/operation manual (20) - For detailed contents of standard accessories, see installation/operation manual (20) - For detailed contents of standard accessories, see installation/operation manual (20) - For detailed contents of standard accessories, see installation/operation manual (20) - For detailed contents of standard accessories, see installation/operation manual (20) - For detailed contents of standard accessories, see installation/operation manual (20) - For detailed contents of standard accessories, see installation/operation manual (20) - For detailed contents of standard accessories, see installation/operation manual
                (21) - Multi combination (22~54HP) data is corresponding with the standard multi combination (21) - Multi combination (22~54HP) data is corresponding with the standard multi combination (21) - Multi combination (22~54HP) data is corresponding with the standard multi combination (21) - Multi combination (22~54HP) data is corresponding with the standard multi combination (21) - Multi combination (22~54HP) data is corresponding with the standard multi combination (21) - Multi combination (22~54HP) data is corresponding with the standard multi combination (21) - Multi combination (22~54HP) data is corresponding with the standard multi combination (21) - Multi combination (22~54HP) data is corresponding with the standard multi combination (21) - Multi combination (22~54HP) data is corresponding with the standard multi combination (21) - Multi combination (22~54HP) data is corresponding with the standard multi combination (21) - Multi combination (22~54HP) data is corresponding with the standard multi combination (21) - Multi combination (22~54HP) data is corresponding with the standard multi combination (21) - Multi combination (22~54HP) data is corresponding with the standard multi combination (21) - Multi combination (22~54HP) data is corresponding with the standard multi combination (21) - Multi combination (22~54HP) data is corresponding with the standard multi combination (21) - Multi combination (22~54HP) data is corresponding with the standard multi combination (21) - Multi combination (22~54HP) data is corresponding with the standard multi combination
Cooling capacity Prated,c kW 22.4 (1) 28 33.5 (1) 40 45 50.4 (1) 52
Heating capacity Prated,h kW 22.4 (2) 28 33.5 (2) 40 45 50.4 (2) 56
  Nom. 6°CWB kW 22.4 (2) 28 33.5 (2) 40 45 50.4 (2) 56
COP at nom. capacity 6°CWB KW/KW 4.15 (2) 3.69 (2) 3.47 (2) 3.74 (2) 3.59 (2) 3.54 (2) 3.2
Space cooling A Condition (35°C - 27/19) EERd   3.0 2.3 2.4 2.6 2.1 1.9 1.9
    Pdc kW 22.4 28.0 33.5 40.0 45.0 50.4 52.0
  B Condition (30°C - 27/19) EERd   5.2 4.7 4.3 4.1 3.9 3.8 3.7
    Pdc kW 16.5 20.6 24.7 29.5 33.2 37.1 38.3
  C Condition (25°C - 27/19) EERd   9.5 8.3 7.7 7.8 7.7 7.5 7.3
    Pdc kW 10.6 13.3 15.9 18.9 21.3 23.9 24.6
  D Condition (20°C - 27/19) EERd   18.8 17.0 13.9 14.3 14.2 18.3 18.3
