| RXYSQ4T8YB9 | RXYSQ5T8YB9 | RXYSQ6T8YB9 | |||||
|---|---|---|---|---|---|---|---|
| Sound pressure level | Cooling | Nom. | dBA | 50.0 (5) | 51.0 (5) | 51.0 (5) | |
| Standard Accessories | Installation manual | 1 | 1 | 1 | |||
| Operation manual | 1 | 1 | 1 | ||||
| Connection pipes | 1 | 1 | 1 | ||||
| Capacity range | HP | 4 | 5 | 6 | |||
| Operation range | Cooling | Max. | °CDB | 46.0 | 46.0 | 46.0 | |
| Min. | °CDB | -5.0 | -5.0 | -5.0 | |||
| Heating | Min. | °CWB | -20.0 | -20.0 | -20.0 | ||
| Max. | °CWB | 15.5 | 15.5 | 15.5 | |||
| ηs,c | % | 269.2 | 260.5 | 268.3 | |||
| Maximum number of connectable indoor units | 64 (3) | 64 (3) | 64 (3) | ||||
| Space cooling | B Condition (30°C - 27/19) | Pdc | kW | 8.9 | 10.3 | 11.4 | |
| EERd | 5.2 | 4.8 | 4.8 | ||||
| D Condition (20°C - 27/19) | Pdc | kW | 4.3 | 4.5 | 4.6 | ||
| EERd | 13.0 | 14.2 | 15.1 | ||||
| A Condition (35°C - 27/19) | EERd | 3.1 | 2.6 | 2.6 | |||
| Pdc | kW | 12.1 | 14.0 | 15.5 | |||
| C Condition (25°C - 27/19) | EERd | 9.3 | 8.9 | 9.1 | |||
| Pdc | kW | 5.7 | 6.6 | 7.3 | |||
| SCOP | 3.9 | 4.2 | 4.4 | ||||
| Compressor | Type | Hermetically sealed swing compressor | Hermetically sealed swing compressor | Hermetically sealed swing compressor | |||
| Weight | Unit | kg | 104 | 104 | 104 | ||
| Refrigerant | GWP | 2,087.5 | 2,087.5 | 2,087.5 | |||
| Charge | kg | 3.6 | 3.6 | 3.6 | |||
| Type | R-410A | R-410A | R-410A | ||||
| Power input - 50Hz | Heating | Nom. | 6°CWB | kW | 2.68 (2) | 3.27 (2) | 3.97 (2) |
| Indoor index connection | Min. | 50.0 | 62.5 | 70.0 | |||
| Max. | 130.0 | 162.5 | 182.0 | ||||
| Cooling capacity | Prated,c | kW | 12.1 (1) | 14.0 (1) | 15.5 (1) | ||
| COP at nom. capacity | 6°CWB | kW/kW | 4.52 | 4.28 | 3.90 | ||
| Recommended combination | 3 x FXSQ25A2VEB + 1 x FXSQ32A2VEB | 4 x FXSQ32A2VEB | 2 x FXSQ32A2VEB + 2 x FXSQ40A2VEB | ||||
| Space heating (Average climate) | TOL | COPd (declared COP) | 2.4 | 2.4 | 2.5 | ||
| Pdh (declared heating cap) | kW | 8.0 | 9.2 | 10.2 | |||
| Tol (temperature operating limit) | °C | -10 | -10 | -10 | |||
| D Condition (12°C) | Pdh (declared heating cap) | kW | 4.1 | 4.1 | 4.3 | ||
| COPd (declared COP) | 7.0 | 7.6 | 8.1 | ||||
| B Condition (2°C) | COPd (declared COP) | 3.6 | 3.8 | 4.0 | |||
| Pdh (declared heating cap) | kW | 4.3 | 5.0 | 5.5 | |||
| C Condition (7°C) | COPd (declared COP) | 5.7 | 6.1 | 6.5 | |||
| Pdh (declared heating cap) | kW | 3.4 | 3.5 | 3.6 | |||
| A Condition (-7°C) | COPd (declared COP) | 2.7 | 2.8 | 2.9 | |||
| Pdh (declared heating cap) | kW | 7.0 | 8.1 | 9.0 | |||
| TBivalent | Pdh (declared heating cap) | kW | 8.0 | 9.2 | 10.2 | ||
| Tbiv (bivalent temperature) | °C | -10 | -10 | -10 | |||
| COPd (declared COP) | 2.4 | 2.4 | 2.5 | ||||
| Piping connections | Liquid | OD | mm | 10 | 10 | 10 | |
| Type | Flare connection | Flare connection | Flare connection | ||||
| Total piping length | System | Actual | m | 300 (6) | 300 (6) | 300 (6) | |
| Gas | OD | mm | 15.9 | 15.9 | 19.1 | ||
| Type | Flare connection | Flare connection | Braze connection | ||||
| SEER | 6.8 | 6.6 | 6.8 | ||||
| Sound power level | Cooling | Nom. | dBA | 68.0 (4) | 69.0 (4) | 70.0 (4) | |
| Dimensions | Unit | Width | mm | 900 | 900 | 900 | |
| Depth | mm | 320 | 320 | 320 | |||
| Height | mm | 1,345 | 1,345 | 1,345 | |||
| ηs,h | % | 154.4 | 164.5 | 174.1 | |||
| Heating capacity | Prated,h | kW | 12.1 (2) | 14.0 (2) | 15.5 (2) | ||
| Nom. | 6°CWB | kW | 12.1 (2) | 14.0 (2) | 15.5 (2) | ||
| Power supply | Phase | 3N~ | 3N~ | 3N~ | |||
| Name | Y1 | Y1 | Y1 | ||||
| Frequency | Hz | 50 | 50 | 50 | |||
| Voltage | V | 380-415 | 380-415 | 380-415 | |||
| Notes | (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m | (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m | (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m | ||||
| (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m | (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m | (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m | |||||
