Specifications Table for RKHBRD-ADY17 / RRRQ-AY1

RKHBRD011ADY17 / RRRQ011AAY1 RKHBRD014ADY17 / RRRQ014AAY1 RKHBRD016ADY17 / RRRQ016AAY1
Heating capacity Nom. kW 11.3 (1), 11.0 (2), 11.2 (3) 14.5 (1), 14.0 (2), 14.4 (3) 16.0 (1), 16.0 (2), 16.0 (3)
Power input Heating Nom. kW 3.80 (1), 4.40 (2), 2.67 (3) 5.02 (1), 5.65 (2), 3.87 (3) 5.86 (1), 6.65 (2), 4.31 (3)
COP 2.97 (1), 2.50 (2), 4.20 (3) 2.89 (1), 2.48 (2), 3.72 (3) 2.73 (1), 2.41 (2), 3.72 (3)
Notes (1) - EW 55°C; LW 65°C; Dt 10°C; ambient conditions: 7°CDB/6°CWB (1) - EW 55°C; LW 65°C; Dt 10°C; ambient conditions: 7°CDB/6°CWB (1) - EW 55°C; LW 65°C; Dt 10°C; ambient conditions: 7°CDB/6°CWB
  (2) - EW 70°C; LW 80°C; Dt 10°C; ambient conditions: 7°CDB/6°CWB (2) - EW 70°C; LW 80°C; Dt 10°C; ambient conditions: 7°CDB/6°CWB (2) - EW 70°C; LW 80°C; Dt 10°C; ambient conditions: 7°CDB/6°CWB
  (3) - EW 30°C; LW 35°C; Dt 5°C; ambient conditions: 7°CDB/6°CWB (3) - EW 30°C; LW 35°C; Dt 5°C; ambient conditions: 7°CDB/6°CWB (3) - EW 30°C; LW 35°C; Dt 5°C; ambient conditions: 7°CDB/6°CWB