    Pdc kW 8.0 9.3 9.4 8.4 9.5 11.5 11.5
Space cooling recommended combination 2 A Condition (35°C - 27/19) EERd   2.6 2.4 2.4 2.6 2.1 1.9 1.9
    Pdc kW 22.4 28 33.5 40 45 50.4 52
  B Condition (30°C - 27/19) EERd   4.9 4.7 4 4.1 3.8 3.7 3.6
    Pdc kW 16.5 20.6 24.7 29.5 33.2 37.1 38.3
  C Condition (25°C - 27/19) EERd   8.8 8.5 7.1 7.9 7.6 7.5 7.3
    Pdc kW 10.6 13.3 15.9 18.9 21.3 23.9 24.6
  D Condition (20°C - 27/19) EERd   15.1 17.2 13.1 14 14 18.1 18.9
    Pdc kW 8.8 9.3 9.1 8.4 9.5 11.4 10.9
Space cooling recommended combination 3 A Condition (35°C - 27/19) EERd   3.0 2.3 2.4 2.6 2.1 1.9 1.9
    Pdc kW 22.4 28.0 33.5 40.0 45.0 50.4 52.0
  B Condition (30°C - 27/19) EERd   5.1 4.7 4.2 4.0 3.7 3.7 3.6
    Pdc kW 16.5 20.6 24.7 29.5 33.2 37.1 38.3
  C Condition (25°C - 27/19) EERd   9.6 8.4 7.7 7.7 7.4 7.6 7.3
    Pdc kW 10.6 13.3 15.9 19.0 21.3 23.9 24.6
  D Condition (20°C - 27/19) EERd   16.0 16.9 13.7 14.0 14.1 18.3 18.3
    Pdc kW 9.1 9.3 9.4 8.4 9.5 11.6 11.6
Space heating (Average climate) TBivalent COPd (declared COP)   2.5 2.4 2.0 2.3 2.2 1.9 1.8
    Pdh (declared heating cap) kW 13.7 16.0 18.4 20.6 23.2 27.9 31.0
    Tbiv (bivalent temperature) °C -10 -10 -10 -10 -10 -10 -10
  Space heating (Average climate)-=-E condition (-10°C) Space heating (Average climate)-=-E condition (-10°C)-=-COPd (declared COP)   2.5 2.4 2.0 2.3 2.2 1.9 1.8
    Space heating (Average climate)-=-E condition (-10°C)-=-Pdh (declared heating cap)-=-kW kW 13.7 16.0 18.4 20.6 23.2 27.9 31.0
  TOL Tol (temperature operating limit) °C -10 -10 -10 -10 -10 -10 -10
  A Condition (-7°C) COPd (declared COP)   2.7 2.6 2.4 2.6 2.6 2.4 2.1
    Pdh (declared heating cap) kW 12.1 14.2 16.3 18.2 20.5 24.7 27.4
  B Condition (2°C) COPd (declared COP)   3.9 3.9 3.9 3.5 3.5 3.7 3.6
    Pdh (declared heating cap) kW 7.4 8.6 9.9 11.1 12.5 15.0 16.7
  C Condition (7°C) COPd (declared COP)   6.3 6.4 6.1 6.1 6.3 6.7 6.5
    Pdh (declared heating cap) kW 5.0 5.5 6.4 7.1 8.0 9.7 10.7
  D Condition (12°C) COPd (declared COP)   7.9 8.2 7.9 8.5 8.6 9.0 9.1
    Pdh (declared heating cap) kW 5.9 5.9 6.3 4.9 4.9 7.1 7.1
Space heating (Average climate) recommended combination 2 TBivalent COPd (declared COP)   2.4 2.4 1.9 2.3 2.2 1.9 1.8
    Pdh (declared heating cap) kW 13.7 16 18.4 20.6 23.2 27.9 31
    Tbiv (bivalent temperature) °C -10 -10 -10 -10 -10 -10 -10
  TOL COPd (declared COP)   2.4 2.4 1.9 2.3 2.2 1.9 1.8
    Pdh (declared heating cap) kW 13.7 16 18.4 20.6 23.2 27.9 31
    Tol (temperature operating limit) °C -10 -10 -10 -10 -10 -10 -10
  A Condition (-7°C) COPd (declared COP)   2.7 2.7 2.4 2.6 2.6 2.4 2.2
    Pdh (declared heating cap) kW 12.1 14.2 16.3 18.2 20.5 24.7 27.4
  B Condition (2°C) COPd (declared COP)   3.9 4 3.9 3.5 3.5 3.8 3.7
    Pdh (declared heating cap) kW 7.4 8.6 9.9 11.1 12.2 15 16.7
  C Condition (7°C) COPd (declared COP)   6.3 6.5 6.1 6.1 6.3 6.8 6.5
    Pdh (declared heating cap) kW 5 5.5 6.4 7.1 8 9.7 10.7