| (3) - Actual number of units depends on the indoor unit type (VRV DX indoor, RA DX indoor, etc.) and the connection ratio restriction for the system (being; 50% ≤ CR ≤130%). | (3) - Actual number of units depends on the indoor unit type (VRV DX indoor, RA DX indoor, etc.) and the connection ratio restriction for the system (being; 50% ≤ CR ≤130%). | (3) - Actual number of units depends on the indoor unit type (VRV DX indoor, RA DX indoor, etc.) and the connection ratio restriction for the system (being; 50% ≤ CR ≤130%). | |||||
| (4) - Sound power level is an absolute value that a sound source generates. | (4) - Sound power level is an absolute value that a sound source generates. | (4) - Sound power level is an absolute value that a sound source generates. | |||||
| (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. | (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. | (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. | |||||
| (6) - Refer to refrigerant pipe selection or installation manual | (6) - Refer to refrigerant pipe selection or installation manual | (6) - Refer to refrigerant pipe selection or installation manual | |||||
| (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB | (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB | (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB | |||||
| (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. | (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. | (8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. | |||||
| (9) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. | (9) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. | (9) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. | |||||
| (10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). | (10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). | (10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). | |||||
| (11) - TOCA means the total value of each OC set. | (11) - TOCA means the total value of each OC set. | (11) - TOCA means the total value of each OC set. | |||||
| (12) - FLA means the nominal running current of the fan | (12) - FLA means the nominal running current of the fan | (12) - FLA means the nominal running current of the fan | |||||
| (13) - The automatic ESEER value corresponds with normal VRV IV-S heat pump operation, including the advanced energy saving functionality (variable refrigerant temperature control). | (13) - The automatic ESEER value corresponds with normal VRV IV-S heat pump operation, including the advanced energy saving functionality (variable refrigerant temperature control). | (13) - The automatic ESEER value corresponds with normal VRV IV-S heat pump operation, including the advanced energy saving functionality (variable refrigerant temperature control). | |||||
| (14) - The standard ESEER value corresponds with normal VRV IV-S heat pump operation, not taking into account the advanced energy saving functionality. | (14) - The standard ESEER value corresponds with normal VRV IV-S heat pump operation, not taking into account the advanced energy saving functionality. | (14) - The standard ESEER value corresponds with normal VRV IV-S heat pump operation, not taking into account the advanced energy saving functionality. | |||||
| (15) - Sound values are measured in a semi-anechoic room. | (15) - Sound values are measured in a semi-anechoic room. | (15) - Sound values are measured in a semi-anechoic room. | |||||
| (16) - Maximum allowable voltage range variation between phases is 2%. | (16) - Maximum allowable voltage range variation between phases is 2%. | (16) - Maximum allowable voltage range variation between phases is 2%. | |||||
| (17) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | (17) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | (17) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | |||||
| (18) - For detailed contents of standard accessories, see installation/operation manual | (18) - For detailed contents of standard accessories, see installation/operation manual | (18) - For detailed contents of standard accessories, see installation/operation manual | |||||
| (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase | (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase | (19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase | |||||
| (20) - Ssc: Short-circuit power | (20) - Ssc: Short-circuit power | (20) - Ssc: Short-circuit power | |||||