  D Condition (12°C) COPd (declared COP)   7.8 8.3 7.9 8.6 8.7 9.1 9.2
    Pdh (declared heating cap) kW 5.9 6 6.4 4.9 5 7.2 7.2
Space heating (Average climate) recommended combination 3 TBivalent COPd (declared COP)   2.5 2.4 2.0 2.3 2.2 1.9 1.8
    Pdh (declared heating cap) kW 13.7 16.0 18.4 20.6 23.2 27.9 31.0
    Tbiv (bivalent temperature) °C -10 -10 -10 -10 -10 -10 -10
  TOL COPd (declared COP)   2.5 2.4 2.0 2.3 2.2 1.9 1.8
    Pdh (declared heating cap) kW 13.7 16.0 18.4 20.6 23.2 27.9 31.0
    Tol (temperature operating limit) °C -10 -10 -10 -10 -10 -10 -10
  A Condition (-7°C) COPd (declared COP)   2.7 2.6 2.4 2.6 2.6 2.4 2.1
    Pdh (declared heating cap) kW 12.1 14.2 16.3 18.2 20.5 24.7 27.4
  B Condition (2°C) COPd (declared COP)   3.9 3.7 3.9 3.5 3.5 3.7 3.6
    Pdh (declared heating cap) kW 7.4 8.6 9.9 11.1 12.5 15.0 16.7
  C Condition (7°C) COPd (declared COP)   6.2 6.4 6.0 6.1 6.2 6.5 6.3
    Pdh (declared heating cap) kW 4.9 5.5 6.4 7.1 8.0 9.7 10.7
  D Condition (12°C) COPd (declared COP)   7.8 8.1 7.8 8.5 8.6 8.7 8.7
    Pdh (declared heating cap) kW 5.8 5.9 6.2 4.9 4.9 6.9 6.9
Indoor index connection Min.   100 125 150 175 200 225 250
  Max.   260 325 390 455 520 585 650
Dimensions Unit Height mm 1,685 1,685 1,685 1,685 1,685 1,685 1,685
    Width mm 930 930 930 1,240 1,240 1,240 1,240
    Depth mm 765 765 765 765 765 765 765
Weight Unit kg 201 201 201 281 281 314 314
Fan External static pressure Max. Pa 78 78 78 78 78 78 78
Compressor Type   Hermetically sealed scroll compressor Hermetically sealed scroll compressor Hermetically sealed scroll compressor Hermetically sealed scroll compressor Hermetically sealed scroll compressor Hermetically sealed scroll compressor Hermetically sealed scroll compressor
Operation range Cooling Min. °CDB -5 -5 -5 -5 -5 -5 -5
    Max. °CDB 43 43 43 43 43 43 43
  Heating Min. °CWB -20 -20 -20 -20 -20 -20 -20
    Max. °CWB 15.5 15.5 15.5 15.5 15.5 15.5 15.5
Sound power level Cooling Nom. dBA 78.0 (4) 79.1 (4) 83.4 (4) 80.9 (4) 85.6 (4) 83.8 (4) 87.9 (4)
Sound pressure level Cooling Nom. dBA 57 57 61 60 63 62 65
Refrigerant Type   R-410A R-410A R-410A R-410A R-410A R-410A R-410A
  GWP   2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5
  Charge tCO2Eq 12.3 12.5 13.2 21.5 23.6 24.4 24.6
  Charge kg 5.9 6 6.3 10.3 11.3 11.7 11.8
Piping connections Liquid Type   Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection
    OD mm 9.52 9.52 12.7 12.7 12.7 15.9 15.9
  Gas Type   Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection Braze connection
    OD mm 19.1 22.2 28.6 28.6 28.6 28.6 28.6
  Total piping length System Actual m 1,000 (6) 1,000 (6) 1,000 (6) 1,000 (6) 1,000 (6) 1,000 (6) 1,000 (6)
Power supply Name   Y1 Y1 Y1 Y1 Y1 Y1 Y1
  Phase   3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~
  Frequency Hz 50 50 50 50 50 50 50
  Voltage V 380-415 380-415 380-415 380-415 380-415 380-415 380-415